Test Run
2. How to cope with Test Run abnormality
The phenomena from main component failure
Component
Phenomenon
Not operating
Compressor
Stop during running
Abnormal noise
during running
Heating failure, fre-
quent defrosting
No operating sound
at applying power
Outside
Heating failure,
EEV
frozen outdoor heat
exchanger part
Low pressure error
or discharge temper-
ature error
When system fault occurs, the error code is displayed at indoor unit display or remote control display, the trou-
ble shooting guide is in the service manual
• When CH05/53/11 ERROR occurs, check if auto-addressing has done and communication wiring is ok.
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Cause
Motor insulation broken
Strainer clogged
Oil leakage
Motor insulation failure
R-S-T misconnection
Bad connector contact
Coil failure
EEV clogged
EEV clogged
- 40 -
Check method and Trouble shooting
Check resistance between terminals and
chassis
Change strainer
Check Oil level after opening oil port
Check resistance between terminals and
chassis
Check compressor R-S-T connection
Check connector
Check resistance between terminals
Service necessary
Service necessary
LGE Internal Use Only