OpenAir GEB Series Enhanced Rotary Non-Spring Return Damper Actuators
DIP Switch
Functionality
GEB161.1
Counterclockwise
GEB164.1
Active
2-10 Vdc
GEB161.1
2-10 Vdc output
GEB164.1
Rotary direction
Self-adapting
Positioning Control Signal: (GEB161.1)
Positioning Control Signal: (GEB164.1)
2....
Siemens Industry, Inc.
Description
2
2
• The arrow direction must match the rotational direction of
• Factory setting:
• Alternative switch-on/off for self-adaptation.
0
• Factory setting: 0
CAUTION:
• Alternative settings:
2
0
• Factory setting: 0-10 Vdc
• Alternative settings:
0....
Factory setting: 0
Label
Description
Clockwise
0
Off
0...10 Vdc
0
0...10 Vdc
0
output
Figure 16. DIP Switches.
the actuator.
: ON
0: OFF
When turning the self-adaptive feature on, or after a
software reset with the feature on, the actuator will
enter a five-minute calibration cycle as the actuator
adjusts to the rotation limits of the system.
A software reset happens after power on or may be
caused by electrostatic discharge (ESD) at levels of
2kV and above.
2-10 Vdc
0-10 Vdc
2...: 2-10 Vdc output voltage
0...: 0-10Vdc output voltage
Technical Instructions
Document Number A6V12029156
December 16, 2021
Function
Rotary angle direction
Self-adaptation to
mechanical range
signal
Selection control
signal
2-10 or 0-10 Vdc
Output Signal
2-10 or 0-10 Vdc
Output Voltage