7 - If intake and exhaust piping must be run up a side
wall to position above snow accumulation or other
obstructions, piping must be supported. At least
one bracket must be used within 6" from the top of
the elbow and then every 24" (610mm) as shown
in FIGURE 43, to prevent any movement in any
direction. When exhaust and intake piping must
be run up an outside wall, the exhaust piping must
be terminated with pipe sized per TABLE 16. The
intake piping may be equipped with a 90° elbow
turndown. Using turndown will add 5 feet (1.5m) to
the equivalent length of the pipe.
8 - A multiple furnace installation may use a group
of up to four terminations assembled together
horizontally, as shown in FIGURE 41.
2" EXTENSION FOR 2" PVC
PIPE1" EXTENSION FOR 3"
PVC PIPE
4''
FURNACE
INTAKE
PIPE
FLAT
SIDE
FLUSH-MOUNT SIDE WALL TERMINATION KIT
51W11 (US) or 51W12 (Canada)
FIGURE 38
12" (305mm)
Minimum
Above Average
Snow
Accumulation
CLAMP
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
FIGURE 39
FURNACE
EXHAUST
PIPE
GLUE EXHAUST
END FLUSH INTO
TERMINATION
1-1/2" ACCELERATOR
Accelerator not required for
3" concentric
FLASHING
(Not Furnished)
INTAKE
SHEET METAL STRAP
(Clamp and sheet metal strap
must be field installed to support
the weight of the termination kit.)
FIELD-PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT DIFFERENT VENT
PIPE SIZE TO TERMINATION
FIELD-PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
DIFFERENT VENT PIPE
SIZE TO TERMINATION
EXHAUST
AIR
INTAKE
AIR
DIRECT VENT CONCENTRIC WALL TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
EXHAUST
VENT
INTAKE
AIR
Inches (mm)
optional intake elbow
OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT
INSTALLATION OF DIRECT VENT WALL TERMINATION KIT
DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
Minimum 12" (305MM)
above chimney top
plate or average snow
accumulation
NOTE - Do
tical discharge through an existing unused chimney or stack is required, insert piping
inside
trated. In any exterior portion of chimney, the exhaust vent must be insulated.
Page 35
Accelerator not required
for 3" concentric
OUTSIDE
INTAKE
WALL
AIR
12" (305mm) Min.
INTAKE
CLAMP
AIR
(Not Furnished)
average snow ac
FIGURE 40
(305mm)
5-1/2"
5"
(140mm)
(127mm)
18" MAX.
(457mm)
EXHAUST VENT
12" (305mm) Min.
above grade or
INTAKE
AIR
Side View
(30G28 or 81J20)
FIGURE 41
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
3" - 8"
(76mm-
8" - 12"
203mm)
(203mm - 305mm)
SHOULDER OF FITTINGS
INTAKE PIPE
PROVIDE SUPPORT
INSULATION (optional)
OF PIPE ON TOP PLATE
SHEET
METAL TOP
PLATE
3" - 8"
(76mm-
203mm)
INSULATE
TO FORM
SEAL
FIGURE 42
EXHAUST
AIR
above grade or
cumulation.
GRADE
12"
Front View
cumulation.
OF ROOF SLOPE *
ALTERNATE
INTAKE PIPE
EXTERIOR
PORTION OF
CHIMNEY

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents