Connect Power Cables; Fdap Gen3 And Fdap Gen3 Anchor - Honeywell Field Device Access Point User Manual

Onewireless
Table of Contents

Advertisement

Connect power cables

FDAP Gen3 and FDAP Gen3 Anchor

The FDAP Gen3 and FDAP Gen3 Anchor have one Ethernet cable and one power cable.
Ethernet interconnection is limited to installations outside Class I Division 1, Zone 0/1
locations. You must construct conduit and cable runs for power and Ethernet. The FDAP
Gen3 and FDAP Gen3 Anchor can be powered directly by external DC power supply such
as, distributed DC source. Ensure that all wires inside the enclosure are routed and
secured properly as displayed in the following figure. The FDAP Gen3 and FDAP Gen3
Anchor have integrated terminal blocks that allow field wiring to be directly terminated
inside the FDAP Gen3 and FDAP Gen3 Anchor have one Ethernet cable and one power
cable. without an additional external junction box. DC Power connection, Ethernet and
Serial connections can be terminated outside the FDAP Gen3 and FDAP Gen3 Anchor
have one Ethernet cable and one power cable. .
DC power wiring
When powered from an external DC source, the power cable should be terminated to the
two-position terminal block (E2) on the Power Board. The polarity of the connector is
marked next to the connector on the Power Board. The power cable should be shielded,
and the drain wire grounded inside the enclosure as displayed in the following figure 14
and figure 15.
It is recommended to use RS-485 or Ethernet one at a time to meet IP66
and IP67 requirements.
ATTENTION
FDAP Gen3 Ethernet and field DC power
Fig. 14.
OWDOC-X256-en-323A
FDAP INSTALLATION
28