Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.

Specifications

Table 1: Loop and mechanical specifications
Max. loop board current
consumption (no devices
connected)
Max. loop output current
ZP7 Series protocol
900 Series protocol
Supply voltage range
ZP7 Series protocol
900 Series protocol
Modulation voltage range
Control level voltage
Resistance
ZP7 Series protocol
900 Series protocol
Capacitance
ZP7 Series protocol
900 Series protocol
LED indications
Data transmission (TX)
Data receipt (RX)
Temperature
Operation
Storage
Relative humidity
Dimensions (W x H)
Weight
[1] Supplied by the control panel.
[2] ZP7 Series protocol only.
[3] Based on 3.5 km max. cable length with 2 mm² diameter for up to
127 devices.
Table 2: Configurable output specifications
Supervision [1]
Class A
Class B
Maximum output current [2]
Maximum electrical
characteristics for sounder
activation
Output voltage range
Open circuit
Standby
Activation
Short circuit
[1] Reverse polarity, end-of-line resistor.
[2] The maximum system consumption limit (Imax b) depends on the
control panel power supply – see your control panel installation
manual for details.
2 / 28
50 mA at 24 VDC [1]
800 mA
250 mA
19.50 to 20.50 VDC
17 to 28 VDC ±1% (+ protocol
modulation)
< 1 VDC (low level) [2]
8 VDC ±1 V
75 Ω max. [3]
52 Ω max. (26 Ω per wire)
700 nF max.
500 nF max.
2 red LEDs (one per loop)
2 green LEDs (one per loop)
−5 to +40°C
−20 to +60°C
10 to 95% noncondensing
106 x 110 mm
110 g
4.7 kΩ 1%, 1/4 W
15 kΩ 1%, 1/4 W
750 mA per output at 25°C
675 mA per output at 40°C
1 A startup current (t ≤ 2ms), load
100 µF
−21 to −28 VDC
−6.1 to −13.7 VDC
21 to 28 VDC
Less than −6.1 VDC
Regulatory information
Conformity
Manufacturer
Carrier Manufacturing Poland Spółka Z o.o.,
Ul. Kolejowa 24, 39-100 Ropczyce, Poland.
Authorized EU manufacturing representative:
Carrier Fire & Security B.V., Kelvinstraat 7,
6003 DH Weert, Netherlands.
Contact information and product
documentation
For contact information or to download the latest product
documentation, visit firesecurityproducts.com.
Product warnings and disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE TO AND
INSTALLATION BY QUALIFIED PROFESSIONALS.
CARRIER FIRE & SECURITY B.V. CANNOT PROVIDE ANY
ASSURANCE THAT ANY PERSON OR ENTITY BUYING ITS
PRODUCTS, INCLUDING ANY "AUTHORIZED DEALER" OR
"AUTHORIZED RESELLER", IS PROPERLY TRAINED OR
EXPERIENCED TO CORRECTLY INSTALL FIRE AND
SECURITY RELATED PRODUCTS.
For more information on warranty disclaimers
and product safety information, please check
https://firesecurityproducts.com/policy/product-
warning/ or scan the QR code:
CS: Instalační návod
Popis
Deska ZP2-A-LB Loop Board poskytuje dvě další smyčky
(LOOP3 a LOOP4) a čtyři další hlídané výstupy (OUT5, OUT6,
OUT7 a OUT8) pro kompatibilní ústředny ZP2-A.
Upozornění:
Deska ZP2-A-LB Loop Board je kompatibilní
pouze k montáži do ústředen ZP2-A.
Instalace
VAROVÁNÍ:
Aby nedošlo ke zranění nebo smrti v důsledku
zásahu elektrickým proudem, odpojte před samotnou instalací
produktu ústřednu od síťového napájení a baterií.
Doporučené kabely
Použijte stíněnou nebo nestíněnou kroucenou dvoulinku
o průřezu 0,13 až 3,31 mm² (12 až 26 AWG). Obvod
zakončete uzemňovacími kolíky ve skříni ústředny.
Další doporučení týkající se kabelů a zapojení naleznete
v instalační příručce k ústředně.
P/N 00-3301-501-2000-02 • ISS 30NOV22

Advertisement

Table of Contents
loading

Table of Contents