(5) Details of Wiring Outlets inside the Electrical Box (Rubber Bush Section)
Rubber Bush (Wiring Outlet)
Correct
Rubber Bush
Electrical Box
(Metal)
Using a cutter knife, cut an X in the rubber bush on site as shown below.
Make sure that the power source wiring
passes through the center of the rubber bush.
Correct
Rubber Bush
Rubber
If the power source wiring does not pass through
Bush
properly, snow or water may enter in the unit.
CAUTION
Be sure to note the following points to run the
cables under the unit using conduit tube.
(The pipe cover needs to be removed before
performing piping and wiring works.)
NOTES:
Do not run the power supply wiring and
communication wiring through the same conduit
tube.
Moreover, keep at least 5cm between the power
supply wiring and communication wiring.
Pull out each wire from each corresponding knockout
hole. Cut an "X" in rubber bush (accessory) and
securely attach it to the knockout hole for cable
protection.
Check that the rubber bush is surely attached.
Attach the pipe cover to prevent rats or other small
animals from entering the unit.
Prevent the wirings from touching or rubbing against
the refrigerant pipes, plate edges and electrical parts
inside the unit.
When the power source cable (cabtyre cable) whose
size exceeds 38mm
the cable, put into the unit and run it. At this time, do
not damage the coated insulating part.
Completely seal the end of conduit tube with sealing
materials to prevent the rain from entering the conduit
tube.
Make a drain hole at the lowest part of the conduit
tube.
A16381E84N-rev.1
Incorrect
Make sure that the rubber bush
is in place.
Incorrect
Snow or water
may enter.
2
is used, peel the sheath part of
CAUTION
Tightly secure the power source wiring using a
cord clamp inside the unit.
NOTE:
Fix the rubber bushes with adhesive when conduit
tubes to the outdoor unit are not used.
< Heat Pump >
Communication Wiring
Power Source Wiring
< Heat Recovery >
Communication Wiring
Power Source
Wiring
Rubber Bush

6.3 Electrical Wiring Connection

WARNING
The ELB (earth leakage breaker), FUSE and S (main
switch) must be installed for each outdoor unit and
also for each indoor unit group. If not, it may cause
an electrical shock or fire.
Perform the electrical work according to the
regulation of each region and the Installation and
Maintenance Manual, and the dedicated electrical
circuit must be used. If the electrical wiring work
is performed incorrectly or there is a capacity
shortage of the power circuit, it will damage
electrical parts and cause an electric shock or a
fire.
Check that the ground wire is securely connected.
If the unit is not correctly grounded, it may lead to
an electrical shock.
Do not connect the ground wiring to a gas piping,
water piping, lighting conductor or ground wiring
for telephone.
The power sources for the indoor unit and outdoor
unit should be supplied respectively.
The power source for each indoor unit group
should be supplied respectively.
6. Electrical Wiring
Liquid Pipe
Gas Pipe
Rubber Bush
Liquid Pipe
High/Low Pressure Gas Pipe
Low Pressure Gas Pipe
82