EDS EGOS Installation Manual

Addressed gas detection systems esternal siren

Advertisement

Quick Links

NEPTUNE
EGOS
ADDRESSED GAS DETECTION SYSTEMS
ESTERNAL SIREN
Installation Manual
www.edselectronic.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EGOS and is the answer not in the manual?

Questions and answers

Summary of Contents for EDS EGOS

  • Page 1 NEPTUNE EGOS ADDRESSED GAS DETECTION SYSTEMS ESTERNAL SIREN Installation Manual www.edselectronic.com...
  • Page 2: Product Family

    Gas Control Panel Loop Card Addressed Carbon Monoxide EGCN2 Addressed Carbon Monoxide and Nitrogen Dioxide Detector EGN2 Addressed Nitrogen Dioxide Detector Addressed Nitrogen Oxide Detector EGOS Addressed External Siren EGLS Addressed Loop Siren Addressed Relay EGIM Addressed 4-20mA Entrance Module...
  • Page 3 PHYSICAL LED Indicator...
  • Page 4: Technical Specifications

    TECHNICAL SPECIFICATIONS Model EGOS Environmental class Outdoor Electrical Nominal voltage 24V DC ± %10 Supply voltage range 21-28V DC Stand-by current <32mA Alarm current <300mA Audio output 102dB-108dB Audio frequency 2.4Khz - 2.9Khz Audio type Programmable sounder period 3/5/10/15min. Selectable...
  • Page 5 The first 2 digits of the serial number on the product indicate the production date (The number on the label of the product). Producer EDS Elektronik Destek Sanayi ve Ticaret Ltd. Meclis Mah. Teraziler Cad. Hayran Sk. No: 4 34785 Sancaktepe / İstanbul / Turkey...
  • Page 6: Main Board

    CONNECTION Mainboard In Figure 1, siren PCB card and connections are shown. SIGN G.IN SIGN BUZZER G.OUT +24V CELL Loop and external supply Buzzer connection Jumpers for voice time and voice type Figure 1: Mainboard...
  • Page 7 Piezo Buzzer connection Figure 2: Buzzer connection EGOS Siren Panel Connection External supply and lop connections are made as shown in Figure 3. Figure 3: Mainboard panel connection...
  • Page 8: Default Values

    Sound Level Settings Alarm type and alarm period can be selected with jumpers. To adjust the type and period, firstly the device connection with loop is cut. The jumpers are adjusted by looking at the following tables. Finally, the loop connector is restrung.
  • Page 9 MOUNTING In this part, the siren mounting is told. Please do not start the mounting operation before understanding the system, parts and the working principle of the system. You are recommended to start mounting after reading the warning and the points to take into consideration. WARNING Anti-static measures should be taken before touching electronic materials.
  • Page 10 Mounting of the Upper Cover Mount the upper cover by using the two screws edgewise. Screw place Hanger place Cable channel Protecting cover Figure 4 : Lower cover Important Mounting Notes For the opening of the upper cover during mounting, it should be minimum 5cm lower than the ceiling.
  • Page 11: Error Recovery Procedures

    FIRST OPENING Power-up the siren. Make the required outlet connections. Mount the loop connector. You can see your automatic learning-after data over the control panel. ERROR RECOVERY PROCEDURES The errors occurring in the detector come to the control panel as error. If there is communication error, the cable connections should be checked.
  • Page 12 10.19 V1 Technical specifications are subject to change without prior notice. EDS Elektronik Destek San. Ve Tic. Ltd. Şti. Meclis Mah. Teraziler Cad. Hayran Sok. No:4 34785 Scan this code with your Sancaktepe / İstanbul / Turkey +90 216 528 45 00 smartphone to visit eds@eds.com.tr...