2.0
Installation
•
Outdoor Application
Chart 2.1 •
Outdoor Comfort Heating Application Chart
Heat Pattern
Mounting
Height
1 kW
7 feet
8 x 10
8 feet
9½ x 11½
9 feet
10½ x 12½
10½ x 13
10 feet
-
11½ x 14½ 11½ x 15½ 11½ x 16½
11 feet
-
12½ x 15
12 feet
-
13 feet
-
14 feet
-
15 feet
-
Chart 2.2 •
Indoor Spot Heating Application Chart
Heater installation shall comply with all IOPM, NEC, ANSI/NFPA-70, CEC, and local restrictions.
When comfort heating people, two heaters should be used to heat both sides of the individual. Heater
installation shall comply with all IOPM, NEC, ANSI/NFPA-70, CEC, and local restrictions.
*Clearances to combustibles must be maintained at all times. If infrared heaters are mounted too low or too
high, they may result in discomfort or lack of heat.
Figure 2.1
•
Heating Application
12 INCHES
18 INCHES
24 INCHES
Areas Heated in Feet
1.75 kW
2.5 kW
3 & 4 kW
8 x 11
8 x 12
9½ x 12
9½ x 13
9½ x 14½
10½ x 14
10½ x 15½
12½ x 16
12½ x 17½
-
14 x 18
-
15 x 18.9
-
-
-
-
17½ x 22½
Estimating Required Loading
Type of Building
Insulated building
Uninsulated
Outdoor Sheltered
Outdoor Unsheltered
Watts Density At Floor Level
Mounting
Height
7 feet
8 x 13
8 feet
9 feet
10 feet
11 feet
12 feet
14 x 19
13 feet
15 x 20
14 feet
16 x 21
15 feet
Watts Required Per Square Foot At Floor Level
25-30
10
BAH Series Manual
Density in Watts
1 kW
1.75 kW 2.5 kW
12.4
20.0
26.5
9.2
16.1
20.1
7.6
13.4
16.8
-
11.1
14.5
-
9.3
12.5
-
-
10.0
-
-
8.8
-
-
-
-
-
-
10
16
45
3 kW
4 kW
28.8
38.4
22.0
29.4
18.6
24.9
16.0
21.6
14.0
18.7
11.2
15.0
10.0
13.3
8.9
11.9
-
10.9