Siemens SIMATIC S7-1500 CPU 1511-1 PN Equipment Manual page 41

Hide thumbs Also See for SIMATIC S7-1500 CPU 1511-1 PN:
Table of Contents

Advertisement

Article number
I/O address area
per integrated IO subsystem
per CM/CP
Subprocess images
Number of DP masters
Number of IO Controllers
Rack
PtP CM
Clock
Operating hours counter
Clock synchronization
CPU 1511-1 PN (6ES7511-1AL03-0AB0)
Equipment Manual, 11/2022, A5E40869673-AC
per priority class, max.
Address area
Number of IO modules
Inputs
Outputs
Inputs (volume)
Outputs (volume)
Inputs (volume)
Outputs (volume)
Number of subprocess images, max.
Hardware configuration
Number of distributed IO systems
Via CM
integrated
Via CM
Modules per rack, max.
Number of lines, max.
Number of PtP CMs
Time of day
Type
Backup time
Deviation per day, max.
Number
supported
Technical specifications
6ES7511-1AL03-0AB0
64 kbyte; max. 16 KB per block
 
2 048; max. number of modules / submodules
 
32 kbyte; All inputs are in the process image
32 kbyte; All outputs are in the process image
 
8 kbyte
8 kbyte
 
8 kbyte
8 kbyte
 
32
 
32; A distributed I/O system is characterized not
only by the integration of distributed I/O via
PROFINET or PROFIBUS communication modules,
but also by the connection of I/O via AS-i master
modules or links (e.g. IE/PB-Link)
 
4; A maximum of 4 CMs/CPs (PROFIBUS,
PROFINET, Ethernet) can be inserted in total
 
1
4; A maximum of 4 CMs/CPs (PROFIBUS,
PROFINET, Ethernet) can be inserted in total
 
32; CPU + 31 modules
1
 
the number of connectable PtP CMs is only lim­
ited by the number of available slots
 
 
Hardware clock
6 wk; At 40 °C ambient temperature, typically
10 s; Typ.: 2 s
 
16
 
Yes
41

Advertisement

Table of Contents
loading

This manual is also suitable for:

6es7511-1al03-0ab0

Table of Contents