ABB COM600 4.0 Operation Manual page 28

Grid automation controller
Table of Contents

Advertisement

Grid Automation Controller COM600 4.0
1MRS757279
FDIR Operation Manual
Example case
In Figure 3.7.6-1, if the fault is detected in IED1, FDIR attempts to isolate the switch
IED2 and restore the switch IED3. When IED3 is closed, the load exceeds the threshold
setting for the current group, see Figure 3.7.6-2. For more information on configuring
the protection settings group, see FDIR Configuration Manual.
Threshold_Setting_Group1.png
Figure 3.7.6-2 Setting Group 1 – Threshold is set at 289
28