Download Print this page

Honeywell NOTIFIER FW-MM Installation And Maintenance Instructions page 2

Wireless monitor module

Advertisement

FIGURE 3. BATTERY COMPARTMENT
BATTERY
COMPARTMENT
MOUNTING
The FW-MM(A) mounts directly to an SMB500(-WH) electrical box. (See
Figure 4.) To avoid interference with the wireless network metal elec-
trical boxes are NOT recommended. Non-metal surface mounted elec-
trical boxes (SMB500/SMB500-WH) are available from Notifier. If not
using an SMB500(-WH), the minimum mounting opening dimensions for the
FW-MM(A) are 4 in. X 3¾ in. x 1½ in. deep.
NOTE: Do not attach the module to temporary structures such that the place-
ment could be altered.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and reg-
ulations. This module is intended for power limited wiring only. FW-MM(A)
must be within 3 feet of monitored device when using field wiring or 20 feet
in non-metallic conduit. In Canada, wiring methods shall be in accordance
with CSA C22.1 Safety Standard for Electrical Installations, Canadian Electri-
cal Code, Part 1, Section 32.
1.
Install module wiring in accor-
dance with the job drawings
and appropriate wiring dia-
grams.
2.
Set the address on the module
per job drawings.
3.
Secure module to electrical
box (supplied by installer), as
shown in Figure 3.
Use of these products in combination with non-Honeywell products in a wireless mesh
network, or to access, monitor or control devices in a wireless mesh nework via the inter-
net or another external wide area network, may require a separate license from Sipco, LLC.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
WARNING: Do not make changes to the equipment. Changes or modifications not expressly approved by the manufacturer could void the user's authority to operate the equipment.
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any
interference, including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes: (1) l'appareil ne doit pas produire de
brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.
This device utilizes the Honeywell915 rev A radio module and complies with IFETEL standard(s). IFT: RCPHOSW14-1983
Notifier
®
and SWIFT ® are registered trademarks of Honeywell International, Inc.
BATTERY
COMPARTMENT
DOOR
FIGURE 5. TYPICAL MONITORING CONFIGURATION
ONLY ONE UL/ULC LISTED CONTACT
CLOSURE MAY BE USED
3.9K EOL
RESISTOR
A2143-10
INSTALL CONTACT CLOSURE DEVICES PER MANUFACTURER'S
INSTALLATION INSTRUCTIONS. WIRELESS MONITOR MODULE MUST BE
WITHIN 3 FEET (1M) OF MONITORED DEVICE WHEN USING FIELD WIRING
INSTITUTO FEDERAL DE TELECOMUNICACIONES
FIGURE 4. MODULE MOUNTING
C2002-00
POWER LIMITED
3.1 VDC MAX
OR 20 FEET (6.1M) IN NON-METALLIC CONDUIT.
LICENSING STATEMENT
For more information, contact Sipco, LLC or Ipco, LLC at 8215 Roswell Rd., Building 900,
Suite 950, Atlanta, GA 30350, or at www.sipocollc.com or www.intusiq.com.
FCC STATEMENT
IC STATEMENT
RAPPORT D'IC
2
C1096-00
WIRELESS
MONITOR MODULE
©2021 Notifier. 7/27/2021
C1097-00
C1099GC-00
I56-4067-005

Advertisement

loading

This manual is also suitable for: