Tecnoautomazione T182A User Manual

Tecnoautomazione T182A User Manual

Swing gate control unit

Advertisement

Quick Links

T182A.
ON
3 4 5 6 7 8 9 10
1
2
LEFT / DIP-SWITCH
RC1
RC2
R1
R2
REMOTE
R3
R4
TIME
A
B
C
OBSTACLE
1
2
3
4
5
6
7
INPUT
INTERNAL
RECEIVER
LEDs:
S1.S2.S3. GATE STATUS / CONTROL BOARD STATUS LEDS
RC1.RC2.R1.R2.R3.R4. RADIO LEDS
RC1. SHOWS THAT A SIGNAL HAS BEEN RECEIVED FROM THE INTERNAL RADIO RC1
RC2. SHOWS THAT A SIGNAL HAS BEEN RECEIVED FROM THE EXTERNAL RADIO RC2
R1. START: INDICATES THAT A START BUTTON ON THE REMOTE HAS BEEN PRESSED
R2. STOP: INDICATES THAT A STOP BUTTON ON THE REMOTE HAS BEEN PRESSED
R3. PEDESTRIAN: SHOWS THAT A START PEDESTRIAN BUTTON ON THE REMOTE HAS BEEN PRESSED
R4. OUT1 ON/OFF: SHOWS THAT A OUT1 BUTTON ON THE REMOTE HAS BEEN PRESSED
A.B.C. PROGRAMMING LEDS
1.2.3.4.5.6.7. INPUTS
AUSILIARY OUTPUTS:
EXPANSION RELAY MODULE - OUT1. ENABLED/DISABLED VIA REMOTE (FUNCTION R4). IF THE RIGHT DIP10 IS ON, THE OUT1 IS ON FOR 3 MIN
AFTER EACH OPENING PHASE.
EXPANSION ELECTRIC-LOCK MODULE OUT2. ENABLED AT OPENING FOR 3 SEC.
LEFT DIP-SWITCH (1) FUNCTIONS
MOTORS POWER. DIP 1 - 2.
OFF / OFF = 40%
1
2
3 4 5 6 7 8 9 10
ON / OFF = 60%
1
2
3 4 5 6 7 8 9 10
OFF / ON = 80%
1
2
3 4 5 6 7 8 9 10
ON / ON = 100%
1
2
3 4 5 6 7 8 9 10
SLOW DOWN. DIP 3.
OFF = DISABLED
1
2
3 4 5 6 7 8 9 10
ON = ENABLED
1
2
3 4 5 6 7 8 9 10
POWER 100%
OBSTACLE DETECTION SENSOR. DIP 4.
OFF = DISABLED
1
2
3 4 5 6 7 8 9 10
ON = ENABLED
1
2
3 4 5 6 7 8 9 10
ELECTRONIC LIMIT SWITCH. DIP 5.
OFF = DISABLED
1
2
3 4 5 6 7 8 9 10
ON = ENABLED
1
2
3 4 5 6 7 8 9 10
SWING GATE CONTROL UNIT. POWER SUPPLY 230 VAC. FREQUENCY 433.92 MHz. 100 STORABLE CODES.
3 4 5 6 7 8 9 10
1
2
RIGHT / DIP-SWITCH
EXTERNAL
RECEIVER
8
9 10 11 12
SOFT START. DIP 6 - 7.
1
2
3 4 5 6 7 8 9 10
1
2
3 4 5 6 7 8 9 10
1
2
3 4 5 6 7 8 9 10
1
2
3 4 5 6 7 8 9 10
GATE LEAVES DELAY. DIP 8 - 9.
1
2
3 4 5 6 7 8 9 10
1
2
3 4 5 6 7 8 9 10
1
2
3 4 5 6 7 8 9 10
1
2
3 4 5 6 7 8 9 10
MOTORS AND PHOTOCELLS TESTS. DIP 10.
1
2
3 4 5 6 7 8 9 10
1
2
3 4 5 6 7 8 9 10
5A FUSE
13 14 15
16 17 18
A MOTOR
B MOTOR
MODES. DIP 1 - 2.
OFF / OFF = 0.1 sec
OFF / OFF = AUTOMATIC CLOSURE
1
2
3 4 5 6 7 8 9 10
ON / OFF = 0.5 sec
ON / OFF = COMMUNITY MODE
1
2
3 4 5 6 7 8 9 10
OFF / ON = 1.0 sec
OFF / ON = STEP-BY-STEP MODE
1
2
3 4 5 6 7 8 9 10
ON / ON = STEP-BY-STEP + AUTOMATIC
ON / ON = 1.5 sec
1
2
3 4 5 6 7 8 9 10
ELECTRIC-LOCK. DIP 3 - 4.
OFF / OFF = 0 sec
1
2
3 4 5 6 7 8 9 10
ON / OFF = 3 sec
1
2
3 4 5 6 7 8 9 10
OFF / ON = 6 sec
1
2
3 4 5 6 7 8 9 10
ON / ON = 12 sec
1
2
3 4 5 6 7 8 9 10
FAST CLOSURE. DIP 5.
OFF = DISABLED
1
2
3 4 5 6 7 8 9 10
ON = ENABLED
1
2
3 4 5 6 7 8 9 10
OIL RECIRCULATION. DIP 6.
1
2
3 4 5 6 7 8 9 10 11 12
1
2
3 4 5 6 7 8 9 10 11 12
INPUTS:
1. START OR OPEN N.O.
2. STOP N.C.
3. EXTERNAL PHOTOCELL N.C.
closing phase: inverts the gate movement
4. INTERNAL PHOTOCELL N.C.
opening phase: pauses the gate movement
closing phase: inverts the gate movement
G
R
5. MOTOR «A» LIMIT SWITCHES N.O.
O
U
N
6. MOTOR «B» LIMIT SWITCHES N.O.
D
7. PEDESTRIAN OR CLOSE N.O
N
L
230 VAC
S1 S2 S3
BOARD STATUS:
x
STAND BY, GATE CLOSED
19
20
GATE IN OPENING OR CLOSING PHASE,
GATE OPEN
PROGRAMMING OF WORKING TIMES /
OBSTACLE SENSOR
PROGRAMMING ERROR
PHOTOCELLS ERROR
MOTOR A ERROR:
A
CONNECTION
B
ERROR OR MOTOR
OVERHEATING
C
MOTOR B ERROR:
A
CONNECTION
B
ERROR OR MOTOR
OVERHEATING
C
RIGHT DIP-SWITCH (2) FUNCTIONS
1
2
1
2
CLOSURE
DISABLED NOT WIRED N.C. INPUTS. DIP 8.
OFF / OFF = STANDARD
1
2
ON / OFF = KICK BACK AT
CLOSING 1 sec
OFF / ON = KICK BACK AT
OPENING
ON / ON = KICK BACK AT
1
2
CLOSING + KICK BACK AT
OPENING
OFF = DISABLED
1
2
ON = ENABLED
1
2
OFF = DISABLED
1
2
ON = ENABLED
1
2
A
OBSTACLE
B
DETECTED
C
A
OBSTACLE
B
DETECTED
C
MODE 1 OR 2 MOTORS. DIP 7.
OFF =
2 MOTORS MODE
3 4 5 6 7 8 9 10
ON =
1 MOTOR MODE
3 4 5 6 7 8 9 10
OFF =
N.C. INPUTS ENABLED
3 4 5 6 7 8 9 10
ON =
NOT WIRED N.C.
3 4 5 6 7 8 9 10
INPUTS DISABLED
INPUTS OPTION 1 - 7. DIP 9.
INPUT 1 = START
OFF =
3 4 5 6 7 8 9 10 11 12
INPUT 7 = PEDESTRIAN
INPUT 1 = OPEN
ON =
3 4 5 6 7 8 9 10 11 12
INPUT 7 = CLOSE
COURTESY LIGHT. DIP 10.
OFF = DISABLED
3 4 5 6 7 8 9 10
ON = ENABLED
3 4 5 6 7 8 9 10

