Section 2. Unit Location Considerations

Table 2.1
Unit Dimensions and Weight
Models
H x D x W (in)
4TTR7024A
4TTR7036A
4TTR7048A
4TTR7060A
* Weight values are estimated.
When mounting the outdoor unit on a roof, be
sure the roof will support the unit's weight.
Properly selected isolation is recommended to
alleviate sound or vibration transmission to the
building structure.
2.2 Refrigerant Piping Limits
1. The maximum TOTAL length of refrigerant
lines from outdoor to indoor unit should
NOT exceed 150 feet* (including lift).
2. The maximum vertical change should not
exceed 50 feet*.
3. Standard and alternate line sizes and
service valve connection sizes are shown in
Table 5.1.
* See Table 5.1 for exceptions for certain
tonnages.
Note: For other line lengths, Refer to Refriger-
ant Piping Application Guide, SS-APG006-EN
or Refrigerant Piping Software Program, 32-
3312-xx (latest revision).
18-AC94D1-4C-EN
Weight* (lb)
41 x 34 x 37
244
45 x 34 x 37
250
45 x 34 x 37
254
45 x 34 x 37
275
W
H
D
Standard
Line Set
150' Max
TOTAL Line Length
3