Advertisement
Analogue time switch with daily and weekly programming. Plug in screw terminal base, or "fast on" terminals. For the timed control of electrical equipment and systems.
Automatic control, independent mounting of wall mounting or 35mm rail in accordance DIN EN 60715.
Shift all the pins upwards and shift downwards the corresponding pins to the desired connection times, in which the 2-3 contact will stay closed.
Turn the dial clockwise so that it meets with real time. The clock hands must meet with real time.
3 positions:
- permanently on (2-3 closed)
- automatic operating
- permanently off (2-3 open)
Supply: According with nameplate
Switching capacity: 16 (4) A / 250 V
Recommended maximum loads:
Own consumption: 1,8VA
Type of action: 1 BSTU in accordance EN 60730-2-7
Accuracy: ± 1 s/day at 23°C
Type of dial: Daily: 96 pins Weekly: 84 pins
Minimum switching time:
D/QRD: 15 minutes
QRS: 2 hours
Operating mode: step by step motor
Operating temperature:-10ºC to +45ºC
Contact: AgCdO One pole changeover
Battery reserve:
Type D: without reserve
Type QRD and QRS: 100 hours after uninterrupted supply of 48 hours.
Pollution situation: 2
This unit incorporates, in models with reserve, a battery which contents can be harmful to the environment. Please do not throw it away without removing the battery and putting it in the proper container for recycled or to send the complete unit back to the factory.
ORBIS TECNOLOGÍA ELÉCTRICA, S.A.
Lérida, 61 Telf.:+ 34 91 5672277;
E–28020 MADRID Fax: +34 91 5714006
E-mail: info@orbis.es
http://www.orbis.es
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Advertisement
Thank you! Your question has been received!
Need Assistance?
Do you have a question about the MINI T that isn't answered in the manual? Leave your question here.