HORIZONTAL LOW-PROFILE FAN COILS
INSTALLATION & MOUNTING INSTRUCTIONS

Concealed Horizontal Fan Coils

Mounting the Unit
1.
Use trapeze hanger or optional factory supplied hanger
brackets as illustrated. Hanging rods should be securely
attached to joists or to mounting anchors which are
properly secured to slab construction with lugs or poured
in place anchors.
2.
Price Fan Coil Units are designed to be mounted in the
direction indicated by the Control Assembly Label found
on the protective shroud.
3.
Do not block the bottom access panel, maintain clearance
for blower service.
4.
Do not install tight to slab, avoid contact with other
obstacles such as rigid conduit and sprinkler piping. This
can cause excessive vibration and noise transmission.
5.
Install the unit in a location that allows free access to the
unit as well as all control components.
6.
Ensure main power to the terminal has been disconnected
prior to performing any electrical work or inspection of the
circuitry.
WARNING:
Do not tamper with control components.
Cooling/Heating Pipe Connections
The valve packages are easily damaged when introduced to
excessive amounts of heat. Great caution must be made when
the connections are made with "sweat" or solder joints. The
valve must be in the open position during all soldering and
brazing operations. Heat should be dissipated with a wet cloth
wrapped around the valve body.
Electrical Connection
CAUTION:
Disconnect all incoming power before any electrical
installation or service is performed on the unit(s).
1.
All field wiring is to be in accordance with the National
Electrical Code ANSI/NFPA No. 70 or the Canadian
Electrical Code, Part 1, CSA Standard C 22.1. Local
codes and the National Electrical Code requirements take
precedence over manufacturer recommendations, and
adherence to these codes shall be the responsibility of the
installing contractor.
2.
Refer to the product identification label on each unit for
information to determine the field wire size.
3.
Check voltage requirements prior to power supply
connection. Refer to the electrical label located on the
electrical control box and also refer to the schematic
drawing provided on the underside of the electrical control
box cover.
4.
If upon energizing the electric motor excessive noise is
apparent, shut down the unit. Determine the cause by
checking for packing materials, etc. and re-energize after
corrective action has been taken.
Auxiliary Drain Pan Mounting
Auxiliary drain pan is mounted inside the attached drain pan.
See Figure A to properly align the mounting holes and install
the screw from the inside out. Once the screws are installed
ensure drain pan is in proper position leaning down against the
attached drain pan. See Figure B for proper positioning.
FIGURE A
FIGURE B
priceindustries.com | HORIZONTAL LOW-PROFILE FAN COILS - Manual
3