  • Page 2 Safety precautions Operation 1. Before usingthis product, please read "safety precautions" carefully to ensure correct and safe use, and please keep the manual properly. 2. Duringoperation, please pay attention to all warning signsand operate as required. 3. Donot use the device in direct sunlight,rain or the humidenvironment. 4.
  • Page 3: Table Of Contents

    Content 1. Introduction ............................1 1.1Symbol ...........................1 1.2Rear view..........................2 1.3Specification .........................3 1.4Electromagnetic compatibility ....................4 2. Installation ............................5 2.1Unpackinginspection......................5 2.2Wiring schedule........................5 2.3UPS connection........................5 2.4External battery connection of longbackup type UPS............6 2.5Connectionto the computer ....................7 3. ControlPanel ............................8 3.1Panel display ........................8 3.2Function of button .......................9 3.3UPS workingstatus table of LCDdisplay ................10 3.4Parameter query ........................11...
  • Page 4: Introduction

    1. Introduction This series of UPS is an online sine wave uninterruptible power supply system with bypass maintenance switch, which can provide reliable and high-quality ACpower for your precision equipment. It can be used in a wide range, from computer equipment, communication system to industrial automatic control equipment.
  • Page 5: Rearview

    1.2 Rearview 6KL/10KL(ISO) 6KS/10KS(ISO) Computerinterface Smart slot(optional) External battery connection " USB port # Input breaker $ Maintenance bypassbreaker % Terminal block & Parallel kit (optional) Output breaker ⑪ Battery breaker www.lbspower.com...
  • Page 6: Specification

    1.3 Specification Model 10KS 10KL Capacity 6kVA/6kW 10kVA/10kW Input Nominal Voltage 208/220/230/240VAC, L1+L2+PE Voltage Range 100-300VAC Frequency 40-70Hz ) 0.99 Power Factor THDi ≤5% (linear load); ≤8% (non-linearload) Output Nominal Voltage 208/220/230/240VAC or 110/115/120VAC, L1+N1+L2+N2+PE Voltage Regulation ± 1 % Frequency 50/60Hz±0.1% Crest Ratio...
  • Page 7: Electromagneticcompatibility

    Load at highaltitude=Rated power *Derating factor (corresponding to altitude) Altitude(m) 1000 1500 2000 2500 3000 3500 4000 4500 5000 Derating factor 100% Notice: If the machine is used at above 1000m,diminishing ratings output must be used, please refer to above table for derating factor. 1.4 Electromagneticcompatibility Safety IEC/EN 62040-1-1...
  • Page 8: Installation

    2. Installation Warning: Toensure safety,please pay attention to cut off the ACbreaker before installation. The battery breaker also need to be cut off, if its a long backuptime model. Caution: 1. Installation and wiring must be performed by professionalpersonnel in accordance with local regulations.
  • Page 9: External Battery Connection Of Longbackup Type Ups

    Warning: When you are connecting the wire, please make sure that the input, output wire and the input, output terminals are connected tightly. Terminals block: 6. Reinstall the cover and lockthe cover with a screwdriver . 7. After connectingthe wire and AC,then put the UPS input breakerto "ON", the UPS will be powered.
  • Page 10: Connectionto The Computer

    Warning: Please do not connect to the terminals of UPS first, otherwise you mayencounter the hazardousof electric shock. 3. Connect the other end of the battery cable to the UPS, and then connect to the battery pack. TheUPS does not connect any load first, and then turns the battery pack switch to "ON", then turn on AC,the UPS beginsto charge.
  • Page 11: Controlpanel

    3. ControlPanel 3.1 Panel display Display Function Error message FAULT Failure occurred Warnings Fault code Mute Mute function Input and output voltage, DCvoltage, UPS internal temperature VAC:input and output voltage; VDC: DCvoltage ℃ : UPS internal temperature; Hz:Frequency Load information The load volume(0-25%, 26%-50%, 51%-75%, 76%-100%) is shown here, and the overload icon flashes when the battery is low or not connected Battery information...
  • Page 12: Function Ofbutton

    3.2 Function ofbutton Button Functional Description Combokey for turningon the UPS ACMode: press the two buttons at the same time for 1 secondabove to start UPS. Battery Mode: please press confirmation button first, after turning onthe screen, please press the two buttons at the same time for 1 second above to start UPS.
  • Page 13: Ups Workingstatus Table Of Lcddisplay

