INSTALLATION | WIRING | COMMISSIONING | MAINTENANCE | I S O 9 0 0 1 ISO 14001 Q u a l i t é Environnement AFNOR CERTIFICATION AFNOR CERTIFICATION CAD O Integral Air Handling Unit with Rotating Heat Exchanger NT-50897201-CAD-O-INTEGRAL-ETD2-AN-230123...
Once the installation is terminated, leave this manual in the machine for future consulting. The installation of this product (implementation, connections, commissioning, maintenance) and all other interventions must be performed by a professional applying the recognized rules of good practice, stan- dards and safety regulations in force. It must conform to the prescriptions related to Electromagnetic Compatibility (EMC) and the Low Voltage Directive (LVD). VIM shall not be held responsible for possible injuries and/or damages caused by the non compliance with safety instructions or following a modification of the product. The CAD O Integral Dual Flow Air Handling Units are designed for dual flow air ventilation and air treat- ment applications in public and private buildings: • Indoor installation (recommended) or outdoor installation with accessories. • Permanent ambiance temperature : -25°C / +40°C. • Outdoor air operating temperature limits: -30ºC / +40ºC.
1.3 Acceptance – Storage In case of missing, non-conforming, or totally or partially damaged delivered products, the Purchaser must make written reservation on the transporter’s receipt and confirm them within seventy-two (72) hours by sending a recommended letter to the transporter, as well as a copy to VIM. Acceptance of the equipment without any reservation will deprive the Purchaser of any subsequent recourse against us. The product must be stored in an area protected from bad weather, shocks and stains due to splashings or splatterings of any kind during its transport from the supplier to the end customer and onto the worksite before installation.
• CAD O Integral EC : integrated hot water coil. • CAD O Integral ER : integrated reversible cold water/hot water coil (VL model only). • CAD O Integral ECF : integrated hot and cold water coils (on size 60 - 80 - 100 - 150 only). • CAD O Integral EX : direct expansion coils (on VL configuration only except sizes 150).
2.2 Main components General specification - Version without heater (E) or with electric heater (EI) Righthand installation in the supply air direction Version VLD Version VLG Electric heater EI after the fan on size 150 Version VTD Version VTG 16 15 10 11 Description Symbol...
Page 7
General specification - Version hot water coil (EC) or reversible cold water/hot water coil (ER) Right hand installation in the supply air direction Version VLD Version VLG Size 150 Version VTD Version VTG Description Symbol Description Symbol ...
Page 8
General specification Version direct expansion coil (EX) Version VLD Version VLG 7 17 Reference Description Symbol Outdoor air duct connection Pressure guard on outdoor air filter Outdoor air temperature sensor Filter G4 (Coarse 70%) outdoor air F7 (ePM1 55%) filter on outdoor Air Rotary heat exchanger Direct expansion coil Supply air fan Supply air temperature sensor ...
Page 9
General specification Hot and cold water coil (ECF) Version VLD Version VLG 17 18 Size 150 11 12 13 1 2 3 4 5 9 10 18 17 Description Symbol Outdoor air duct connection Pressure guard on outdoor air filter Outdoor air temperature sensor Filter G4 (Coarse 70%) outdoor air F7 (ePM1 55%) filter on outdoor Air Rotary heat exchanger...
Page 10
Rotary heat exchanger - Principle / Construction The construction of the rotating heat exchanger used into the CAD O Integral consists of alternating layers of flat and corrugated aluminum foil, which form a spiral from the center. This results in a defined structure of small triangular flutes. Supply and exhaust air each pass through half of the wheel in counter flow direc- tions. The rotor exchanger is a rotating transfer media. It temporarily takes up the heat from the warm air stream and releases it in the colder air stream.
INSTALLATION 3.1 Machine identification / Symbols Identification label – fixed on the casing Version VL (supply side upward) Version VT (on upper righthand corner) Meaning of the symbols present on the unit and in the manual Symbol Machine Symbol Instructions manual Outdoor air Extract air ...
Page 14
Model CAD O Integral 60 VL 345 224 569 345 251 596 345 245 590 345 252 597 345 273 618 345 262 607 CAD O Integral 80 VL 457 285 742 457 322 779 457 313 770 457 323 780 457 352 809 457 337 794...
Page 15
Model CAD O Integral 60 VL 345 224 569 345 251 596 345 245 590 345 252 597 345 273 618 345 262 607 CAD O Integral 80 VL 457 285 742 457 322 779 457 313 770 457 323 780 457 352 809 457 337 794...
Page 16
CAD O Integral VLD - Size 150 model ECF In line air connection / right hand side maintenance acces (delivered in 2 parts) 1/2" Model ER4R Model EC and ER water coil water coil Model CAD O Integral 150 3325 1552 1774 2215 2460 2100 2288 1409 1798 1840 Model CAD O Integral 150 2107 947 1 1/2"...
Page 17
CAD O Integral VLG - Size 150 model ECF In line air connection / Left hand side maintenance acces (delivered in 2 parts) 1/2" Model ER4R Model EC and ER water coi water coil Model CAD O Integral 150 3325 1552 1774 2215 2460 2100 2288 1409 1798 1840 Model CAD O Integral 150 2107 947 1 1/2"...
