Hitachi SH1 Series Basic Manual page 23

Hide thumbs Also See for SH1 Series:
Table of Contents

Advertisement

Chapter 2
• For LD/VLD rating
Model
Applicable
SH1-*****-*
Motor(kW)
(SH1-***H)
SH1-00041-H(SH1-007H)
1.5
SH1-00054-H(SH1-015H)
2.2
SH1-00083-H(SH1-022H)
3.7
SH1-00126-H(SH1-037H)
5.5
SH1-00175-H(SH1-055H)
7.5
SH1-00250-H(SH1-075H)
11
SH1-00310-H(SH1-110H)
15
SH1-00400-H(SH1-150H)
18.5
SH1-00470-H(SH1-185H)
22
SH1-00620-H(SH1-220H)
30
SH1-00770-H(SH1-300H)
37
SH1-00930-H(SH1-370H)
45
SH1-01160-H(SH1-450H)
55
SH1-01470-H(SH1-550H)
75
SH1-01760-H(SH1-750H)
90
SH1-02130-H(SH1-900H)
110
SH1-02520-H(SH1-1100H)
132
SH1-03160-H(SH1-1320H)
160
SH1-03410-H(SH1-1600H)
185
SH1-03950-H(SH1-1850H)
200
SH1-04460-H(SH1-2000H)
220
SH1-04810-H(SH1-2200H)
250
SH1-05500-H(SH1-2500H)
280
SH1-06600-H(SH1-3150H)
315
 Device model name on above table shows example selection. The device
selection should be made in base on rated current, short circuit current
capability and accordance to the local electrical legislation.
 Applicable motor capacity is based on Hitachi 400Vac, 60Hz, 4 pole IE3
motor.
 Refer to the wire gauge table on chapter 2.6 for power line cable.
 Electrical endurance for AC-1 magnetic contactor is 500000 times,
however, for emergency stop in motor operation will be only 25 times.
 Select AC-3 class magnetic contactor for inverter output for application
which has an emergency stop or commercial power line operation.
 When selecting oversize inverter capacity compare to motor rating,
select magnetic contactor according to the inverter capacity
Without reactor(DCL or ACL)
Earth-leakage breaker(ELB)
Magnetic Contactor(MC)
Example
Rated Current
AC-1
model
(A)
EX50C
10
HS8
EX50C
10
HS8
EXK50-C
15
HS8
EXK50-C
20
HS8
EXK50-C
30
HS8
EXK50-C
40
HS20
EXK50-C
50
HS25
EXK100-C
75
HS35
EXK100-C
75
HS50
EXK100-C
100
HS50
RXK125-S
125
H80C
EXK225
150
H80C
EXK225
200
H100C
EX400
250
H150C
EX400
300
H200C
EX400
400
H200C
EX600B
500
H250C
EX600B
600
H400C
2-12
Applicable devices (Input Voltage 400~440V)
Earth-leakage breaker(ELB)
Example
AC-3
model
HS8
EX50C
HS8
EX50C
HS10
EX50C
HS20
EXK50-C
HS25
EXK50-C
HS35
EXK50-C
HS50
EXK50-C
HS50
EXK50-C
H65C
EXK60-C
H80C
EXK100-C
H100C
EXK100-C
H125C
RXK125-S
H125C
EXK225
H200C
EXK225
H250C
EXK225
H300C
EX400
H300C
EX400
H400C
EX400
RX600B
RX600B
RX600B
RX600B
RX600B
RX800B
Installation and Wiring
With reactor(DCL or ACL)
Magnetic Contactor(MC)
Rated Current
AC-1
(A)
5
HS8
10
HS8
10
HS8
15
HS8
20
HS8
30
HS8
40
HS20
50
HS20
60
HS35
75
HS50
100
HS50
125
H65C
150
H80C
200
H100C
225
H125C
300
H150C
350
H200C
400
H250C
500
H400C
500
H600C
500
H600C
600
H600C
600
H600C
700
H800C
AC-3
HS8
HS8
HS8
HS20
HS20
HS25
HS35
HS35
HS50
H65C
H65C
H80C
H100C
H125C
H150C
H250C
H250C
H300C
H600C
H600C
H600C
H600C
H600C
H800C