Page 2
EXPLANATION The device switches to alarm state when the detected smoke reaches the alarm threshold. Red alarm LEDs turn on in case of alarm. In addition to that, the relay is activated and terminal 2 short-circuited to terminal 3. If the contact between terminal 5 and terminal 6 is closed, alarm condition continues at least 30 seconds.
Page 3
Impurity Compensation (Drift Compensation) The impurity compensation is a microprocessor controlled and smart algorithm compensating the impurity of the optical cell up to a certain level. When it reaches to the limit level, it gives a warning by flashing the error LED in every 4 seconds for cleaning the cover.
Page 4
PHYSICAL Optical Cell Live indicator LED Alarm LED indicator...
TECHNICAL SPECIFICATIONS Model OD12R Environmental class II indoor Electrical Supply voltage range 10V-15V DC Stand-by current <40 μA Alarm current <20mA Alarm indicator Double LED Red Fault indicator Single LED Yellow Live indicator LED Single LED Green Reset Auto / Locked...
Page 6
The year and week of manufacture is included in the first four digit of your product serial number (located on the product identification label) Manufacturer EDS Elektronik Destek Sanayi ve Ticaret Ltd. Meclis Mah. Teraziler Cad. Hayran Sk. No: 4 34785 Sancaktepe / Istanbul / TURKEY Recycle...
CONNECTION Detector Connections OD12R Connections / Ratings Function Terminal Specification Supply 10-15V DC Current (Stand by): ≤40µA Current (Alarm): ≤20mA Relay Output Zone + 12 Relay: 12V 1A RÖLE Diode: 1N4001 OD12R Out(-) Open ( Iatch ) Close ( Auto )
Panel Connections Zone MOUNTING Warning: The general system design shall be made by paying regards to mounting, implementation, operating and maintenance EN54-7 standard and local regulations.
Installation Place the detector to its base, and rotate clockwise till hearing the click sound (Figure 1). The detector shall be locked to its base. You can also make another locking operation by rotating the allen screw found in the base for those with 5 pins. Test absolutely after mounting the detector to its place.
Page 12
12.19 V2 Technical specifications are subject to change without prior notice. Scan this code with your smartphone to visit www.edselectronic.com...
Need help?
Do you have a question about the OD12R and is the answer not in the manual?
Questions and answers