Page 18
CAD O Integral VLEXD 07 / 13 / 19 / 25 / 35 / 45 / 60 / 80 / 100 Right hand side access door on the supply air flow direction CAD O Integral VLEXG 07 / 13 / 19 / 25 / 35 / 45 / 60 / 80 / 100...
Page 19
1007 1041 1023 CAD O Integral 150 VLEX 1855 1895 Recycling box CREI / Mixing box CMOI Right or left version available according the unit configuration (same sizes). CREI-CMOI for CAD O Integral 07 to 45 Dimensions (mm) Description CREI-CMOI 07/13 982,5 CREI-CMOI 19 581 1082,5 355 CREI-CMOI 25 700 1182,5 400...
CREI-CMOI for CAD O Integral 150 Dimensions (mm) Description CREI-CMOI 150 1549 2215 2460 1563 Dimensions (mm) Description CREI-CMOI 150 1409 2000 1798 Dimensions (mm) Description CREI-CMOI 150 1388 1840 3.3 Handling The units are delivered screwed to pallets, except on size 150 delivered on its frame. The CAD O Integral dual flow air handling units can be handled by a pallet transporter, a forklift, or a crane. The handling machines will be adapted to the load and the lifting conditions. In all cases, the lifting will be done at the device’s base. The centre of gravity is located at the centre of the unit. The device must be carefully manipulated only in the horizontal position. Ø 50 mm. holes are provided for in the frame to allow passing a pipe to hook the slings. To avoid deteriorating the unit’s envelope, long length slings and lifting beam spacers must be used. In case a forklift / pallet transporter is used, the forks should be long enough to avoid pushing in the lower panel.
Moving and lifting CAD O INTEGRAL 150 Exchanger module Coil module Crane lifting module by module or after assembly on the ground. 3.4 Placement and attachment point Placement The CAD O Integral must be laid on a smooth horizontal surface capable of supporting the load. The CAD O Integral VL / VT Integral units are designed for an installation inside the building. Only the VLEX versions delivered with a roof can be used outdoors. In all cases, provide the ducts, connection accessories, heater antifreeze protection and antivibration equipment. In heavy snowfall zones, an additional protection must be provided for. It is important to provide enough space (Z minimum) to allow opening the doors, commissioning and main- tenance (filters, fans, heat exchanger). Do not position the unit against a wall to avoid the transmission of structurally borne noise. 200 mm...
Page 22
CAD O Integral 07 / 13 / 19/ 25 Sizes / Dim. (mm) Cote A Cote B CAD O Integral 07/13 VL 1308,5 CAD O Integral 19 VL 1458,5 CAD O Integral 25 VL 1558,5 CAD O Integral 13 VT...
Page 23
CAD O Integral 60 / 80 / 100 On size 60 - 80 - 100, units are delivered with frame in galvanized steel 3mm thickness, 100mm height, with assembling system between 2 modules, fixing holes for antivibration pads or adjustable feets. With this frame system, the unit could be lift with a crane after assembling the unit on the floor. Sizes / Dimensions (mm) CAD O Integral 60 VL 1968 1868 919,4 824,6 1100 CAD O Integral 80 VL 2108 2008 999,4 884,6 1350 1220 1090 CAD O Integral 100 VL...
Page 24
CAD O Integral 25 Kit of 4 feet 018300 CAD O Integral 35/45 Kit of 6 feet 018301 Opening of the doors The CAD O Integral units up to size 100 are equipped as follows : • In the front on the lefthand and righthand sides, doors mounted on hinges held closed by latches. • In the central front position, a door held up by a latch placed on the bottom on a support rail and retained in the top part by a retractable hook.
On the units of size 60 - 80 and 100, a door handrail is install on the controler part. It allows the locking of the door in the open position. CAD O INTEGRAL 150 are equipped with doors or half-doors mounted on hinges, closed by locks, on the front and back of the unit. CAD O Integral 150 Without coil or electric heater With water coil Door...
Page 26
The units size 150 are delivered with bumpers to prevent damage to the unit during transport and its handling. Once the unit is positioned, the bumpers must be removed, especially those at the junction of modules • On the first part, fix on both side the junction elements without fully tighten the junction strengthening elements. Hole on the direction of the floor • Move closer as much as possible to both modules ; fix the junction elements on the second module loosely. Finalize the junction with the tensioner screw. ENGLISH 26/96 NT-50897201-CAD-O-INTEGRAL-ETD2-AN-230123...
Page 27
2 - Heat exchanger electrical power. 3 - Plug fan control signal. 4 - Heat exchanger control signal. 5 - Exhaust air fan pressure transmitter. 6 – Pressure guard + temperature probe. Roof mounting on CAD O Integral 150 VLEX On the VLEX models of sizes 150, the roof is pre-assembled in the factory on each of the modules. The roof junction have to be mounted on site after assembling the 2 modules together. ENGLISH 27/96 NT-50897201-CAD-O-INTEGRAL-ETD2-AN-230123...
3.6 Connection between mixing or recycling box and the CAD O Integral The unit can be equipped with mixing box (CMOI) or recycling box (CREI), connection according the below procedure : Size 07 to 45 • Move closer the 2 modules by taking care to • Screw 2 modules together with 10 auto-drills align the round cuts on the feet support. screws delivered with the box Size 60 to 100 •...
