Download Print this page

Advertisement

Quick Links

INSTRUCTION MANUAL
E2xS2R & E2xS2F Sounder
For use in Hazardous Locations
1) Product Table
E2xS2FDC024
E2xS2RDC024
E2xS2FDC048
E2xS2RDC048
E2xS2RAC115
E2xS2RAC115
E2xS2FAC230
E2xS2RAC230
The current levels shown above are for the tone resulting in max. current draw (tone 1 - 340Hz Continuous)
Table 1: Electrical Ratings.
Ensure the system power supply is capable of providing the maximum current required for all units. Review associated cable
size, length and quantity of units on each circuit.
2) Warnings
 DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
 DO NOT OPEN WHEN ENERGISED
 POTENTIAL ELECTROSTATIC CHARGING
HAZARD - CLEAN ONLY WITH A DAMP
CLOTH
 HIGH VOLTAGE SHOCK HAZARD. WAIT 5
MINUTES AFTER REMOVING POWER
BEFORE OPENING THE ENCLOSURE
Avertissement:
 NE PAS OUVRIR UN PRESENCE
D'ATMOSPHERE EXPLOSIVE
 NE PAS OUVRIR ENERGIE
 DANGER POTENTIEL CHARGE
ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON HUMIDE
 HAUT TENSION, RISK DE CHOC.
ATTENDEZ 5 MINUTES APRES AVOIR
DEBRANCHE L'ALIMENTATION AVANT
D'OUVRIR LA BOITIER
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. D209-00-011-IS
E2xS2R
Model
Issue 1
E2xS2F
Nom. Voltage
24Vdc
48Vdc
115-120Vac
Nominal +/- 10%
50/60Hz
220-230Vac
Nominal +/- 10%
50/60Hz
3) Rating & Marking Information
3.1. ATEX / IECEx / UKEx certification
The E2xS2 alarm horn complies with the following standards:
EN IEC 60079-0:2018 / IEC60079-0:2017 (Ed 7):
Explosive Atmospheres - Equipment. General Requirements
EN IEC 60079-7:2015 +A1:2018 / IEC 60079-7:2018 (Ed. 5.1):
Explosive Atmospheres - Equipment Protection by Increased
Safety "e"
EN 60079-31:2014 / IEC 60079-31:2013 (Ed 2):
Explosive Atmospheres - Equipment Dust Ignition Protection
by Enclosure "t"
E2XS2 :
20-08-22
Voltage Range
10-30Vdc
38-58Vdc
Standards
Ratings
Ex ec IIC T4 Gc Ta -20°C to +55°C
Ex tc IIIC T85°C Dc Ta -20°C to +55°C
www.e2s.com
Operating
rms Current
280mA
215mA
142mA
76mA
Tel: +44 (0)208 743 8880
Sheet 1 of 5

Advertisement

loading
Need help?

Need help?

Do you have a question about the E2xS2FDC024 and is the answer not in the manual?

Questions and answers

Summary of Contents for E2S E2xS2FDC024

  • Page 1 INSTRUCTION MANUAL E2xS2R & E2xS2F Sounder For use in Hazardous Locations E2xS2R E2xS2F 1) Product Table Operating Model Nom. Voltage Voltage Range rms Current E2xS2FDC024 24Vdc 10-30Vdc 280mA E2xS2RDC024 E2xS2FDC048 48Vdc 38-58Vdc 215mA E2xS2RDC048 E2xS2RAC115 115-120Vac Nominal +/- 10% 142mA...
  • Page 2 E2xS2: 85°C Equipment Category 3G / 3D Equipment Level Protection Gc, Dc European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880 Document No. D209-00-011-IS Issue 1 20-08-22 Sheet 2 of 5...
  • Page 3 18°. On completion of the installation the two large to be customer supplied) Fig. 2 Accessing the Enclosure. European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880 Document No. D209-00-011-IS Issue 1...
  • Page 4: Cable Connections

    2.5mm². 1KΩ 15KΩ 0.5W 48V DC 3.9KΩ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880 Document No. D209-00-011-IS Issue 1 20-08-22 Sheet 4 of 5...
  • Page 5 If opening the unit during maintenance operations a clean environment must be maintained and any dust layer removed prior to opening the unit. European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880 Document No. D209-00-011-IS Issue 1...
  • Page 6 WRITTEN CONSENT. 05/08/2020 IMPRESS HOUSE R.N.POTTS STANDARDS MANSELL ROAD EUROPEAN SAFETY SYSTEMS LTD. ACTON DRAWING NUMBER LONDON W3 7QH SCALE SHEET ALTERNATIVE MATERIAL AS PER LATEST DATE OF ISSUE SHOWN ABOVE Ex N APPROVED DATE D209-06-001 WWW.E2S.COM NTS 1 05/08/2020 R.N.POTTS...
  • Page 7: Eu Declaration Of Conformity

    Other Standards and Regulations EN 60529:1992+A2:2013 - Degrees of protection provided by enclosures (IP code) – enclosure rated IP66/IP67 E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: sales@e2s.com www.e2s.com DC-062_Issue_I (E2x).docx - Page 1 of 2 - QAF_252_Issue_5...
  • Page 8 This Declaration is issued under the sole responsibility of the manufacturer. Martin Streetz Document No.: DC-062_Issue_I Quality Assurance Manager Date and Place of Issue: London, 22/08/2022 E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: sales@e2s.com www.e2s.com DC-062_Issue_I (E2x).docx - Page 2 of 2 - QAF_252_Issue_5...
  • Page 9 Other Standards and Regulations EN 60529:1992+A2:2013 ‐ Degrees of protection provided by enclosures (IP code) – enclosure rated IP66/IP67 E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: sales@e2s.com www.e2s.com DC-103_Issue_A - Page 1 of 2 - QAF_252_Issue_5...
  • Page 10 This Declaration is issued under the sole responsibility of the manufacturer. Martin Streetz Document No.: DC‐103_Issue_A Quality Assurance Manager Date and Place of Issue: London, 22/08/2022 E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: sales@e2s.com www.e2s.com DC-103_Issue_A - Page 2 of 2 - QAF_252_Issue_5...