Note:
This luminaire (with reinforced insulation between control/LED terminal and AC supply) contains non-user
replaceable light source and battery - to be replaced (if required, refer installation instructions for battery
replacement) by Clevertronics service personnel/agents or a registered electrician.
Battery Replacement:
1.
Prior to any work, isolate the power to the luminaire that requires battery replacement.
2.
Disengage the slide connect bracket from the exit body.
3.
Remove Cover Plate.
4.
Remove cable tie holding the battery and remove the Battery Connector from the Emergency
Driver.
5.
Replace battery, connect to Emergency Driver and secure with cable tie.
6.
Replace Cover Plate and reinstall the fitting.
Testing Procedure:
When the unit is connected to the un-switched active, it must be allowed to charge the battery for at
least 24 hours. The emergency lamp only illuminates during a power fail. Conduct the following tests:
The emergency lamp must illuminate for at least 180 min after disconnection from the mains. If the
unit fails to illuminate for the requisite time, remedial action must be taken to repair the situation
and once completed, the unit must pass a subsequent test.
Press and hold Test Button*, the product will go into Dynamic Green mode.
NOTE: Initiating a Function or Duration test using the Zoneworks Software will trigger Dynamic Green for
completion of the test.
*The Test button needs to be held for longer than 1 seconds for the product to go into Emergency Mode.
Trouble Shooting:
Below are a list of common problems and their possible causes.
Fault:
The Green LED Test Switch indicator is not illuminated.
Check:
A.C. is connected and is turned on.
Battery is connected
Test Switch for damage.
Fault:
Lamp does not illuminate in emergency mode.
Check:
A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault:
Lamp illuminates in emergency mode, but only stays on for a short period.
Check:
Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Fault:
The Dynamic Green is not sequencing.
Check:
The 24 Volt/VF control is connected and turned on.
Polarity of 24V control.
Check that the correct interface control is selected.
Warranty:
For Product Warranty information and Terms and Conditions of Sales please refer to our website
https://clevertronics.co.uk/product-warranty-statement/
UK Instruction Sheet Template – V1.1 – Updated: 20/11/2020
CLP™ Cleverfit Pro Dynamic Green
Installation & Maintenance Instruction Leaflet
Models:
DYGC-xCP-uu-vv-ww-xx-yy-zz
Testing:
Zoneworks
xx = ZW
Z/W DATA
xx = DATA
Zoneworks HIVE
xx = HVG
Normally Open
xx=NO
Normally Closed
xx=NC
Activated Only by Fire Panel xx=AOFP
Weatherproof
x=W
Spare Parts:
1550030
BATT: LP 3.2V 3200mAh 300mm lead,noBRKT
8002927
PCA: DYxx Driver Board #CT10142-L9
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation,
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in
accordance with the relevant British Standards.
Clevertronics Pty Ltd is a vendor of CleverEVAC products. It is not a fire engineer or designer. It does not
purport to recommend its products for use in any particular application or to achieve any particular
outcome. Purchasers and users of its products must take their own steps to ensure compliance with
statutory requirements, safe practice and suitable application of the products.
Australia (Head Office)
Website:
www.clevertronics.com.au
Email: info@clevertronics.com.au
Phone: +61 3 9559 2700
Fax: +61 3 9559 2799
UK OFFICE
Website:
www.clevertronics.co.uk
362 Stockley Close
West Drayton UB7 9BL
Phone: 01895 430 255
Options:
Running man with right arrow
yy=RR
Running man with left arrow
yy=RL
Running man with Up arrow
yy=RU
Running man with down arrow yy=RD
Double sided Running Man Arrow yy=DS-RAOW
Dynamic Green Disabled
uu=DDG
Theater Mask
vv=TH
SoundEscape module
ww=SND
Black
zz=BLK
1949393
V1.0
1 December 2021

Advertisement

loading
Need help?

Need help?

Do you have a question about the CleverEVAC CLP Cleverfit Pro Dynamic Green and is the answer not in the manual?

Questions and answers

Summary of Contents for Clevetronics CleverEVAC CLP Cleverfit Pro Dynamic Green

  • Page 1 Note: This luminaire (with reinforced insulation between control/LED terminal and AC supply) contains non-user replaceable light source and battery - to be replaced (if required, refer installation instructions for battery replacement) by Clevertronics service personnel/agents or a registered electrician. CLP™ Cleverfit Pro Dynamic Green Battery Replacement: Installation &...
  • Page 2 Installation: Selecting the Type of the Interface The CLP Cleverfit Pro Dynamic Green can be installed either Ceiling or Wall Mounted. The CLP Cleverfit The fitting comes pre-set to the Volt Free (VF) control interface, to change this to 24V you will have to Pro Dynamic Green uses a “slide connect bracket base”...