Roof assembly between a CAD O INTEGRAL 150 VLEX and a CMOI / CREI On the VLEX models of sizes 150, the roof is pre-assembled in the factory on each unit's modules and on the CMOI-CREI VLEX mixing / recycling box. • Remove the end roof of the heat exchanger module from the unit. • Assemble the unit and mixing box assembly • Install and fix the junction roof between the unit and the box. HYDRAULIC AND FLUID CONNECTION 4.1 Water coils connection The unit’s hydraulic data are specific to your installation and are deter- mined by the computer selection : Water pressure drop / Waterflow. Refer to the selection to size the network, accessories, pump, etc.
Page 30
On size 150, the water pipes are connected on the front, outside the unit. 504423-Etiquette-Marquage-batteries-eau-190114 2 modèles - Format 50 x 50 mm Pantone 108 Noir 100% sortie Water d'eau output Water output Water input Water entrée input d'eau Condensates drain (reversible water coil ER version VL only) The installed coil is equipped with a droplet separator and a condensate dip tray made of stainless steel welded in the corners.
4.2 Valves connection Motorized 3-way valves are not delivered mounted. They are proposed as accessories by VIM. Respect the positioning of the mixing valve on the network and the water inlet and outlet directions. Electric connection on the CAD O Integral box: see subsection "Inputs – outputs", page 43 Unit with hot and cold water up to size 100. Cold water Hot water Unit with hot water coil and / or cold water coil from size 150. Connection on the main face of the unit. Provide sufficient space to allow the opening of the door for main- tenance...
(examples)", page 45. When the unit is equipped with a water coil it is recommended to provide for an antifreeze protection damper on the fresh air network. If possible, use a motorized airtight damper. A second damper should be mounted on the extraction network to isolate the unit. Unit up to size 45 – circular air duct connection CAD O Integral Type Code Designation Duct Ø (mm) 07 VT / 13 VT...
Page 34
The outside units until the size 45 can be equipped with standard accessories for circular ducts, type APC for the exhaust air and outdoor air inlet protection canopy. For the sizes 60, 80 and 100 with rectangular air connection, exhaust air and outdoor air protection canopy are specific. Dimensions (mm) Type Designation APPR 60 Exhaust air protection canopy CAD O Integral 60 1065 APPR 80 Exhaust air protection canopy CAD O Integral 80 1265 APPR 100 Exhaust air protection canopy CAD O Integral 100 1465...
Page 35
Installation APPA-APPR up to size 150 (Screws included) APPR APPA 2 HM8x20 2 HM8x20 APPA / APPR specific mounting for size 150 Mounting of the support rails using Installation of the peripheral seal Remove the front grids 6 HM6x20 screws (same phase 2 of the other sizes) Installation of the 1st module thanks Fix the 2nd module by following the to the rail upper, fix it with 1 M8...
For an operation at constant pressure, it is necessary to install a pressure probe (Accessory) in the supply duct at a minimum distance of twice the connection’s diameter. 2xD mini Recommended pressure sensor : Application Code Designation Description Pressure transmitter in box 0 to 500 Pa/ Output Signal 0,5/ 4,5 Vdc CAD O Integral 07/13 132146 SPRD-010B 500 Nominal voltage 12 up to 24 V dc Pressure transmitter in box 0 to 800 Pa/ Output Signal 0,5/ 4,5 Vdc All sizes except 07/13 132105 SPRD-010B 800 Nominal voltage 12 up to 24 V dc SPRD Accessoiry...
Page 37
Global unit Power and current for the totality of the selected CAD O Integral unit. Capacity of the power connection terminal strip : 10 mm², tightening torque: 2.5Nm. Heat exchanger rotor drive motor Nominal Maxi Model Voltage Current Voltage Frequency...
Page 38
Safety contactor 13NO 21 NC Control Triac 14NO 22 NC Sizes Voltage (V) Nominal power (W) Current (A) CAD O Integral 07 EI Mono 230V 13.1 CAD O Integral 13 EI Mono 230V 17,4 CAD O Integral 19 EI Mono 230V...
Page 39
On the units of size 60 - 80 and 100, the sécurity thermostat could be reseted from the inside of the unit. Put out the exhaust air filters Put out the rubber washer Reset the manual security thermostat On 150 units, the electric heater safety thermostat is reset inside the unit on the front of the coil. Slide finger to rearm ENGLISH 39/96 NT-50897201-CAD-O-INTEGRAL-ETD2-AN-230123...
6.2 Internal electrical box – composition / connection Position Description Main power connection switch / safety circuit breaker (1) Electrical power distributor for the different components Alimentation 230V/24V 50/60Hz Control circuit protection fuse (F1= 1,6 A ; F2= 1,6 A; F3= 2,0 A) Analogic output switches (2) Temperature sensor switches (2) Universal switches : CO2 sensor / pressure tranmitter … Digital input switches : On/Off, thermostat… (2) Relay outputs: KM1, KM2, KM4, KM5: information transfer, register command Pressure transmitter control on exhaust air flow Pressure transmitter control on supply flow Controller CORRIGO : Regin-OEM ref 28ES 3P 40A switch disconnector (all CAD O except sizes 80 and 100 if electric heater), connection capa- city: Rigid cable : 2.5 to 16 mm² max / Flexible cable : 2.5 to 10 mm² max 80A disconnect switch: (CAD O 80 and 100 if electric heater) connection capacity: Rigid cable : 2.5...
