Advertisement

Quick Links

InMax – Revolution
Electrical, industrial quarter turn actuators size S
On-off, 24...240 VAC/DC, 95° angle of rotation
Fast spring return < 1 sec.
Compact. Easy installation. Universal. Cost effective. Safe.
Type
Torque
Supply
InMax-8-F1
8 Nm
24..240 VAC/DC
InMax-8-SF1
8 Nm
24..240 VAC/DC
InMax-8-BF1
8 Nm
24..240 VAC/DC
InMax-15-F1
15 Nm
24..240 VAC/DC
InMax-15-SF1
15 Nm
24..240 VAC/DC
InMax-15-BF1
15 Nm
24..240 VAC/DC
InMax-...-VAS
Type as above but with stainless steel housing (AISI 316) gearbox parts in stainless steel, cable gland and hollow rivet nickel-plated
InMax-...-CTS
Type as above but with aluminium housing and Amercoat paint, gearbox parts, cable gland and hollow rivet nickel-plated
Application
Air Damper
Ball valve
Description size S
The InMax actuators are a revolution for safety, fire and shut-off
dampers other motorized applications in chemical, pharmaceutical,
industrial and Offshore-/Onshore plants, for use in safe areas.
IP66 protection, small dimensions, only 3,5 kg weight, universal
functions and technical data, an integrated heater and an optional
stainless steel housing guarantee safe operation even under difficult
environmental conditions. High quality brushless motors guarantee
long life.
All actuators are programmable and adjustable on site. Special tools or
equipment are not required. Motor running times selectable or
adjustable on site. The integrated universal power supply is self
adaptable to input voltages in the range of 24 to 240 VAC / DC.
The actuators are 100% overload protected.
InMax-...-F1 actuators are equipped with spring return fail safe function.
Futher the InMax-..-SF1 with integrated aux. switches for end position
indication and the InMax-..-BF1 with an additional circuit to connect an
external passive potential free thermostat Type InPro-TT-... Standard
shaft connection is a double squared direct coupling with 12 × 12 mm.
Different accessories are available to adapt aux. switches, terminal
boxes or adaptations for ball valves and throttle valves.
Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com
Motor running time
Spring return
3/15/30/60/120 sec. at 90°
< 1 sec. at 90°
3/15/30/60/120 sec. at 90°
< 1 sec. at 90°
3/15/30/60/120 sec. at 90°
< 1 sec. at 90°
3/15/30/60/120 sec. at 90°
< 1 sec. at 90°
3/15/30/60/120 sec. at 90°
< 1 sec. at 90°
3/15/30/60/120 sec. at 90°
< 1 sec. at 90°
Throttle valve
Highlights
 Industrial actuators, IP66 protection
 Universal supply unit from 24 to 240 VAC/DC
 Circuit for directly connection of a InPro-TT-.. sensor (option -BF1)
 2 integral aux. switches, switching at 5° and 85° angle of rotation (option -SF1)
 5 different motor running times (3-15-30-60-120 sec./90°), adjustable on site
 Spring return running time < 1 sec./90°
 On-off control with spring return function
 100 % overload protected, selflocking
 Compact design and small dimension (L × W × H = 210 × 95 × 80 mm)
 Direct coupling to the damper shaft with double-squared connection 12 × 12 mm
 95° Angle of rotation incl. 5° pre-tention
 Robust aluminium housing (optional stainless steel or amercoat painting)
 Simple manual override include + preparation for comfortable manual override
 Gear made of stainless steel and sinter metal
 Weight only 3,5 kg
 Integral heater for ambient temperatures down to -40°C
 Integral safety temperature sensor
 Integral equipment for manual adjustment (push button, lamp, switch)
 Preparation for adaptable aux. switches (type InSwitch)
 Range of accessories
www.schischek.com
E X P L O S I O N P R O O F
InMax- 8 - F1
InMax- 8 - SF1
InMax- 8 - BF1
InMax- 15 - F1
InMax- 15 - SF1
InMax- 15 - BF1
InMax- ... - ... - VAS
InMax- ... - ... - CTS
Control mode
Additional features
On-off
On-off
2 contacts (5/85°)
On-off
2 contacts (5/85°) + fire trigger
On-off
On-off
2 contacts (5/85°)
On-off
2 contacts (5/85°) + fire trigger
Original view InMax-..-.F1
Subject to change!
Wiring diagram
SB 1.4 / 1.5
SB 1.4/ 1.5
SB 7.5/7.6
SB 1.4 /1.5
SB 1.4/1.5
SB 7.5/ 7.6

Advertisement

Table of Contents
loading

Summary of Contents for Schischek InMax Revolution

  • Page 1  Integral equipment for manual adjustment (push button, lamp, switch)  Preparation for adaptable aux. switches (type InSwitch)  Range of accessories Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com www.schischek.com...
  • Page 2: E X P L O S I O N P R O O F

    InPro-TT-.. passive temperature sensor AR-12-xx reduction of square damper connection from 12 mm to 11, 10, ... Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com www.schischek.com...
  • Page 3: Electrical Connection

    Angle of rotation must be started and operation mode of max. 10% ED must be guaranteed. (1 cycle per minute) Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com www.schischek.com...
  • Page 4 Extra information "ME-M" (see additional data sheet) extra technical information, dimensions, installation instruction and illustration D.IM-05.02-S-en-F1 04-aug-2011 Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com www.schischek.com...
  • Page 5 Lengthof cable L = 126 m Cross section of A = 1,5 mm² 56m/Wmm²) Example: 24 V power supply with wire diameter 1,5 mm² = 126 m Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com...
  • Page 6 At overload resp. temperature rise the actuator will remain functionless until cooling. during operation briefly before reaching the end / blockade position. During cooing the LED is red. Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com...
  • Page 7 Otherwise the limiters could respond and switch of the actuator irreversibly. Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com...
  • Page 8 "HV-S" manual override. External applied force to the shaft can lead to mechanical damage of the actuator. Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com...
  • Page 9 1. Put the squared connection part to the actuator, then mount InSwitch and fix it with 4 2. InMax with mounted InSwitch screws 4 × Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com...
  • Page 10 (B) 2 × 2 × Terminal box mounted above the actuator Terminal box mounted beside the actuator Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com...