Download Print this page

Quick Charge MB Multi MB1210X2 Operating Instructions Manual

Bank battery chargers

Advertisement

Quick Links

O P E R A T I N G I N S T R U C T I O N S
MB Multi Bank Battery Chargers
Models:
MB1210X2, MB1210X3, MB1210X4, MB1210X6, MB1210X10, MB1210X12
For Industrial Use:
Designed for gel, wet cell, AGM, and Lithium Ion Batteries
(Lithium ion applications must be factory programmed)
Quick Charge Corp.
800 658-2841
e-mail
quickcharge@icnet.net
www.quickcharge.com
Made in the U.S.A
101712

Advertisement

loading

Summary of Contents for Quick Charge MB Multi MB1210X2

  • Page 1 MB Multi Bank Battery Chargers Models: MB1210X2, MB1210X3, MB1210X4, MB1210X6, MB1210X10, MB1210X12 For Industrial Use: Designed for gel, wet cell, AGM, and Lithium Ion Batteries (Lithium ion applications must be factory programmed) Quick Charge Corp. 800 658-2841 e-mail quickcharge@icnet.net www.quickcharge.com Made in the U.S.A...
  • Page 2: Quick Start Instructions

    QUICK START INSTRUCTIONS: Check that the temporary paper label on the charger marked with the profile setting matches your battery type. If not, see the reprogramming section. If your charger has an ON/OFF switch move it to the OFF position. Connect the red charge leads to battery positive, black’s to negative.
  • Page 3 Look to the Trouble shooting section for any deviations from this. Since these chargers are independent from each other, you can set each circuit differently. For example, you may want to set some circuits to an AGM profile, and others to a wet cell profile, just remember to mark or label how they are set on the outside so as not to get them mixed up, charging a battery with the wrong profile can damage it.
  • Page 4: Other Safety Information

    DO NOT USE THIS CHARGER ON A TWO POLE UNGROUNDED OUTLET OR ATTEMPT TO BREAK OFF THE GROUND PRONG FOR USE ON A RECEPTACLE OR EXTENSION CORD NOT HAVING A GROUND. If an extension cord must be used, make sure it is in good condition.
  • Page 5 The tops of the batteries and battery hold downs must be kept clean and dry at all times to prevent excessive self discharge and flow of current between the battery post and frame. With wet cell batteries, maintain the proper electrolyte level by adding water when necessary.
  • Page 6 REPROGRAMMING: Remove the sheet metal screws holding on the cover, or panel Select the switch configuration that most closely matches your application. Whether choosing maintenance mode, or shut off is a personal preference, however the maintenance mode assures batteries will remain charged and won’t self discharge. IMPORTANT: Use switch numbers as a guide, as some boards may be upside down, and reversed.
  • Page 7: Troubleshooting

    TROUBLESHOOTING Symptom Cause Corrective Action When plugged into AC Connected reverse to Correct polarity, or power the LED flashes battery, or not connected connect to battery. red/green. to battery. Break in DC cord, or Have a qualified person connector. make repair. Battery too dead to Replace.
  • Page 8 When powered up the The battery is very low, Leave connected, it may LED is solid red with a and the charger is in a take hours, but if the yellow flash. slow charge phase until voltage rises even a little the voltage rises to a safe bit, it should recover, level before full turn on.
  • Page 9 Quick Charge corporation shall not in any event be liable for the cost of any special, indirect or consequential damages to anyone, product or thing. This warranty is in lieu of all other warranties expressed or implied.