Power connection Actuators power supply Main electric power Auxilary power supply supply to the unit (Customer) (Customer) (coming from unit) Exhaust air fan motor 2T1 4T2 6T3 Distribution of internal power supplies done Bat1 Bat1 Bat1 outside unit in factory Supply air Electrical Heat...
Use one of the cable grommets available to connect inside the control unit. Once the connection comple- ted, attach the cable to the mounting bracket with a collar to avoid strain on the connector’s springs when handling. The ETD2 control is IP20, it is exclusively reserved for indoor use, protected from humidity. It is equipped with an internal temperature sensor. In the case of external mounting of the CAD O INTEGRAL VLEX, you can also leave it inside in the housing of the electrical box. Once the settings have been made, the remote control can be disconnected. Electrical schematic diagram of the connection : Câble (code 132389) CORRIGO controller Régulateur CORRIGO Ext.
Page 43
Inputs – outputs Customer main power supply Total Start Total Mixing alarmes supply air alarm register B and C OEM - Controller Modbus (fan) M1 M2 Electrical power distributor Exchanger electrical for the di erent components power supply 2T1 4T2 6T3 Analogic input (sensor) Terminals Signal...
Page 44
Logical Input (control and safety guard) : those input may only wire to voltage free contacts Switch Signal Variable Name Description 21-22 DI 1 Defrost DX Group Reception of the signal of defrost procedure on DX group 23-24 DI 2 filter pressure guards Monitoring of the filters cleanliness condition Monitoring of the safety thermostats triggering in case of an...
Logic output (actuator and info report) : les contacts sont libres de potentiel Switch Signal Variable Description KM1 : 12-11-14 Control output for the fresh air register servo motor Available : - either for use of a 230 V register with a control by 230 V Supply air fan signal (on terminal) and a 230V power supply (L-N) - or by a dry contact for a general usage N-L-on 230V KM2 : Total alarm Total alarm status 12-11-14...
Page 46
Case of a reversible water coil ER (delivered mounted – cold or hot) + dampers (accessories) Out door air 3 way valve actuator Frost protection Change over damper on hot/cold water coil sensor thermostat actuator with security Supply air spring return T°...
Page 47
Case of a PWM controlled EI electric heater (delivered mounted) + dampers (accessories) Out door air Electrical heater damper battery control by Over heat protection actuator PWM signal control thermostats with security signal spring return type LF 230S Electrical power Supply air T°...
Page 48
Case of a register with 24V actuator (accessories) 21 11 24 14 Fdc A and B Actuator with spring return for fresh air damper type LF 24 S blowing step (antifreeze) Case of DX coil with DX groupequiped with CTA kit Control unit DX-Kit CTA Defrost DX group...
Page 49
Case of operation in constant airflow (CAV) – controlled by optical sensor or box 0 / PV / GV (accessories) Warning : All the controls must be made with potential free contacts Variant : ON / OFF Fan control 0-PV-GV Presence detector Switch board into the unit Case of operation in variable airflow (VAV) – CO2 probe (accessory) The unit is preprogrammed for the usage of a CO2 measurement probe with a range 0 – 2000 ppm and a signal of 0 –...
Page 50
Case of operation in constant pressure (COP) – pressure probe at supply (accessory) The unit is preprogrammed for the usage of a pressure probe with a range of 0 – 800 Pa (0-500Pa on size 07/13) and a signal of 0.5 – 4.5 Vdc. Another probe can be used by means of an advanced parameter setting. ON/OFF Pressure transmitter 0.5-4.5V Switch board into the unit ENGLISH 50/96 NT-50897201-CAD-O-INTEGRAL-ETD2-AN-230123...
Page 51
Electric wiring mixing box CMOI Internal wiring from the connection box to the damper actuators and the CO2 sensor are made into the ma- nufacture. Only the connection between the unit and the mixing box has to be done on the installation site. CAD O Integral 21 11 24 14 230 V Night cooling switch on N PH Supply air (open fresh fan switch air damper) 22 12 22 12 Connection box into the CMOI 24 V...
Page 52
Electric wiring recycling box CREI Internal wiring from the connection box to the damper actuatore are made into the manufacture. Only the connection between the unit and the mixing box has to be done on the installation site. CAD O Integral 21 11 24 14 230 V Outdoor N PH Supply air air damper fan switch 22 12 22 12 Connexion box into the CREI 24 V F1 F2 24V CO2Com...
6.6 Synoptic installation diagrams (examples) CAD O Integral E / EI Sizes 07 to 100 Exhaust air Extract air Rejet air vicié Reprise air vicié SCO2 Outdoor air Supply air Aspiration air neuf Sou age air neuf HR-R Bat2 Triac1 Size 150 Rejet air vicié...
