Troubleshooting - Mitsubishi Electric PKFY Series Technical & Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for PKFY Series:
Table of Contents

Advertisement

7

TROUBLESHOOTING

7-1. How to check PKFY-P20VAM-A, PKFY-P25VAM-A
Part Name
Room temperature
Disconnect the connector, then measure the resistance using a tester.
thermistor(TH21)
(Surrounding temperature 10°C~30°C)
Liquid pipe temperature
thermistor(TH22)
Normal
Gas pipe temperature
4.3k
thermistor(TH23)
Vane motor
1Measure the resistance between the terminals using a tester.(Surrounding temperature 25:.)
3
Blue
M
1-2
5
Yellow
Red-Pink
Red
1
Orange Pink
Connect pin No.
4
2
Fan motor
1Measure the resistance between the terminals using a tester.(Surrounding temperature 20:.)
White-Black
FAN
Red-Black
1
White
Red
4
Black
6
2Without disassembling the parts, measure the electrical pressure of the gray wire(Signal line) and
brown wire (GND) while the power is on.
Brown
Gray Yellow
3
2
1
CN34
Normal
Abnormal
Linear expansion
Disconnect the connector then measure the resistance valve using a tester.
(Coil temperature 20°C)
valve
CN60
White
1
Yellow
2
(1)-(5)
Orange
3
LEV
White-Red
Blue
4
Red
5
Brown
6
All manuals and user guides at all-guides.com
Abnormal
~9.6k
Open or short
'
'
Normal
1-3
1-4
Red-Blue
Red-Orange
400'
± 7%
Normal
195'
200'
!At first, check if the electrical pressure is 12V between the
brown wire(GND) and yellow wire(VCC).
@Slowly start running the fan. It is normal if while the fan rotate once,
the electrical pressure change from 0V to12V then go back to 0V.
If the electrical pressure stay at around 0V or 10V, it means the fan
motor has the defects.
Normal
(2)-(6)
(3)-(5)
Yellow-Brown
Orange-Red
150'
±10%
Check points
(Refer to the next page for a detail.)
Abnormal
1-5
Red-Yellow
Open or short
Abnormal
Open or short
Abnormal
(4)-(6)
Blue-Brown
Open or short
12