Prosense PPS‐RCO Quick Installation Guide 
System Status
Prosense PPS‐RCO Series detectors has four LEDs on main board. Power LED (green) shows 
system power status and yellow LED shows fault status. Fault relay will be activated and 
Fault LED (yellow) will start flashing right after power applied. After appoximitly 90 sec the 
yellow LED will be turned of and only power LED (green) will start blinking. This status means 
that detector is ready to normal operation. In case of fault power LED (green) will contiune 
blinking and fault LED (yellow) will be lit solid. The alarm LEDS (red) will be activated when 
detector measures gas level at alarm thresholds and also activate related alarm LEDs.
First time switch on (Commissioning)
WARNING 
The following procedure requires the detector cover to be removed while carrying out 
supply voltage checks. Therefore the appropriate permits to work should be sought in 
preparation. Prior to carrying out any HOT WORK ensure local and site procedures are 
followed. Ensure that the associated control panel output actuation is inhibited so as to 
prevent false alarms. 
Caution: The following procedure should be followed carefully and only performed by 
suitably trained personnel 
 
1. Remove the detector cover  
2. Make sure the detector's output and power input connections done correctly 
3. Check that all electrical connections are terminated correctly 
4. Switch On the external power supply to feed the detector. If it is connected to DP32 
Panel, cables should be installed according to DP32 Panel user manual as panel can 
provide both power and communication connections to the detectors. 
5. Using a Digital Multi Meter (DMM), check the Supply Voltage at the terminals V+ and V‐ 
this should be a minimum supply voltage of 12VDC (Maximum supply voltage is 24VDC).  
6. Check LED status on detector main board. LED status should be like explained above 
after applying power. 
7. Wait two minutes and confirm detector LED status pointing normal operation. If 
detectors used with DP32 Panel, panel should recognise each detector correctly at their 
addresses. 
8. Switch Off the external power to the detector. 
9. Fit the cover and make sure non of the cables cause an obstruction while fitting cover 
10. Switch on external power to the detector or panel if used.  
 
PRS‐QIG‐PQ‐EN‐Rev.01‐11.2018 
 