Function/Description Of Major Control Board Components - Industrial Climate Engineering MiniPac ECUA06ACA A2 Series Operation And Installation Manual

Environmental control unit
Table of Contents

Advertisement

Evaporator Blower and Motor (EBM)
Twin blower and motor.
Pulls cabinet air through evaporator and discharges cooled air back to cabinet.
Squirrel cage blower design.
Blower and motor combination must be replaced as complete unit.
Shaded pole motor.
Resistance Heater (optional)
Electric resistance heat to heat cabinet air.
1.0 kW @ 240 VAC.
Located in supply air outlet.
Nichrome wire.
High limit thermostat (approximately 145°F) and thermal cut-out safety device.
1.3
Function/Description of Major Control Components
Control Voltage Transformer
Provides low voltage to control circuits.
Reduces line voltage (208/230 VAC) to 24 VAC.
40 VA power rating.
Impedance protected.
Factory wired for 230 VAC operation; if voltage is <220 VAC, wire for 208 VAC.
Compressor Contactor (CC)
24 VAC coil.
Switches compressor and condenser.
Energized during cooling mode.
Heat Contactor (optional)
Double pole.
24 VAC coil.
Energized during heating mode.
Normally open (NO).
High Voltage Terminal Block
Connection point for main incoming power.
Two pole.
Ground Screw
Grounding terminal for main power.
Connected to high voltage receptacle on side of unit.
Low Voltage Terminal Block
Connection point for low voltage controls.
Thermostat, transformer, alarm.
10 terminals.
Compressor Capacitor
Start/run capacitor for PSC (permanent split capacitor) compressor motor.
15 µfd, 370 VAC.
Provides starting torque and improves operating efficiency.
6