EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE
END TO END (BARRIER)
OPTICAL BEAM LINEAR

SMOKE DETECTOR

RK100B - RK200B
USER GUIDE
TECHNICAL INSTRUCTIONS FOR
INSTALLATION, SETUP AND
MAINTENANCE
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RK100B and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for EDS RK100B

  • Page 1: Smoke Detector

    EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE END TO END (BARRIER) OPTICAL BEAM LINEAR SMOKE DETECTOR RK100B - RK200B USER GUIDE TECHNICAL INSTRUCTIONS FOR INSTALLATION, SETUP AND MAINTENANCE...
  • Page 2: Table Of Contents

    EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE CHAPTER INDEX 1 - Qualified Personell 2 -Normative references 3 - Installation 4 - Cable Connections 5 - Electrical Connections and Initial Setup 6 - Operation 7 - Optical Allignment...
  • Page 3 EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE STANDARD STARTING CONDITION (Read ahead) • SW1 - position 1 (minimum threshold level) • SW2 - position 1 (minimum threshold level ) • SW3 - position 4 (maximum Trasmitter power ) •...
  • Page 4 EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE QUICK INSTALLATION The procedure below is intended for trained personell with previous experience in installing EDS Beam Smoke Detectors RK100B and RK200B. If you don’t have the needed experience please refer to the standard installation procedure of this manual.
  • Page 5: Qualified Personnel

    EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE GENERAL Note : the following instructions are suitable for the RK100B and RK200B models. The RK100/200B is a new conception of optical beam smoke detector barrier. It’s composed by a...
  • Page 6: Installation

    EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE 3 - INSTALLATION 3.1 - For the installation of the RK100/200B we suggest to use, besides the normal tools (drill, expansion plugs, etc), also the following elements: • 1 - 7mm “C” key •...
  • Page 7: Cable Connections

    EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE 4 - CABLE CONNECTIONS 4.1 - the low detector’s power consumption (20 mA with normally open alarm relay contact (NO) and 30 mA with normally closed alarm relay contact (NC)) allows to use small size sections cables.
  • Page 8: Electrical Connections And Initial Setup

    EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE 5 - ELECTRICAL CONNECTIONS AND INITIAL SETUP 5.1 - Connect the device cables as shown on the labels facing the terminal board. The given symbols indicate what follows: • (V+) - (V -) - supply’s terminals 11 - 30 Vdc •...
  • Page 9 EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE 5.2 - Jumper Settings JP1- to enter/exit the optical alignment procedure. To activate the procedure of optical alignment JP1 must be in 2-3 (ON) position. To deactivate the procedure of optical alignment JP1 must be in 1-2 (OFF) position.
  • Page 10: Operation

    EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE 6 - OPERATION 6.1 - the RK100/200B detector is equipped with 2 circuits of detection of the smoke produced by a fire: • Obscuration - circuit sensitive to obscuration.
  • Page 11: Optical Allignment

    EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE 7 - OPTICAL ALIGNMENT 7.1 - proceed with the optical alignment of Transmitter TX and Receiver RX. To facilitate the operation we suggest to do it in low ambient light conditions and to proceed in the following way: •...
  • Page 12: Setup Of The Obscuration Circuit

    EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE 8 - SETUP OF THE OBSCURATION CIRCUIT Electric signal setup must be performed according to the following sequence: 8.1 - do not power up the TX and the RX 8.2 - on the Transmitter (TX) rotate the selector SW3 in one of the positions 1-2-3-4 (fig.10) according...
  • Page 13 EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE 8.12 - search for the maximum output signal optimizing the optical alignment of the Transmitter acting slowly and in sequence on the 3 screws of regulation V1-V2-V3 present on the optical block.
  • Page 14 EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE • if the signal overcomes 4 V, the blue Led flashes faster and faster as the frequency signal increases up to 4,7V • when the signal overcomes the 4,7V and in the range 4,7V - 4,9V, the blue led is continously ON.
  • Page 15: Set Up Of Turbulence Circuit

    EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE 9 - SETUP OF THE TURBULENCE CIRCUIT 9.1 - The RK100/200B detector is equipped with a special additional circuit for the detection of air Turbulence (heat). This circuit is independent from the classic obscuration one and in particular situations it can be used to increase the performance of the detector.
  • Page 16: Detector's Activation

