OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS

FIG. 1:

  1. Manual control.
  2. Programming dial.
  3. Index.

DESCRIPTION

INCA DUO time switch controls any electrical installation through daily (D and QRD) or weekly programs (S and QRS).

INSTALLATION


Installation and mounting of electrical devices must be carried out by an authorised fitter.

The device must not be installed near inductive loads (meters, transformers, transformer centres, industrial machinery, etc.)

The device is internally protected against interference by a security circuit. However, some particularly strong magnetic fields may alter its functioning.

MOUNTING: Electronic control device of independent mounting in distribution cabinet provided with symmetric profile of 35 mm. in accordance with EN 60715 standard (DIN Rail).

CONNECTION

CONNECTION

Connect according to the diagram in FIG. 2 taking into account that it's a volt-free changeover contact.

PROGRAMMING

Move all pins to the right. Move to the left the pins corresponding to the desired connection times, in which contact 1 – 2 will remain closed.

TIME SETTING

Turn the dial in the indicated direction until the index shows the current time.

MANUAL CONTROL

2 settings:
-Automatic mode.
I- Permanent connection (1 - 2 always closed).

TECHNICAL FEATURES

Rated voltage: As indicated in the device.
Breaking capacity: 16(4) A /250 V~
Action type: D: 1B, 1T, 1U, 1R
QRD y QRS: 1B, 1T, 1U, 1S
Own consumption: 0.5 W
Running accuracy: ±1 sec./day at 22 ºC
Power reserve: D and S: No reserve
QRD and QRS: 100 hours after 48 hours of uninterrupted connection.
Dial type: Daily: 96 pins.
Weekly: 84 pins.
Minimum manoeuvre time: Daily: 15 minutes Weekly: 2 hours
Manoeuvre accuracy: Daily dial: ± 5 min. Weekly dial: ± 30 min.
Operating temperature: -10 ºC to +45 ºC
Degree of protection: IP 20 in accordance with EN 60529
Protection class: II under correct mounting conditions.
Rated impulse voltage 2,5 kV
Pollution situation: Sealable cover. 2.


This time switch includes, in the models with power reserve, a battery whose contents may be damaging to the environment. Do not get rid of the product without taking the precaution of dismantling the battery and placing it in an appropriate recycling container, or sending the product to the factory.

E-mail: info@orbis.es
http://www.orbis.es

Documents / Resources

References

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download ORBIS INCA DUO - Timer Switch Manual

Advertisement

Need help?

Need help?

Do you have a question about the INCA DUO and is the answer not in the manual?

Questions and answers

Table of Contents