IEC 60227 or IEC 60245. Mains supply cables certified or approved by a recognized testing authority are regarded as meeting this requirement. SVERKER 650 ZP-BA01E BA0143KE...
Page 5
Unplug the instrument from the mains supply when it is left unattended or not in use. Refer all servicing to Megger authorized personnel. If you need to return the instrument, please use either the original crate or one of equivalent strength...
2 INTRODUCTION Introduction The SVERKER 650 is a rugged instrument but it still should be handled with care. The relay testing unit is electrically fully isolated in all measuring ranges, except for the mains output. The set of resistors is not connected with the rest of the relay testing unit set.
Page 7
3 CONTROl PANEl BA0143KE ZP-BA01E SVERKER 650...
▪ load regulation 3 % ▪ line regulation less than 4 % 110 V 0.3 A 110-125 V CA Capacitor 10 μf/450 V AC for reactive power relays Automatic cut-out for the mains voltage, 4 A SVERKER 650 ZP-BA01E BA0143KE...
Page 9
Voltage adjustment terminal U6 Terminal for connection of a resistor on the primary side of the output transformer Terminal for an external ammeter Terminal for external start and stop of timer Terminal for starting external operation BA0143KE ZP-BA01E SVERKER 650...
Read the manual and comply with the 0-10 A (85 V), 0-40 A (25 V) or 0-100 A (10 V). Safety instructions, see page 5, before us- ing SVERKER 650. Increase the current to the operating value Always comply with local safety regula- using the variable transformer.
Use an external measuring instrument for using the variable transformer. better accuracy. Check the current on the ammeter or exter- nal instrument during the test. Note Shift polarity of the voltage or current if func- tion has failed to appear. BA0143KE ZP-BA01E SVERKER 650...
Note The timer can be started externally by a make at terminal (W3). The switch (S1) should then be in position “ON+TIME” or “OFF+TIME”. When using the timer internally, the terminal (W3) has to be short-circuited. SVERKER 650 ZP-BA01E BA0143KE...
Connect the tripping circuit. Set the changeover switch for time measure- ment in position make/break. Set the switch in position “ON”. Increase the voltage/current until the relay picks up. Then set the switch in position “OFF + TIME”. BA0143KE ZP-BA01E SVERKER 650...
5 SPECIfICATIONS Specifications Specifications SVERKER 650 Outputs Current outputs, CA Specifications are valid at nominal input voltage and an ambient Range No-load Output Load / un- temperature of +25°C, (77°f). Specifications are subject to voltage voltage (min) load times On change without notice.
Page 16
▪ Insulation Power Factor (C&DF) Test Equipment worldwide. ▪ Insulation Resistance Test Equipment Megger is certified according to ISO 9001 and 14001. ▪ Line Testing Equipment Megger is a registered trademark. ▪ Low Resistance Ohmmeters ▪...
Need help?
Do you have a question about the SVERKER 650 and is the answer not in the manual?
Questions and answers