PACH & COMPANY AeGIS 7000 Series Quick Start Manual page 2

Hide thumbs Also See for AeGIS 7000 Series:

Advertisement

Figure 1
SYSTEM POWER
16-18 GAUGE 2-CONDUCTOR
STRANDED WIRE
12VAC40VA is supplied,
input
voltage must be read 12.5-13.5VAC
with the system ON.
12VDC 3A is not supplied,
input volt-
age must be read 13.5-14.0VDC with
the system ON. Polarity not sensitive.
Do not use the same Power Supply
to power the maglock or strike, doing
so will damage the system and void
the warranty.
TELEPHONE
CAT 5 TWISTED PAIR, MAXIMUM
DISTANCE 200 FEET.
RECOMMENDED 18 GAUGE
2-CONDUCTOR SHIELDED
STRANDED WIRE
if the distance is
longer than 200 feet to eliminate
static and radio frequency
interference (ground one end of the
shield to telephone ground block).
Radio Frequency Filter may be
required if the system is installed
close to Local Radio Station.
MAGLOCK (FAIL SAFE)
16-18 GAUGE 2-CONDUCTOR
STRANDED WIRE FOR EACH
DOOR. DO NOT POWER THE
MAGLOCK USING THE
SYSTEM'S POWER SUPPLY,
DOING SO WILL DAMAGE THE
SYSTEM AND VOID THE
WARRANTY. An isolation relay
with separate power supply is
recommended for maglock
installation to eliminate magnetic
spike.
POSTAL LOCK
POWER SWITCH
Postal lock or Fire Lock
can be obtained from
the local post office or
fire department.
Normally Open
connection is factory
FUSE
standard.
Normally Closed
connection, move the
yellow wire to the switch
marked NC.
LCD ADJUSTMENT
Increase the
Intensity: turn VR3
clockwise.
Decrease the Intensity:
turn VR3
counter clockwise.
SPEAKER/MIC ADJUSTMENT
Increase the
Volume: turn VR2
REMOVE THE BOARD BEFORE REMOVING
counter clockwise.
THE KNOCKOUT TO AVOID DAMAGE TO
Decrease the Volume:
turn VR2
THE BOARD. RECONNECT THE CABLE AS
clockwise.
SHOWN ON THE DIAGRAM.
SYSTEM POWER
14-16 GAUGE SINGLE
CONDUCTOR SOLID WIRE.
Recommended Earth Ground:
• Water Pipe
• Ground Steel Rod.
BATTERY BACKUP
16-18 GAUGE
2-CONDUCTOR
STRANDED WIRE
12VDC 4.5Ahr rechargeable
battery. The system has
built-in charger circuit.
Polarity sensitive.
STRIKE (FAIL SECURE)
16-18 GAUGE 2-CONDUCTOR
STRANDED WIRE FOR EACH
DOOR. DO NOT POWER THE
ELECTRIC STRIKE USING
THE SYSTEM'S POWER
SUPPLY, DOING SO WILL
DAMAGE THE SYSTEM AND
VOID THE WARRANTY
. An
isolation relay with separate
power supply is recommended
for AC Strike installation to
eliminate electric spike.
The switch must be OFF when
you do the wiring. Turn the
system ON by toggling the
switch to the ON position (left)
and the power LED will come
ON.
1.5A 250V fast blow fuse. Do not
bypass the fuse with aluminum
foil or wire, it may cause fire.
MASTER CODE BUTTON
Press and release the Red Button
to retrieve the Master Code. If the
LCD display shows ****, call the
manufacturer at 1-888-678-7224.
REMOVING THE KNOCK-OUT