Specifications - Siemens OpenAir GDE Series Technical Instructions

Electric damper actuator
Hide thumbs Also See for OpenAir GDE Series:
Table of Contents

Advertisement

Technical Instructions
Document No. 155-188P25
Rev. 3, August, 2001

Specifications

Power supply
Equipment rating
Auxiliary features
Function
Mounting
Housing
Ambient conditions
Agency certification
Page 2
Operating voltage (G–Y1 or G-Y2)
Frequency
Power consumption
Rating
Feedback potentiometer(GDE/GLB132.1P)
Dual auxiliary switch contact rating
Voltage
Switch Range
Switch A
Recommended range usage
Factory setting
Switch B
Recommended range usage
Factory setting
Switching hysteresis
Torque
GDE
GLB
Runtime for 90° opening or closing
GDE
GLB
Nominal angle of rotation
Maximum angular rotation
Shaft size: Minimum shaft length 3/4-inch (20 mm)
3/8 to 5/8 inch
8 -16 mm
Enclosure
Material
Gear lubrication
Ambient temperature
operation
storage and transport
Ambient humidity (non-condensing)
OpenAir ™ Non-Spring Return Rotary Electric Damper Actuator
24 Vac +20%, -15%
50/60 Hz
2.3 VA
Class 2 according to UL, CSA
Class III per EN60730
0 to 1000 Ω
<10 mA
4A resistive, 2A inductive
24 Vac/24 Vdc
0 to 90° with 5° intervals
0 to 45 °
0 to 90° with 5° intervals
45 to 90°
85°
44 lb-in (5 Nm)
88 lb-in (10 Nm)
90 sec. at 60 Hz (108 sec. at 50 Hz)
125 sec. at 60 Hz (150 sec. at 50 Hz)
90°
95°
1/4 to 1/2 inch
6 - 12.7 mm
Figure 1. Acceptable Shaft Sizes.
NEMA Type 2
IP54 according to EN60529
Durable plastic
Silicone free
-22 to 130°F (-30 to 55°C)
-22 to 140°F (-30 to 60°C)
95% R.H.
UL listed to UL873
C-UL certified to Canadian Standard
C22.2 No. 24-93
24 Vac 3-position Control
9/16 inch
15 mm
Siemens Building Technologies, Inc.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Openair glb series

Table of Contents