Mounting
January 2023
3.7.1 
Perform loop current test using AMS Device Manager
(Fixed Voltage Drop)
Figure 3-19: AMS Device Manager Configure Screen
Procedure
1. Right-click on the THUM Adapter and select Configure.
2. When the menu opens, select Manual Setup from the window on the left and select
3. Make sure the Time drop down menu at the bottom of the page has Current
4. Under the Voltage Drop drop down menu in the Smart Power Options box, select
5. Select Apply to make any changes.
34
the Wired Device tab on the top.
selected.
Fixed Voltage Drop.
Reference Manual
00809-0100-4075
Emerson.com/Rosemount