    3.4 UPS workingstatus table of LCDdisplay ACMode LCDdisplay content Instruction UPS can provide stable ACoutput when ACinput in the permissible range. In ACMode, batteries will also be chargedby the UPS. Battery Mode LCDdisplay content Instruction When the ACinput is out of limited rangeor shut off,the UPS will turn to Battery Mode.
  • Page 14: Parameter Query

    3.5 Parameter query Normally the LCD display can show 8 pages totally. Pressing the query button 0.1-2sec can enter into the different pages which show all information, such as input, battery, output, load, software version, temperature, and etc. If alarms occur, the display will add one more pageto show the alarm information.
  • Page 15: Function Setting

    3.6 Function setting 01: Output voltage LCDDisplay Setting 1. Press the function setting button over 2 sec, then goto the setting page.Press the page turning buttons till the setting page ofoutput voltage, and the word "OPU" flashing. 2. Press confirmation button 0.5-2sec, then go to the setting page of output voltage OPU.
  • Page 16 02-2Battery low voltage shutdown point/End of discharge voltage (EOD) LCDDisplay Setting The options of EOD setting are dEF, 9.8V,9.9V,10V,10.2V,10.5V. By default, the EOD is dEF (The EOD will be changed accordingto loading condition. 10.5V@load<25%,10.2V@25%<load<50%,10V@load> 50%). 02-3:Economic Operation Mode LCDDisplay Setting ECOis OFF by default, can be set as ONto improve the efficiency of system operation.
  • Page 17 02-5:Battery quantity (PCS) LCDDisplay Setting When EP is set to ON, the PCSoption appears onthe function setting page,will enter the password page,enter the password (the general passwordis 135),you can set the number of batteries. The default battery number is 16pcs,which can be set to 16/18/20pcs.
  • Page 18: Warning Code/Faultcode Andsolution

    4. Warning code/fault codeand solution 4.1 Warning code andsolution " When the " symbolon the UPS LCDflashes, the UPS is in alarm state. Press the page turning key to the error state page (refer to 3.5), observe the alarm code and makeappropriate processingaccording to the table below.
  • Page 19: Fault Code Andsolution

    4.2 Fault code andsolution " When the "FAULT"is longbright, and" symbolon the UPS LCDflashes, the UPS is in fault state. UPS automatically switches to the error status page(refer to 3.5) to observe the fault code and makeappropriate processingaccording to the following table. Fault Indication Possible reasons...
  • Page 20 Negative power 1. Bypass reverses to the Checkthe loads and if no abnormal, protection(output inverter. please contact the supplier. with ACinput fail) 2. load abnormal Inv relay or SCR Relay RL8 is damaged. Please contact the supplier. open circuit Inv relay or SCR short circuit Bypass relay or Relay RL4/RL6is damaged.
  • Page 21: Commonfaults And Trouble Shooting

    4.3 Commonfaults and trouble shooting Number Problem or errors description Reason Solution Connectto city electricity, No input power Checkif the input wiring and no display on LCDdisplay harness of UPS is in well panel connection. Input voltage under Use voltage meter to checkthe voltage or overload input voltage if in normal or meets the requirement.
  • Page 22: Controland Communication

    5. Control andcommunication UPS includes several communicationports: RS232,EPO,SNMP card, USB, and dry contact card. NOTICE: Only one of SNMP card, and dry contact card can be used at the same time. Only one of RS232and USB is available at the sametime. 5.1 SNMP Card SNMP card is used to monitor the UPS via TCP/IPprotocol, users can check the UPS status and data online.
  • Page 23: Epo

    5.3 EPO Theremote EPO is located onthe rear panel of UPS. Its normal closed,if its open, it will active EPO function, the UPS will shutdown output. www.lbspower.com...
  • Page 24: Battery Maintenance& Repair

    6. Battery Maintenance& Repair (1) Thisseries of UPS only needsvery little maintenance. Thebatteries of the standard machine are seal type and no need to maintain frequently. But also keepchargingto get the expected battery life. UPS keepschargingwhen it is connecting to AC,no matter on/off.And if also have function of over chargingand overload protection.