Installing and connecting the device
3.2 Preparing for installation
3.2.4

Checking clearances

The following clearances are required around the HMI device to ensure sufficient self-
ventilation:
• At least 23 mm to the right and to the left of the mounting cutout (in the x direction) for
mounting the clamping frame during installation
• At least 50 mm above and 50 mm below the mounting cutout (in the y direction) for
ventilation
• At least 10 mm behind the rear panel of the HMI device (in the z direction)
The following figure shows the clearances during mounting of the HMI devices in horizontal
and vertical formats:
x
y
z
Note
Ensure that the maximum ambient temperature is not exceeded when mounting the device
in a cabinet and especially in a closed enclosure.
16
Clearance for installation in landscape format
Clearance for installation in portrait format
Distance from wall at least 23 cm.
At least 50 mm distance
At least 10 mm distance
Compact Operating Instructions, 08/2022, A5E33472156-AP