Page 54
CAD O Integral ECF Exhaust air Reprise air vicié Rejet air vicié Extract air Outdoor air Supply air Sou age air neuf Aspiration air neuf Bat1 Bat3 HR-R Pr10 CAD O Integral EX Exhaust air Rejet air vicié Reprise air vicié...
COMMISSIONING All the CAD O Integral units are subjected to a DC check and a functional test before they are delivered. Factory parameter settings of the units: • Ventilation mode = CAV mode (description in subsection "8.1.1 Constant flow operation (CAV)", page 57). • High speed = Unit’s max airflow, Low speed = Max airflow / 2. • Fan type: determined according to the airflow coefficient K specific to the fans (description in subsec- tion "Setting the extraction and supply fans:", page 72). • Heating mode = constant supply T° (description in subsection "8.2.2 Temperature control modes", page 60). •...
CONTROL - FUNCTIONS / PARAMETERS CAD O INTEGRAL CORRIGO CONTROL EI EC ER ECF EX MAIN COMPONENTS Inyernal electrical box - composition : - Main power connection switch / safety circuit breaker - Controller and terminal strip integrated into the unit, easy access main side FUNCTIONS Air flow control...
8.1 Airflow control Fan Airflow management can be carried out according to 3 control modes: CAV, VAV, COP. Whatever mode is selected, each fan suction pavilion (extraction and supply) is equipped with a pressure tap and connected to a pressure sensor. The flow rates resulting from the pressure measurements are calculated by the regulator, according to a coefficient K specific to each fan. • The DO1 digital output corresponds to the supply fan running command and can be used for acces- sory operation linked to the operating status of the fans (for example starting a DX unit if the supply fan is running). • Analog output AO4 corresponds to the 0-10V control signal sent to the supply fan. •...
Page 58
The air flow will automatically change between these two rates depending on the signal received. Independently, a BOOST (extra m /h) airflow can be programmed in the form of a fixed airflow for extrac- tion and supply. • Digital input DI5 = Start/stop. • Digital input DI6 = forcing GV - forcing of the max flow rate set for the max signal. • BOOST (extra m3/h) selection can be done from the remote control. To perform a BOOST forcing via a digital input, it is necessary to reparametrize a digital input (DI1 for example) and assign it the "Additional alarm 7" function. When closing this digital input, an “External BOOST forcing” message will appear on the main screen. • A fourth flow set point for "night free cooling” overventilation can be entered via the remote control, in the form of an offset of the high-speed flow GV (see free cooling for operation) 8.1.3 Operation at constant pressure COP on extraction or supply mode Recommended mode in multi-zone configuration associated with terminal airflow modulation systems.
8.2 Temperature control 8.2.1 General principle The temperature set point as well as the temperature regulation mode are entered via the touch screen. The supply or ambient temperature is maintained at the set value by acting on the controller outputs (hea- ting/exchange/cooling), a single PI loop is used. The exchanger is considered to be the first potential source of heat or cooling even before the batteries. For CAD O INTEGRAL fitted with a standard rotary heat exchanger (1 speed), the wheel is controlled in binary mode (on or off). For CAD O INTEGRAL equipped with a sorption exchanger, the rotation speed is variable, proportional to a 0 - 10V signal. By varying the speed of rotation, it is therefore possible to modify the efficiency of the exchanger to reach a given temperature set point. Échangeur rotatif mono vitesse Échangeur rotatif à vitesse variable Single-speed rotary heat exchanger Rotary exchanger with variable speed Froid Froid Chaud Warm...
Page 60
8.2.2 Temperature control modes The temperature regulation can be carried out according to the following 4 modes: • Supply air control at constant temperature The supply air temperature is maintained at the set value by acting on the exchanger outputs, hot output and cold output. The setpoint is adjusted using the display and number keys. The user set point for the mode is entered in °C in the settings menu. • Supply air control at constant temperature with outdoor temperature compensation The supply air temperature setpoint is adjusted according to the outside temperature according to a compensation law made up of 8 factory preset setpoints. The supply temperature is maintained at the set value by acting on the exchanger, internal coil, exchan- ger, external coil outputs.
8.3 Special case: temperature control with EX direct expansion coil General: • A communication box, “CTA kit”, must be provided by the unit's supplier. He makes the communica- tion possible between the direct expansion group and the CORRIGO regulator. • The direct expansion coil regulation mode is selected on the touch control. • Temperature regulation by DX group. • The DX group controls the regulation temperature using its own sensors. •...
Page 62
Stop conditions: • The outside temperature is above 18°C or below 10°C (risk of condensation station). • The return temperature is below 18°C • The time programs (timer) for normal speed, normal override and control are “On”. • It is past 7:00 in the morning. If at least one of these conditions is fulfilled after the first three minutes of operation, then the overventila- tion is stopped. When the over-ventilation function is active, the fans run: • In CAV at the speed set for high speed(GV) + an offset in m /h (settings entered in the CAV settings menu). • In VAV at the speed set in high speed (Vmax) + an offset in m /h (setting entered in the VAV settings menu).
