5. Technical data

5.1 Electrical data

Supply voltage
24 VDC ± 10 %.
Power supply is required to be class 2.
Overvoltage category II.
Check that the supply voltage corresponds to the values stated on
the nameplate.
The wires must be rated at minimum 70 °C (158 °F), minimum 18
AWG.
Mount only copper wires in the terminals.
Power
See nameplate.
Maximum power dissipation
Object
99332827
Input/output connections
Signal excitation (excl. EMC) must be limited to -0.5 to +26 VDC or
an effective clamp current less than ± 15 mADC.
Relay output, REL 1, REL 2
250 VAC nominal and 24 VDC nominal mix use.
Nominal current: 10 mA - 2 A AC/DC.
GENIbus terminal
-7 to +12 VDC.
Nominal current condition: 4 mADC.
Short-circuit current condition: 328 mA.
Terminal impedance: 120 Ω.
CIO terminals
All analogue signals have an out-of-range alarm.
Voltage
Current

Temperature

Digital input mode
Digital output mode
DIO terminals
Digital input mode
Digital output mode
10
Maximum power dissipation
4.3 W
0 - 10 V
0 - 5 V
0 - 3.5 V
0 - 20 mA
4 - 20 mA
Pt100 2-wire.
Pt1000 2-wire.
Measurement range: -30
to +180 °C (-22 °F to +356 °F).
Low logic level below 1.8 V.
High logic level higher than 2.7
V.
Open collector.
Current sink capability: maxi-
mum 75 mA, no sourcing.
Overcurrent protected.
Low logic level below 1.8 V.
High logic level higher than 2.7
V.
Open collector.
Current sink capability: maxi-
mum 75 mA, no sourcing.
Overcurrent protected.
DI terminal
Digital input mode

5.2 Mechanical data

Altitude
Maximum 2000 m (6562 ft).
5.3 Temperature
Ambient temperature
Minimum
-30 °C (-22 °F)
Maximum
+70 °C (+158 °F)
Storage temperature
Minimum
-40 °C (-40 °F)
Maximum
+70 °C (+158 °F)

5.4 Environmental data

Humidity
5-95 %.
Enclosure class
IP20.

6. Disposing of the product

This product or parts of it must be disposed of in an environmentally
sound way.
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company or
service workshop.
The crossed-out wheelie bin symbol on
a product means that it must be dis-
posed of separately from household
waste. When a product marked with
this symbol reaches its end of life, take
it to a collection point designated by
the local waste disposal authorities.
The separate collection and recycling
of such products will help protect the
environment and human health.
See also end-of-life information at
recycling.
Low logic level below 1.8 V.
High logic level higher than 2.7
V.