Wiring; Operation - Profi-pumpe INVERTER PUMP CONTROL 5 Operating Instructions Manual

5-2,2kw/5-5,5kw/5-7,5kw 400v/400v
Table of Contents

Advertisement

Available languages

Available languages

4 English
4.1 WIRING DIAGRAMM:
Wiring Diagram and Instruction
230V single-phase in and 230V single-phase out
TO SENSOR
Psi 24V
U V
24V
4~20mA
400V three-phase in and 400V three-phase out
TO SENSOR
TO PUMP
Psi 24V
U V W
24V
4~20mA
3~380V AC
50/60Hz
M
5-2,2KW 400V/400V (PSM01138VK)
5-5,5KW 400V/400V (PSM01139VK)
5-7,5KW 400V/400V (PSM01140VK)
5. OPERATION - INVERTER (5- 0,5KW / 5-1,5KW / 5-2,2KW / 5-4,0KW / 5-5,5KW / 5-7,5KW)
Make absolutely sure that the device is placed in a location with sufficient cooling to protect
it from overheating.
5.1 Checking before Operation
1. Check the input power and surroundings is comply with the conditions of using.
2. Check whether the pressure sensor is connected with the system .
3. Check whether the product is installed firmly .
4. The pump starts
It is essential to refer to the operating instructions for the pump to find out what
conditions must be met before starting up the pump, after connection is verified. If the pump
is three phase, please check whether the direction of motor revolve is correct. If the motor rotates
inversely, please exchange
TO PUMP
TO POWER
N L1
1~220V AC
1~220V AC
50/60Hz
50/60Hz
M
TO POWER
R S T
3~380V AC
50/60Hz
230V single-phase in and 230V three-phase out
TO SENSOR
TO PUMP
Psi 24V
U V W
24V
4~20mA
3~220V AC
50/60Hz
M
1. Never connect the terminals U,V,W
directly to the power supply
2. Don't connect the AC main circuit power
supply and output terminals U, V, W.
3. Wiring after the power cut off.
4. To verify the inverter rated voltage and the
input supply voltage are consistent
5. The inverter can't be done the dielectric
voltage withstand Test.
6. Terminal screw tightening torque 1.7N.m.
7. Make sure the ground terminal is connected
before wiring the main circuit terminals.
8. Connect the input power after installing the
panel,when the power is connected, don't
remove the panel
TO POWER
N L1
1~220V AC
50/60Hz

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Psm01138vkPsm01139vkPsm01140vk

Table of Contents