1.9

Ratings, Wiring and Identification

Summary Ratings
ELECT. HEAT
BASIC
VOLTAGE
MODEL
PHASE / HZ
ECUA06ACA (A)
208-230/1/60
MCA = Minimum Circuit Ampacity (Wire Size Amps).
MFS = Maximum Fuse Size or HACR circuit breaker.
Unit Load Amps
BASIC
VOLTAGE
MODEL
PHASE
NUMBER
HERTZ
ECUA06ACA (A) 208-230/1/60
IBM = Indoor Blower Motor
Electrical Characteristics
BASIC
MODEL
TYPE
Rotary
208/230-60-1
ECUA06ACA (A)
RLA = Rated Load Amps
LRA = Locked Rotor Amps
RPM = Revolutions per Minute
Model Identification
ECU
A
06
Nominal Cooling
06 = 6,000 BTUH
Refrigerant
A = R410A
Environmental
Control
Unit
000 = None
005 = 0.5 kW
CKT #1
CKT #1
MCA
MFS
MCA
MFS
6.1
15
6.1
15
CURRENT
LOAD OF RESISTIVE HEATING ELEMENTS ONLY
AMPS
AC
IBM
0.5 kW
1.0 kW
5.15
0.60
2.10
4.20
COMPRESSOR
VOLTS
RLA
LRA
MCC
3.7
22.2
5.8
MCC = Maximum Continuous Current
HP = Horse Power
AC
System Type
Air Conditioner
010 = 1.0 kW
022 = 2.2 kW
CKT #1
CKT #1
MCA
MFS
MCA
MFS
6.1
15
n/a
n/a
(AMPS)
2.2 kW
3.6 kW
n/a
n/a
OUTDOOR FAN MOTOR
VOLTS
RPM
FLA
208/230-60-1
1430
0.85 1/10 208/230-60-1
A
•••
Electric Heat – kW
000 = No Heat
010 = 1.0 kW
Power Supply
A = 208/230V,1ø,60Hz
11
036 = 3.6 kW
CKT #1
MCA
MFS
n/a
n/a
TOTAL MAXIMUM HEATING AMPS (STANDARD
UNIT)
0.5 kW
1.0 kW
2.2 kW
2.70
4.80
n/a
INDOOR FAN MOTOR
HP
VOLTS
RPM
FLA
1210
0.60 1/10
FLA = Full Load Amps
••
Series
A2 = Series No. 2
A3 = Series No. 3
A5 = Series No. 5
ECUA06 7/2014 new
3.6 kW
n/a
HP