Riello FS5 Installation, Use And Maintenance Instructions page 6

Forced draught gas burner
Table of Contents

Advertisement

LINE OF GAS-SUPPLY
1
2
3
1
– Gas supply pipe
2
– Manual cock (charged to the installer)
3
– Gas pressure gauge (charged to the installer)
4
– Filter
5
– Gas pressure switch
6
– Safety valve
GAS TRAIN ACCORDING TO EN 676
MULTIBLOC
MBC 65 DLE
MB DLE 405 B01
The gas train is supplied separately, for its adjustment see the enclosed instructions.
POSITIONING ELECTRODE-PROBE
Put the ceramic
near the diffuser disc
Probe
D5033
IMPORTANT
Do not turn the starting electrode but leave it as shown in the drawing; if the starting electrode is
put near the ionization probe, the amplifier of the control box might be damaged.
20025473
M1
4
5
6
CONNECTION
CODE
GAS TRAIN
3970569
Rp 1/2
3970530
Rp 1/2
Ionization
probe
Diffuser
7
8
M2
7
– Pressure governor
8
– Adjusting valve
M1 – Gas-supply pressure test point
M2 – Pressure coupling test point
BURNER
Rp 1/2
Rp 1/2
Ignition electrode
2
WARNING 2.5 – 3.5 mm
4
MBC 65 DLE
6
8
D5069
EMPLOY
Natural gas and LPG
Natural gas and LPG
Electrode
7
D7279