To be able to benefit from the nocturnal overventilation, it is necessary to force the opening of the modula- tion registers, wiring principle below: 230V~ 230V~ TRAFO 0 24~ CAPI 0 24~ 0 24~ Registre LM24-A-SR Information Information register overventilation LM24-A-SR Surventilation 230V~ Capteur Optique Optical sensor N L L D1D2 CAPI 230V~ damper Registre 230V~ LM230A, RMME... LM230A, RMME... 8.5 Hot water coil frost protection The hot water or reversible coils integrated in our units have a water temperature sensor “Antifreeze pro- tection sensor” installed on the water outlet pipe and connected to the regulator (AI3).
8.6 CMOI – Mixing box The mixing box is mainly used in mixed ventilation and heating installations. It will make it possible to operate in recycling mode during periods of non-occupation and in all fresh air during maximum occupancy of the premises. Operating principle: The mixing box is fitted with a CO2 sensor (SCO2 A-010 400-1100ppm) which continuously measures the level of CO2 contained in the extracted air, it sends a proportional signal to the damper servomotors to open them more or less depending on the indoor air quality. Unit shut down (antifreeze protection, system shutdown, etc. Unité à l'arrêt ( protection antigel, arrêt système...) SCO2 When the unit is stopped, the extraction and fresh air dampers are closed, the mixing damper is open.
8.7 CREI - Recycling box The recycling box is used when it is desired to recycle the air extracted over a time slot when it is not oc- cupied, to allow for example a rise in temperature of the room. Operating principle: Timer programming of recycling hours is to be carried out in time slot 5. This time slot, which does not have priority, is to be programmed outside the other time slots (normal speed or reduced speed). Programming example: Time program Programmation Marche Start vitesse normale normal speed Arrêt Stop Programmation Time program Marche Start vitesse réduite reduce speed Stop...
Example : BOOST : High Speed: Low Speed: • From 9:45 a.m. to 10:15 a.m. in period 1 • From 8 a.m. to 12 p.m. in period 1 • From 6 a.m. to 9 p.m. in period 1 • And from 12 p.m. to 2 p.m. in period 2 • And from 2 p.m. to 6 p.m. in period 2 The automaton will then control the fans as follows : Marche Start Programmation...
Sensor error extract air temp Sensor error extract air temp Sensor error SAF pressure sensor error SAF pressure Sensor error EAF pressure Sensor error EAF pressure Sensor error water sensor Sensor error water sensor Extra alarm 7 External boost switch Extra alarm 8 Heating desable Extra alarm 9 Additional compensation air flow Extra alarm 10 DX group defrost (reduce speed + offset) 10. USING AND CONFIGURING THE CONTROL VIA THE TOUCH DISPLAY ETD2 10.1 Presentation of the ETD2 touch display Welcome screen This window displays strictly essential information on the state of the machine. It is possible to switch to...
Page 68
Main menu In the menu window, you can access the following functions: Synoptic Temperatures Fan operating speed Screen display settings Alarms Password with 3 authority levels: User, Installer or Factory. Depending on the level of authority entered, padlocks present on the icons indicate the impossi- bility of accessing the content. Menu accessible at installer or factory level: Settings (installer password) Clock (installer password) Communication (installer password) Advanced settings and adjustments (factory password) Registration (installer password)
Page 69
Speed selection settings Depending on the settings made on the UTA (Constant flow CAV - Variable flow VAV - Constant pressure COP), the speed selection screens will appear. CAV MENU Allows: • to stop the unit • to manually select one of the 3 speeds parameters (ECO – GV – BOOST) • to operate according to the time programming The lower display shows the actual airflow and the fan control signal.
Page 70
Alarm settings Allows you to view active alarms, acknowledge them or block them if necessary. Authority levels and passwords This page allows you to connect with a sufficient level of authority to perform certain functions. User level - Password 3333 optional Default level that allows the use of the CTA without specific settings or backup operations. Installer level - Password 2222 CTA usage level + specific settings and backups. Expert level - Factory password transmitted only by our after-sales service Access to all functions To identify yourself, press the icon corresponding to the required level. Enter the password using the numeric window.
Setting ventilation modes Access to this menu requires the minimum level of authority: Installer Level. You can then modify the factory settings presented in § "Factory parameter settings of the units:", page Choice of fan regulation mode: • CAV = Constant airflow • VAV = Variable airflow according to an external signal (CO2 sensor for example) • COP = Constant pressure Supply COP (transmitter installed in the supply duct) Extraction COP (transmitter installed in the extraction duct) 10.2 Specific settings on mode CAV If Constant flow - CAV selected On this page it is possible to enter the desired values in...
Page 72
• Setting the scale of the pressure sensors used • Characteristics of the proportional bands and integral times of the flow control loop (default values in the table below) Each CAD O INTEGRAL fan is equipped with a differential pressure sensor, connected to the regulation. • Sizes 07 to 13 = 0-500 Pa pressure sensor and 0.5 - 4.5 Vdc signal.
10.3 Specific settings to mode If COP constant pressure selected on SUPPLY If COP constant pressure selected on EXTRACTION • Select the location of the pressure sensor in the duct (supply or extraction). • Enter the pressure setpoints in Pa in ECO and GV mode for the supply fan or for the extraction fan. If you only have one set point, enter the same value twice. • Enter, if necessary, an offset value between the extraction and supply airflow. • Activate or deactivate the free cooling over-ventilation function and set the time range during which this function will be active. •...