    10.4 - the inside electronics wait 5 minutes for the installation of the cover and then perform a quick procedure (1-2 minutes) to get the RK100B output signal level back to 4,7-5V 10.5 - after this activation procedure, the detector becomes operational. The blue alignment led switchs off (detail chap.10.2) and it begins to flash as described in 10.6...
  • Page 17: Operational Test

    EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE 12 - OPERATIONAL TEST 12.1 - verification of the circuit sensible to obscuration The verification is done simply darkening the TX or the RX with an opaque screen. After 10 seconds, the RX alarm relay must activate / deactivate (chap.5.2 - jumper JP7) and the frontal alarm red led must be switched on.
  • Page 18: Fault Output

    14 - ALARM MEMORY AND CONFIGURATION DATA 14.1 - the receiver of the RK100B is equipped with alarm memory that can be activated / deactivated with the JP5 jumper (fig.9): •...
  • Page 19: Maintenance

    EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE 16 - MAINTENANCE 16.1 - the instrument requires an easy and periodic maintenance. It can be programmed or made automatic using remote signaling of the detector. During the normal operation and after a certain time from installation, if maintenance is not performed, the detector, because of the dirt and dust deposited on the front of the covers, gives out a fault output signal, because of the decrease of the signal below the limit of compensation.
  • Page 20: Technical Data

    • Models: RK100B, RK200B • Type: Barrier Optical Beam Smoke Detector • Manufacturer: EDS srl - V. Cà Nova Zampieri 6 - 37057 S.G. Lupatoto - Verona - ITALY • Power Supply: 12/24 Vdc • Power Supply Range: 11- 30 Vdc •...
  • Page 21 EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE fig.1 fig.2...
  • Page 22 EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE l a m p a d a L A L r i v e l a t o r e fig.3 disco bianco white disc foro hole diodo fotoemittente photoemitting diode fig.4...
  • Page 23 EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE fig.5 diametro del raggio [cm] distanza [m] 100 120 140 160 180 200 fig.6...
  • Page 24 EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE fig.7...
  • Page 25 EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE ° ° < > r u t i t a fig.8...
  • Page 26 EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE DS1651 LED di allineamento LED di Allarme turbo relay Fehlerrelais fault relay Turborelais TURBO SENS alarm relay Alarmrelais fig.9...
  • Page 27 EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE RECEIVER INTERNAL ELEMENTS P1 - trimmer for the regulation of the signal level. Normally regulated to 50-60% that corresponds to a signal of 5V at the maximum distance SW1 - selector for the regulation of the sensitivity of the circuit sensible to Turbulence (heat).
  • Page 28 EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE TRANSMITTER INSIDE PARTS DS1653 fig.10 POWER SW3 - selector for the regulation of the transmitter power (TX) - power increases from 1 to 4. Maximum power in the position 4 and mimimum in position 1.
  • Page 29 EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE TERMINAL BLOCK OF alimentazione 11-30 Vcc THE TRANSMITTER fig.12 segnale analogico 0-5V analog signal output 0-5V contatto relè GUASTO FAULT relay contact contatto relè TURBOLENZA TERMINAL BLOCK OF TURBULENCE relay contact THE RECEIVER contatto relè...
  • Page 30 EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE CENTRALE DI CONTROLLO alimentazione connessione zona1 segnale analogico 0-5V schermo contatto relè GUASTO resistenza di Allarme contatto relè TURBOLENZA contatto relè d'ALLARME resistenza di fine linea alimentazione 11-30 Vcc fig.14...
  • Page 31 8. PROCEDURE In the event of a defect covered by this warranty, the purchaser should contact EDS - Via Cà Nova Zampieri 6, 37057 S. G. Lupatoto - Verona, Italy or an authorized EDS Service Center. To be honored, claims must be submitted within the 24 month warranty period (according to the product) and within eight (8) days of discovery of the defect.
  • Page 32 The technical information in this document have been carefully checked and can be considered reliable. In any case the EDS Company is not responsable for any eventual inaccuracy and reserves the right to make changes to any part of this document and/or to the products, in order to improve their quality, reliability or design.