Prosense PPS‐RCO Quick Installation Guide 
General Specification
PPS‐RCO Series Detector Electrical Specifications: 
Input Voltage Range 
Max Power Consumption  0.96 Watts at 16VDC ‐ normal condition 
  
Terminals 
Relays 
Communication 
Sensor 
Detector Body Specifications: 
Material 
Weight 
Mounting 
Entries 
Environmental: 
IP Rating 
Operating Temperature 
Operating Humidity 
Operating Pressure 
Storage Conditions 
 
 
PRS‐QIG‐PQ‐EN‐Rev.01‐11.2018 
12 to 20VDC (16VDC nominal) 
1.60 Watts at 16VDC ‐ alarm and fault condition 
4 x 2 x screw terminals suitable for wire diameter 1.5mm2 to 2.5mm2 
3 x (1A 30VDC, 0.5A 125VAC, 0.3A 80VDC). 
Non‐selectable: normally open and de‐energized 
RS485, Modbus RTU 
Electrochemical 
Table 2: PPS‐RCO Series detectors electrical specifications 
Plastic (black) 
Plastic buat: 230g (with Sensor Header) 
Wall mounting 
PG11 
Table 3: Detector body specifications 
IP54 (plastic buat)  
‐10ºC to +50ºC / 14ºF to +120ºF 
Continuous 20‐90%RH (non condensing) 
 
90‐110kPa 
‐10°C to +50°C (14°F to +120°F) 
Table 4: Environmental specifications 