10.4 Settings common to all fan operating modes Access to this menu requires the minimum level of authority: Installer level. This screen is used to configure the reaction of the fans when the "fire" digital input is activated. • By default: extraction and supply stop. This screen is used to set the temperature regulation mode that will be used by the air handling unit. This page allows you to configure the type of post- processing installed. By pressing the icons, it is possible to define the desired configuration: • No electric coil post-heating coil •...
11. ADVANCED SETTINGS VIA ETD2 TOUCH DISPLAY 11.1 Schedule programming Access to this menu requires the minimum authority level: Installer Level. This menu is used to define: • Date and time • Time programs for unit operation • Automatic Winter/Summer time change Date / time menu Allows the regulation to be set to the correct time and date. It is possible to automatically activate summer/winter time changes. If unit configured in CAV: If unit configured in VAV: Time program settings menu A Summary key allows viewing of all the configured time slots.
Page 76
It is possible to configure up to 4 time programs per day of the week + 1 Holiday day If the unit has been configured in CAV it is possible to select: • STOP / ECO / GV / BOOST If the unit has been configured in VAV it is possible to select: • STOP / AUTO / GV / BOOST If the unit has been configured in COP , it is possible to select: •...
11.2 Communication protocol settings Access to this menu requires the minimum authority level: Installer Level. This menu contains the configuration parameters for the MODBUS RS485 and MODBUS IP – BACnet MSTP – BACnet IP protocols. Communication to RS485 supervision must be done on communication port N°. 1. Allows selection of the desired protocol using the arrows: • Modbus • BACnet MS/TP • Modbus IP • BACnet IP Modbus This screen enables or disables the Modbus on port 1 RS485 • Address : Represents the address you wish to assign to the unit (by default the units are at address 1) •...
This menu allows: • To save the configuration made on site after having finished commissioning • To load the last configuration stored on site • To return to the configuration of the unit leaving the factory (default parameters CAV mode) • The recording of factory settings requires Expert level, only reserved for VIM after-sales service • Resetting the CORRIGO to completely reload the unit's program - will require a complete reparameterization. To save your site configuration: • Press the corresponding icon • A pop-up window appears asking you to validate your request. • A new window informs you when the operation is finished...
To recall the last saved configuration: • Press the corresponding icon • A pop-up window appears asking you to validate your request. • A new window informs you when the operation is complete. 11.4 Advanced settings This menu requires the Expert level - Factory password transmitted only by our after-sales service. This menu is used to view the status of the inputs/ outputs, to force their values, to modify their assignments and their reactions.
Page 80
Analog outputs - vizualisation and modification Press the value to modify, a pop-up window appears. The arrows allow you to select between: • Value provided by the controller • Force a manual set point value • Cut output As long as the value is forced, the hand next to the value appears in red. Digital outputs - vizualisation and modification Press the value to modify, a pop-up window appears. The arrows allow you to select between: • Value provided by the controller • Force a manual set point value As long as the value is forced, the hand next to the value appears in red. ENGLISH 80/96 NT-50897201-CAD-O-INTEGRAL-ETD2-AN-230123...
Page 81
11.4.2 Input/Output - Assignment of new functions The advanced settings menu is broken down into 2 submenus: • I/O functions (inputs / outputs) • Control functions I/O function (inputs / outputs) This menu is used to assign or reassign a function to the inputs/outputs. Analog inputs To modify the assigned function, press the value to be modified, a pop-up window will open. With the up and down arrows, assign a new function then press OK Digital inputs...
Page 82
11.4.3 Control functions ENGLISH 82/96 NT-50897201-CAD-O-INTEGRAL-ETD2-AN-230123...
12. COMMUNICATION 12.1 Connection to Centralized Technical Management (BMS) in Modbus language MODBUS RTU on port 1 - RS 485 The CORRIGO controller has 2 RS485 communication ports (to be used with an STP cable), port 1 is by default dedicated to Modbus communication CORRIGO (Modbus RTU) MODBUS IP on TCP/IP port The CORRIGO controller has a TCP/IP communication port (RJ45 socket) allowing TCP/IP connection to a TCP/IP network. This port is by default dedicated to Modbus IP communication.
Page 84
Type Register Read/ Accepted Function Description Write values Manual control of the unit Pace in CAV Holding 0=Off, 1=reduce speed, 2=Normal speed, 3=Auto according 0,1, 2, 3 or 4 mode Register timer, 4 =Extra speed (Boost) Manual control of the unit Holding 0,1, 2, 3, 4 0=Off, 1=Manual, 2=Auto according external signal, 3=Extra Register or 5...
Type Register Read/ Accepted Function Description Write values DISPLAY OF ALARMS Input Summary of Presences of alarm Status 0 or 1 alarms 0=Normal 1=alarm Register Input Alarm filter guard Filter alarm Status 0 or 1 0=Normal 1=alarm Register Input Supply air fan alarm Status 0 or 1 0=Normal 1=alarm...
12.3 Resetting the CORRIGO controller In some cases, after multiple settings or following a malfunction, it is sometimes necessary to reset the pro- grammer. Perform this operation only after having been instructed to do so by the VIM after-sales service.
