Cross section area of Wire for Main Power and ON/OFF capacities
9-2-2.
<When power is supplied separately>
Model
PUMY-P250YBM
Outdoor unit
PUMY-P300YBM
<When power is supplied from the outdoor unit>
Model
PUMY-P250YBM
Outdoor unit
PUMY-P300YBM
*1 A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*2 In multi-phase appliances, the colour of the neutral conductor of the supply cord, if any, shall be blue.
<Indoor units> When power is supplied to indoor unit and outdoor unit separately
Total operating current of the indoor unit
F0 = 16 A or less *2
F0 = 25 A or less *2
F0 = 32 A or less *2
Apply to IEC61000-3-3 about max. permissive system impedance.
*1 The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*2 Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2 = {V1 × (Quantity of Type 1)/C} + {V1 × (Quantity of Type 2)/C} + {V1 × (Quantity of Type 3)/C} + ··· + {V1 × (Quantity of Type 16)/C}
Connect to Branch box (PAC-MK·BC)
Indoor unit
Type 1
PEAD-M·JAA(D)
Type 2
SEZ-M·DA(L)2, PCA-M·KA2
Type 3
SLZ-M·FA2, PLA-M·EA2
MSZ-AP·VG(K), MSZ-RW·VG-E1, MFZ-KT·VG, MFZ-KT·VG-E2, MLZ-KY·VG-E1,
Type 4
MSZ-LN·VG2, MSZ-EF·VG(-E2/ER2/ET2), MSZ-EF·VGK(-E1/ER1/ET1)
Type 5
MSZ-FH·VE2
Type 6
Branch box (PAC-MK·BC)
Connect to Connection kit (PAC-LV11M)
Indoor unit
Type 7
MSZ-EF·VG(-E2/ER2/ET2), MSZ-EF·VGK(-E1/ER2/ET1), MSZ-AP·VG(K), MFZ-KT·VG, MSZ-LN·VG2
Type 8
MSZ-FH·VE2
Type 9
Connection kit (PAC-LV11M)
Connect to City Multi
Indoor unit
Type 10
PEFY-P·VMA(L)-E, PEFY-P·VMA(L)-E2, PEFY-P·VMA(L)-E3, PEFY-P·VMX(L)-E(1)
Type 11
PEFY-P40-140VMHS-E, PEFY-P·VMH-E2
PMFY-P·VBM-E, PLFY-P·VFM-E, PEFY-P·VMS1(L)-E, PCFY-P·VKM-E, PKFY-P·VKM-E,
Type 12
PKFY-P·VLM-E, PFFY-P·VKM-E2, PFFY-P·VCM-E
Type 13
PLFY-P·VEM-A, PLFY-M·VEM-E
Type 14
PEFY-M·VMA(2)(L)-A, PEFY-M·VMA(L)-A1
Type 15
PEFY-P200/250VMHS-E, PEFY-P·VMHS-E-F
Type 16
PEFY-P·VMR-E-L/R, PFFY-P·VLEM-E, GUF-RD(H)4
C : Multiple of tripping current at tripping time 0.01s
Please pick up "C" from the tripping characteristic of the breaker.
<Example of "F2" calculation>
* Condition: PEFY-P·VMS1-E × 4 + PEFY-P·VMA-E × 1, C = 8 (refer to right sample chart)
F2 = 19.8 × 4/8 + 38.0 × 1/8
= 14.65
*3 Current sensitivity is calculated using the following formula.
G1 = { V2 × (Quantity of Type 1)} + {V2 × (Quantity of Type 2)} + ··· + {V2 × (Quantity of Type 16)} + { V3 ×
(Wire length [km])}
G1
Current sensitivity
30 or less
30 mA 0.1 sec or less
100 or less
100 mA 0.1 sec or less
Wire thickness
1.5 mm 2
2.5 mm 2
4.0 mm 2
1. Bear in mind ambient conditions (ambient temperature, direct sunlight, rain water, etc.) when proceeding with the wiring and connections.
2. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops.
Make sure the power-supply voltage does not drop more than 10%.
3. Specific wiring reguirements should adhere to the wiring regulations of the region.
4. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 60245 iec57). For example, use
wiring such as YZW.
5. Install an earth longer than other cables.
TCH091
Minimum Wire Cross-sectional area (mm²)
Power supply *2
3N~ 380-400-415 V 50 Hz
3N~ 380-400-415 V 50 Hz
Minimum Wire Cross-sectional area (mm²)
Power supply *2
3N~ 380-400-415 V 50 Hz
3N~ 380-400-415 V 50 Hz
Minimum wire thickness (mm
Main Cable
Branch
1.5
1.5
2.5
2.5
4.0
4.0
V3
48
56
66
Main Cable
Ground
4.0
4.0
6.0
6.0
Main Cable
Ground
6.0
6.0
6.0
6.0
)
2
Ground-fault interrupter *1
Ground
1.5
20 A current sensitivity *3
2.5
30 A current sensitivity *3
4.0
40 A current sensitivity *3
26.9
19.8
17.1
26.8
19.8
17.1
18.6
13.8
113
Breaker for Wiring *1
Breaker for Current Leakage
32 A
32 A 30 mA 0.1 sec. or less
40 A
40 A 30 mA 0.1 sec. or less
Breaker for Wiring *1
Breaker for Current Leakage
40 A
40 A 30 mA 0.1 sec. or less
40 A
40 A 30 mA 0.1 sec. or less
Local switch (A)
Capacity
Fuse
16
16
25
25
32
32
V1
V2
2.4
7.4
6.8
5.1
3
V1
V2
7.4
6.8
2.4
3.5
V1
V2
38
1.6
2.4
3
4.8
0
0
Sample chart
6000
600
60
10
1
0.1
0.01
1
2
3
Rated Tripping current (x)
Breaker for wiring
(NFB)
20
30
40
SAMPLE
4
6
8
10
20
C