Advertisement

loading
Need help?

Need help?

Do you have a question about the T182A and is the answer not in the manual?

Questions and answers

Summary of Contents for Tecnoautomazione T182A

  • Page 1 T182A. SWING GATE CONTROL UNIT. POWER SUPPLY 230 VAC. FREQUENCY 433.92 MHz. 100 STORABLE CODES. INPUTS: 3 4 5 6 7 8 9 10 3 4 5 6 7 8 9 10 1. START OR OPEN N.O. LEFT / DIP-SWITCH RIGHT / DIP-SWITCH 2.
  • Page 2 TERMINAL BLOCK CONNECTIONS POWER SUPPLY START STOP MOTORS 13 14 15 16 17 18 5 6 7 8 9 10 11 12 5 6 7 8 9 10 11 12 2 3 4 2 3 4 13.16 open 14.17 common 15.18 close PHOTOCELLS TRANSMITTER EXTERNAL PHOTOCELL INTERNAL PHOTOCELL...
  • Page 3 FUNCTIONS DESCRIPTION SLOW DOWN: THE GATE SLOWS DOWN FOR THE SET SLOW DOWN TIME AT THE END OF THE OPENING AND CLOSING PHASES. DURING THE SLOW DOWN PHASE THE MOTORS WORKS AT THEIR MAX POWER. PEDESTRIAN: ONLY GATE LEAF A IS INVOLVED IN THE OPENING PHASE. GATE LEAF B REMAINS CLOSED. SOFT START: THE MOTORS POWER INCREASES GRADUALLY TILL IT REACHES ITS MAX VALUE.
  • Page 4 European Union This symbol is only valid in the European Union (EU). If you wish to discard this product please contact your local authori es ordealer and ask for the correct method of disposal. MADE IN ITALY T.A. Tecno Automazione s.r.l. - Via Vicinale snc - 03018 - Paliano - (FR) - Italy - Tel +39 0775 533677 - Fax +39 0775 533299 - info@tecnoautomazione.com - www.tecnoautomation.com - www.tecnoautomazione.com...