NEPTUNE Neptune Series Addresable LPG Detector Measuring Range LPG: 0-100 %LEL EGLL ADDRESSABLE GAS DETECTION SYSTEM ADDRESSABLE LPG GAS DETECTOR Warranty Certificate & User Manual www.edselectronic.com...
Liability Limitation To the extent allowed by the laws, EDS shall not be responsible, within the framework of any liability whatsoever, for any loss or business loss, usage loss, interruption of works, data loss, or any other indirect, incidental, special, or conditional damages that arise from contract, tort, negligence, product liability, or any other issue.
TECHNICAL SPECIFICATIONS Model EGLL Environment Class Indoor Environment Electrical Communication RS485 Supply voltage range 20-28V DC Nominal voltage 43mA Alarm current 43mA Sensor Sensor Type Catalytic Gases Detected LPG (Butane, Propane) Detection range 0-100 %LEL Measurement unit %LEL Reaction Time <10s Warm up time 10 min...
Page 5
The first 2 digits of the serial number on the product indicate the date of manufacture. (The number on the label of the producer) EDS Elektronik Destek Sanayi ve Ticaret Ltd. Manufacturer Meclis Mah. Teraziler Cad. Hayran Sk. No: 4 34785 Sancaktepe / İstanbul / Türkiye...
MOUNTING AND CABLING This section describes the detector mounting. Please do not start the mounting process without understanding the system, its parts and the working principle of the system. It is recommended to start the assembly after reading the warnings and points to be considered.
For detector mounting, mount it from the necessary places using M3x30 mm screw and Ø 6mm plastic socket. It is recommended to mount the detector at a height of 15-25cm (Figure 1) Detector 15-25cm Figure 1: Mounting Height Cabling In the cabling, the functions of the cables should be specified with the labels.
Wall Mounting Place Cover Screws 20M Cable Gland Connection Sensor Place Figure 2 : Gas Detector Illustration Electrical Connection Detector connections are as shown in Figure 3. Loop Connection Addressing Button Address LEDs L1 L2 L3 Figure 3 : Gas Detector Connection...
Page 9
Control Panel Detector Connections The connection between the Detector and the Control panel is made through loops as shown in Figure 4. Figure 4 : Control Panel Detector Connections...
FIRST OPERATION Power up the detector. Make the necessary output connections. Plug in the loop control panel. You can see your data after automatic learning through the control panel. In normal operation, the yellow LED lights up every 15 seconds.
Page 11
ADDING THE DEVICE TO THE PANEL It is connected to its counterpart (VCC A B GND) on the panel from the device connections. Panel power is cut off and restarted. To enter the automatic learning mode, the right button is pressed for 3 seconds during the initial phase.
Page 12
Note Parts marked with an x in the table indicate that it is lit. Long press the up button again. The lit LEDs go out and the addressing process is finished. Between 1-12, zone 1, between 13-22, zone 2, between 23-32, the address is used as zone 3.
TROUBLESHOOTING Errors in the detector are sent to the control panel as errors. In case of error, the yellow LED on the detector flashes continuously. If there is a communication error, the cable connections should be checked. Breaks in the cables may cause an error. WARNING Make sure to make the connections properly.
Page 16
When your device has reached the end of its useful life, contact your local authority for disposal and recycling options, take it to a collection point for the recycling of electrical and electronic equipment or hand it over to EDS Elektronik. This product does not contain harmful or prohibited substances specified in the Regulation on the Control of Waste Electrical and Electronic Equipment issued by the Turkish Republic Ministry of Environment and Urbanization.
WARRANTY CERTIFICATE The terms of the warranty is valid for products sold in Europe Union. Failure to occur during loading, unloading and shipment after delivery of the goods is not covered by the warranty. Damage, malfunction and information services caused by operating errors are not covered by the warranty.
Page 18
This period starts from the notification date of the product’s failure to the service station and in default of the service station, so one of those as the product’s seller, dealer, agent, representation,importer or importer-producer. If the product is not troubleshot with in 10 days, the importer-producer or importer must assign another product within similar properties to the use of the consumer till the product’s repair is completed.
Page 19
Ministry of Customs and Trade. Producer Manufacturer title / Service address: Stamp / Signature: EDS Elektronik Destek San. ve Tic. Ltd. Şti. Meclis Mah. Teraziler Cad. Hayran Sok. No:4 34785 Sancaktepe/Istanbul/Turkey Tel: 0216 528 45 00 Fax: 0216 314 17 80 e-mail: eds@eds.com.tr www.edselectronic.com...