Page 87
Reset the CORRIGO To perform this operation, the CORRIGO must be powered up, power the unit by turning the proximity switch. From the catering menu Press "Reset CORRIGO" Wait for the end of the reset time The screen used to choose the program to load into the controller appears: • Select the RHE program for units up to size 100 and RHE GT for size 150.
13. MAINTENANCE 13.1 Prior precautions • Put on appropriate PPE (Personal Protective Equipment) before any intervention. • Respect the danger labels on the various access doors: Live equipment / Rotating machine / Potentially flam- mable dusty filters. Do not open the access doors without having cut off the power supply at the padlockable disconnect switch present on the unit. If work is to be carried out inside the device, cut off the power supply at the main circuit breaker and ensure that no one can accidentally switch it back on. Make sure moving parts are stationary. 13.2 Maintenance frequency Comply with legal obligations as a minimum. The table below gives indicative average maintenance frequencies. It does not take into account specific factors such as indoor or outdoor installation, the intensity of atmos- pheric pollution, the number of occupants or the number of hours of operation, etc. Organ At startup At least every 6 months Filters Check contamination + clean Dust or replace Check connections and direction of Fans Check dirt + clean if necessary...
13.3 Maintenance / replacement of fresh air / extract air filters As standard, CAD O INTEGRAL include filters: • on the extracted air protecting the exchanger filter M5 (ePM10 50%) or F7 48mm (ePM1 55%). • on fresh air pre-filter G4 (coarse 70%) + Filter F7 (ePM1 55%) or F9 (ePM1 80%) (option). The F7 filters are held flat on the seals by 2 compression locking slides. Clogging of the filters controlled by differential pressure switches with information feedback on the regulation. (Coarse 70%) (ePM1 55%) Media area (Coarse 70%) (ePM10 50%) Size / M5 / F9 (ePM10 50%) (ePMP1 80%) Media area (m²) (m²) (mm) Media area (mm) (mm) 07/13 600 x 372 x 48 0,57...
13.4 Maintenance / replacement of the rotary exchanger and belt After a long period of use, dust can accumulate in the exchanger and reduce the passage of air. To main- tain performance, it is important to check the exchanger at least once a year and clean it if necessary. To facilitate maintenance, the exchanger motor assembly can be removed from the unit: •...
13.7 Maintenance / replacement of the water coil To preserve the characteristics of the battery, purge the water circuit once a year. Depending on the am- bient pollution, and despite the filtration, dust may settle on the battery. After disassembly, the coil can be cleaned with a jet of water, steam or compressed air, proceed with care not to damage the fins of the coil. For units fitted with reversible cooling coils (ER), clean the condensate pan with water and a non-abrasive detergent. Check for proper drainage and check the siphon. 13.8 CORRIGO PLC battery replacement When the low battery alarm appears and the red indicator light turns on, it means that the backup battery for memory backup and real-time clock is too weak. The procedure for changing the battery is described below. A capacitor saves the memory and keeps the clock running for about 10 minutes after the power is turned off. If changing the battery takes less than 10 minutes, there is no need to reload the program and the clock continues to operate normally. The spare battery is type CR2032. • Press the clips on each side of the box with a small screwdriver to detach the cover from the base.
Page 92
Filter G4+activated carbon 680288 FICA G4 Coarse 65% 512x525x48 mm Activated carbon filter (Coarse 65%)-150 018201 Electric heater BEOI 13 Electric Battery 4 kW Mono 230 V CAD O INTEGRAL 018202 Electric heater BEOI 19 Electric Battery 8 kW Mono 230 V CAD O INTEGRAL 018203 Electric heater BEOI 25 Electric Battery 12 kW Tri 400 V CAD O INTEGRAL...
Page 93
018214 Plug fan PFOI 35 Plug fan ECM D355 1000W Tri 400 V CAD O INTEGRAL 018218 Plug fan PFOI 45 Plug fan ECM D400 1850W Tri 400 V CAD O INTEGRAL 018215 Plug fan PFOI 60 Plug fan ECM D400 1850W Tri 400 V CAD O INTEGRAL 018216 Plug fan PFOI 80 Plug fan ECM D450 2730W Tri 400 V CAD O INTEGRAL 018217 Plug fan PFOI 100 Plug fan ECM D560 3000W Tri 400 V CAD O INTEGRAL 132594 Screen Screen ETD2 CORRIGO-4,3"-Remote touch control + câble 10ml 1323880001 CORRIGO E28 3P CORRIGO E28-3 Ports V3 Regulator CAD O Integral / RHE ENGLISH 93/96 NT-50897201-CAD-O-INTEGRAL-ETD2-AN-230123...
14. WASTE MANAGEMENT 14.1 Treatment of Packaging and non-hazardous waste Packaging (non-returnable pallets, boxes, films, wooden packaging) and other non-hazardous waste must be recycled by an approved service provider. It is strictly forbidden to burn them, bury them or put them in wild dumping. 14.2 Treatment of Professional WEEE This product must not be landfilled or treated with household waste but must be taken to an appropriate collection point for waste electrical and electronic equipment (WEEE). ENGLISH 94/96 NT-50897201-CAD-O-INTEGRAL-ETD2-AN-230123...