(Flow Selector unit address)
• As for every single port type FS unit, multi port type FS unit and SV unit, set up CODE No. "FE" within the range
of 1~128.
This CODE No. should cannot be duplicate in one system.
1. Push and hold "
MENU" button and [
2. Select the "DN setting" using the [
] and [
Select the corresponding "Indoor unit" using the "F1(Unit)" button and push the "F2 (Set)" button.
(The fan and louvers of the selected indoor unit will be activated.)
3. Set the Indoor Unit Function Code (I.DN) to [FE] and the data using the [
(The fan of the selected indoor unit is turned on.)
4. When done, press the "
MENU" button.
5. Push the "
Back CANCEL" button and complete the setting for the time being.
1,4
5
How to set up the CODE No. [105]
(Flow Selector unit and Shut-off Valve
unit port address)
• As for multi port type FS unit, set up CODE No. "105" within the range of 1~12.
This CODE No. should not be duplicate in one system.
• As for both single port type FS unit and SV unit, set up CODE No. "105" to 1.
1. Push and hold "
MENU" button and [
2. Select the "DN setting" using the [
] and [
Select the corresponding "Indoor unit" using the "F1 (Unit)" button and push the "F2 (Set)" button.
(The fan and louvers of the selected indoor unit will be activated.)
3. Set the Indoor Unit Function Code (I.DN) to [105] and the data using the [
(The fan of the selected indoor unit is turned on.)
4. When done, press the "
MENU" button.
5. Push the "
Back CANCEL" button and complete the setting for the time being.
109-EN
SV : Shut-off Valve
FS : Flow Selector
] setting button simultaneously for 4 seconds or more.
] button and press the "F2 (Set)" button.
] and [
] button
2
1
2,3,4
SV : Shut-off Valve
FS : Flow Selector
] setting button simultaneously for 4 seconds or more.
] button and press the "F2 (Set)" button.
] and [
] button
– 55 –
How to set up the CODE No. [106]
(Combining branches mode of Flow Selector unit)
• When connecting the indoor units to combining branches of the multi port type FS unit, set up CODE No. "106"
to 1.
• When connecting the indoor units to NOT combining branches of the multi port type FS unit, set up CODE No.
"106" to 0.
1. Push and hold "
MENU" button and [
2. Select the "DN setting" using the [
Select the corresponding "Indoor unit" using the "F1(Unit)" button and push the "F2 (Set)" button.
(The fan and louvers of the selected indoor unit will be activated.)
3. Set the Indoor Unit Function Code (I.DN) to [106] and the data using the [
(The fan of the selected indoor unit is turned on.)
4. When done, press the "
MENU" button.
5. Push the "
Back CANCEL" button and complete the setting for the time being.
How to set up the CODE No. [107]
(Safety measures)
• It is necessary to set up safety measures.
• If the settings and actual connections are different, the system will not be able to operate.
0: No Safety equipment is required
1: Pump-down operation
2: Individual shut-off operation
3: Only refrigerant leak detector
1. Push and hold "
MENU" button and [
2. Select the "DN setting" using the [
Select the corresponding "Indoor unit" using the "F1 (Unit)" button and push the "F2 (Set)" button.
(The fan and louvers of the selected indoor unit will be activated.)
3. Set the Indoor Unit Function Code (I.DN) to [107] and the data using the [
(The fan of the selected indoor unit is turned on.)
4. When done, press the "
MENU" button.
5. Push the "
Back CANCEL" button and complete the setting for the time being.
] setting button simultaneously for 4 seconds or more.
] and [
] button and press the "F2 (Set)" button.
] and [
] setting button simultaneously for 4 seconds or more.
] and [
] button and press the "F2 (Set)" button.
] and [
FS : Flow Selector
] button
] button
110-EN