Test Run - Fujitsu AGHG12KVCA Installation Manual

Hide thumbs Also See for AGHG12KVCA:
Table of Contents

Advertisement

■ Auto restart
Enable or disable automatic restart after a power interruption.
Function num-
Setting
ber
value
00
40
01
* Auto restart is an emergency function such as for power outage etc. Do not attempt to
use this function in normal operation. Be sure to operate the unit by remote controller or
external device.
■ Room temperature sensor switching
(Only for wired remote controller)
When using the Wired remote controller temperature sensor, change the setting to "Both" (01).
Function num-
Setting
ber
value
00
42
01
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
* Remote controller sensor must be turned on by using the remote controller
■ Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
Function num-
Setting
ber
value
00
01
44
02
03
■ Combination of external input and output
By combining the function setting of the indoor unit, you can select various combinations
of functions.
Combination examples of external input and output are as follows:
Function
Setting
number
value
Operation/Stop mode 1
00
(R. C. enabled)
01
(Setting forbidden)
46
02
Forced stop mode
Operation/Stop mode 2
03
(R. C. disabled)
Function
Setting
number
value
CN20
00
Operation/Stop
09
Error status
60
Indoor unit fan
10
operation status
External heater
11
output
En-12
(♦... Factory setting)
Setting description
Enable
Disable
(♦... Factory setting)
Setting description
Indoor unit
Both
(♦... Factory setting)
Setting description
A
B
C
D
(♦... Factory setting)
Setting description
External input control
CN14
CN15
Forced thermostat Off
(♦... Factory setting)
Setting description
External output control
CN21
CN22
Indoor unit fan
Error status
operation status
Indoor unit fan
Operation/Stop
operation status
Operation/Stop
Error status
Indoor unit fan
Operation/Stop
operation status
■ Setting record
Record any changes to the settings in the following table.
Function
number
11
30
31
35
36
40
42
44
46
60
After completing the function setting, be sure to disconnect the power and reconnect it
again.

6. TEST RUN

Do not turn on the power until all installation work is complete.
When restarting after a long period of disuse in the winter, turn the power switch on at
least 12 hours before starting the unit.
Check items
Is operation of each button on the remote controller normal?
Does each lamp light normally?
Do airfl ow direction louvers operate normally?
Is the drain normal?
Do not have an abnormal noise and vibration during operatio
Do not operate the air conditioner in test run for a long time.
NOTES: • After test run, a buzzer beeps.
• If the indoor unit fan rotates and the ECONOMY lump blinks, refrigerant
leakage may have occurred.
• Open the windows to ventilate the room and contact an authorized service
personnel.
[Operation method]
Depending on your installation, choose from the following:
■ By the wireless remote controller (with [TEST RUN])
(1) To start test run, press [START/STOP] and [TEST RUN] on the remote controller.
(2) To end test run, press [START/STOP] on the remote controller.
■ By the indoor unit or IR receiver unit
(1) To start test run, press [MANUAL AUTO] of the unit for more than 10 seconds (forced
CN23
cooling).
External heater
(2) To end test run, press [MANUAL AUTO] for more than 3 seconds or press [START/
output
STOP] on the remote controller.
External heater
(3) The Operation indicator lamp and Timer indicator lamp will simultaneously flash during
output
the test run mode.
External heater
■ By the wired remote controller
output
(1) For the operation method, refer to the installation manual and the operation manual of
Error status
the wired remote controller.
Heating test run will begin in a few minutes when HEAT is selected by the remote control-
ler [reverse cycle model only].
Function setting
Filter sign
Room temperature control for indoor
unit sensor
Room temperature control for wired
remote controller sensor
Auto restart
Room temperature sensor switching
Remote controller custom code
External input control
External output control
WARNING
CAUTION
Setting value
Cooling
Heating
Cooling
Heating
n?

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aohg12kvca