SUN2000-(75KTL, 100KTL, 110KTL, 125KTL) Series
User Manual
No.
Cable
5
AC output
power cable
(multi-core)
AC output
power cable
(single-core)
Note [1]: The value of S
the same material. If the materials are different, ensure that the conductor of the PE cable with a
proper cross-sectional area produces a conductance equivalent to that of the cable specified in
the table. The specifications of the PE cable are subject to this table or calculated according to IEC
60364-5-54.
Note [2]: For some models, the outer diameter of a single-core cable ranges from 14 mm to 36
mm based on the label in the maintenance compartment.
Issue 15 (2023-01-31)
Category
● If you connect a PE
cable to the ground
point on the enclosure,
you are advised to use
a three-core (L1, L2,
and L3) outdoor cable
and M12 OT/DT
terminals (L1, L2, and
L3).
● If you connect a PE
cable to the ground
point in the
maintenance
compartment, you are
advised to use a four-
core (L1, L2, L3, and
PE) outdoor cable,
M12 OT/DT terminals
(L1, L2, and L3), and
M10 OT/DT terminals
(PE). You do not need
to prepare a PE cable.
You are advised to use a
single-core outdoor cable
and M12 OT/DT
[2]
terminals.
is valid only if the conductors of the PE cable and AC power cable use
p
Copyright © Huawei Technologies Co., Ltd.
Conductor
Outer
Cross-Sectional
Diameter
Area Range
● Copper cable:
24–66 mm
– S: 70–240
2
mm
– S
≥ S/2
p
● Aluminum
alloy cable or
copper-clad
aluminum
cable:
– S: 95–240
2
mm
– S
≥ S/2
p
● Copper cable:
14–32 mm
– S: 70–240
2
mm
● Aluminum
alloy cable or
copper-clad
aluminum
cable:
– S: 95–240
2
mm
5 Electrical Connections
Source
Prepared by
the
customer
Prepared by
the
customer
52