Evaporator Blower and Motor (EBM)
•
Twin blower and motor.
•
Pulls cabinet air through evaporator and discharges cooled air back to cabinet.
•
Squirrel cage blower design.
•
Blower and motor combination must be replaced as complete unit.
•
Shaded pole motor.
Resistance Heater (optional)
•
Electric resistance heat to heat cabinet air.
•
1.0 kW @ 240 VAC.
•
Located in supply air outlet.
•
Nichrome wire.
•
High limit thermostat (approximately 145°F) and thermal cut-out safety device.
1.3
Function/Description of Major Control Components
Control Voltage Transformer
•
Provides low voltage to control circuits.
•
Reduces line voltage (208/230 VAC) to 24 VAC.
•
40 VA power rating.
•
Impedance protected.
•
Factory wired for 230 VAC operation; if voltage is <220 VAC, wire for 208 VAC.
Compressor Contactor (CC)
•
24 VAC coil.
•
Switches compressor and condenser.
•
Energized during cooling mode.
Heat Contactor (optional)
•
Double pole.
•
24 VAC coil.
•
Energized during heating mode.
•
Normally open (NO).
High Voltage Terminal Block
•
Connection point for main incoming power.
•
Two pole.
Ground Screw
•
Grounding terminal for main power.
•
Connected to high voltage receptacle on side of unit.
Low Voltage Terminal Block
•
Connection point for low voltage controls.
•
Thermostat, transformer, alarm.
•
10 terminals.
Compressor Capacitor
•
Start/run capacitor for PSC (permanent split capacitor) compressor motor.
•
15 µfd, 370 VAC.
•
Provides starting torque and improves operating efficiency.
6
ECUA06 7/2014 new