Page 1
END TO END TYPE RK100BS-EX TECHNICAL MANUAL TECHNICAL INSTRUCTIONS FOR ASSEMBLY START AND MAINTENANCE ATEX EDS - V. Ca' Nova Zampieri 6 - 37057 S. G. Lupatoto - VERONA - Tel. 045/ 547529 - Fax 045/8750065 - Email: eds@eds.eu - Web: www.eds.eu...
EN50130-4: 1995 / A2: 2003 ATEX Directive 2014/34 / EU 1.1 - The installation of the RK100BS-EX detector must be carried out according to the rules indicated in the Italian standards UNI 9795 (Automatic fixed detection, manual signaling and fire alarm systems. Systems with point detectors of smoke and heat , linear optical smoke detectors and manual signaling points).
EDS - INFORMAZIONI TECNICHE 2.2 - The RK100BS-EX detector can be installed in areas with danger of explosion: zone 1 - zone 2 - zone 21 - zone 22. It must not be installed in a hazardous area classified as zone 0.
9 - OPERATION 9.1 - The RK100BS-EX detector is equipped with a smoke detection circuit produced by a fire: • DARKENING - circuit sensitive to darkening. This circuit bases its operation on the decrease in the intensity of the infrared beam, along the optical path...
Page 6
10 - OPTICAL ALIGNMENT WITH POINTER LASER BLP-100 10.1 - The BLP pointers are installed on board the EDS optical detectors in order to speed up the optical alignment operations between TX and RX (for barrier devices) or between the detector and its optical reflector (for reflection reflectors) 10.2 - The BLP laser pointer is an accessory that makes the installation of EDS detectors very fast.
Page 7
JP2 - JP4 jumpers to set the output contact respectively of the Alarm relay and normally closed NC fault or normally open NA (see fig.1) The RK100BS-EX detector is supplied with normally closed NC set contacts. For the Alarm relay the indication of JP2 is valid if JP7 is in the OFF position.
Page 8
EDS - INFORMAZIONI TECNICHE • in position 2-3 memory inserted. In the event of an alarm the detector remains in alarm until the voltage is removed for 5 seconds JP6 - jumper for microprocessor Reset JP7 - jumper for setting the Alarm relay operating mode normally energized or de-energized •...
Page 9
EDS - INFORMAZIONI TECNICHE • if the signal exceeds 4.9V, both blue and red LEDs light up steadily. This indicates saturation. 12.8 - The following table summarizes the above data. ° ° < > 12.9 - Then act on trimmer P1 until the signal level indicated by the LEDs and displayed through the porthole, is between 4 - 4.8V (blue LED flashing or fixed).
• circuit operating anomaly (means failure of some component) 15 - ALARM MEMORY AND DATA 15.1 - The RK100BS-EX receiver is equipped with an alarm memory that can be enabled / disabled using the JP5 jumper (fig.1): • jumper JP5 in position 1-2 - memory not activated (OFF) •...
17.4 - The internal electronics waits 5 minutes for the cover to be installed and then performs a rapid procedure (time 1-2 minutes) to restore the RK100BS-EX signal back to 4.7-5V (normal operation level ) 17.5 - Once this adjustment phase has ceased, the detector becomes operational. The blue Alignment LED ceases the particular flashing indicated in chap.10.2 and starts to flash as indicated in 17.6...
EDS - INFORMAZIONI TECNICHE 19 - INDICATION OF FRONT LEDS 19.1 - The TX LED flashes every 10 seconds. The front LEDs of the RX during normal operation of the detector, give the following indications: • normal operation: the blue LED flashes every 10 seconds •...
Page 15
EDS - INFORMAZIONI TECNICHE disco bianco white disc foro hole view of the white disk inside the optic sensore sensor diodo fotoemittente photoemitting diode fig.1 optical beam emitted by the TX fig.2 diametro del raggio [cm] distanza [m] fig.3...
Page 16
EDS - INFORMAZIONI TECNICHE VIEW OF INTERNAL PARTS OF THE RECEIVER DS1651B LED di allineam ento Laser BLP100 LED di Allarm e fault relay SENS alarm relay SW 2 M EM fig.4...
Page 17
JP4 (relative to the Fault relay) must be in position 1-2 to have the contact closed because the Fault relay is normally energized. The RK100BS-EX detector is supplied with normally closed NC set contacts. For the Alarm relay the indication of JP2 is valid if JP7 is in the OFF position.
Page 18
EDS - INFORMAZIONI TECNICHE VIEW OF INTERNAL PARTS OF THE TRANSMITTER DS1653 Laser BLP100 POW ER SW 3 fig.5 SW3 - selector for adjusting transmitter power (TX) - power increases from 1 to 4. Power is maximum in position 4 and minimum in position 1.
Page 20
The alarm signal is given by the Alarm relay (for activation of the circuit sensitive to Darkening) The Fault is signaled using the NC contact of the RK100BS-EX Fault relay. The values of the alarm and line end resistances will be indicated by the control panel manufacturer.
4 - Name, registered trade name or registered trademark and contact address of the manufacturer as required pursuant to article 11(5) : EDS srl , Via Cà Nova Zampieri 6, San Giovanni Lupatoto (Verona) , 37057, Italy 5 - Where applicable, name and contract address of the authorised representative whose mandate covers the tasks specified in article 12(2) : Not applicable.
Page 22
EDS - INFORMAZIONI TECNICHE 9 - Declared Performance. All requirements including all essential characteristics and the corresponding performances for the intended use or uses indicated in 3 have been determined as described in the EN mentioned in the following. Essential Characteristics...
Page 23
1. OBJECT legal action brought by the purchaser based on alleged EDS S.r.l. - Via Cà Nova Zampieri 6, 37057 S. G. Lupatoto - Verona, negligence or other tortuous conduct by EDS, the Purchaser’s Italy (hereinafter “EDS”), guarantees its products to be free from...
Page 24
EDS - INFORMAZIONI TECNICHE The information contained in this document has been carefully evaluated and can be considered reliable. In any case, the EDS company does not take responsibility for any inaccuracies. Furthermore, the EDS company reserves the right to make changes in any part of this document and / or product, such as to increase its quality, reliability or design.
Need help?
Do you have a question about the RK100BS-EX and is the answer not in the manual?
Questions and answers