Accessory Parts; Installation Of R32 Refrigerant Air Conditioner - Toshiba MMY-SUG0801MT8P-E Installation Manual

Hide thumbs Also See for MMY-SUG0801MT8P-E:
Table of Contents

Advertisement

3

Accessory parts

Part name
Q'ty
Owner's Manual
1
Installation Manual
1
Installation data
1
CD-ROM
(Owner's Manual,
1
Installation Manual)
Binding band
12
F-GAS label
1
Piping
1
Insulation-cover
2
45-EN
Shape
Usage
(Be sure to hand over to customers)
(Be sure to hand over to customers)
(Be sure to hand over to customers)
For other languages that do not appear in this
Installation Manual, Please refer to the enclosed
CD-ROM.
2 pcs...long type
10 pcs...short type
Fill the items on the label after adding refrigerant.
Installation for the Heat pump system.
Freeze prevention for Heat Pump System
Long size:1 pc., Short size:1 pc.
– 23 –
4

Installation of R32 refrigerant air conditioner

CAUTION
R32 refrigerant air conditioner installation
• This air conditioner adopts the HFC refrigerant (R32) which does not destroy ozone layer.
Therefore, during installation work, make sure that water, dust, former refrigerant, or refrigerant oil does not enter
the R32 refrigerant air conditioner cycle. To prevent mixing of refrigerant or refrigerant oil, the sizes of connecting
sections of charge port on the main unit and installation tools are different from those of the conventional
refrigerant units.
Accordingly, special tools are required for the R32 or R410A refrigerant units. For connecting pipes, use new and
clean piping materials with high pressure fittings made for the R32 or R410A only, so that water and/or dust does
not enter.
Required Tools/Equipment and Precautions for use
Prepare the tools and equipment listed in the following table before starting the installation work.
Newly prepared tools and equipment must be used exclusively.
Legend
: Conventional tools (R32 or R410A)
: Prepared newly (Use for R32 only)
Tools / equipment
Gauge manifold
Vacuuming / charging refrigerant
and operation check
Charging hose
Charging cylinder
Can not be used
Gas leak detector
Charging refrigerant
Vacuum pump
Vacuum drying
Vacuum pump with backflow
Vacuum drying
prevention function
Flare tool
Flare processing of pipes
Bender
Bending pipes
Refrigerant recovery equipment
Refrigerant recovery
Torque wrench
Tightening flare nuts
Pipe cutter
Cutting pipes
Refrigerant cylinder
Charging refrigerant
Welding machine and nitrogen
Welding pipes
cylinder
Electronic refrigerant charging
Charging refrigerant
scale
Use
How to use tools / equipment
Conventional tools (R32 or R410A)
Conventional tools (R32 or R410A)
Unusable (Use the electronic refrigerant charging
scale)
Prepared newly (Use for R32 only)
Conventional tools (R32 or R410A)
Usable if the backflow prevention adapter is
installed.
Conventional tools (R32 or R410A)
Conventional tools (R32 or R410A)
Conventional tools (R32 or R410A)
Conventional tools (R32 or R410A)
Conventional tools (R32 or R410A)
Conventional tools (R32 or R410A)
Prepared newly (Use for R32 only)
Conventional tools (R32 or R410A)
Conventional tools (R32 or R410A)
46-EN