senva EM-PULSE Installation Instructions Manual

senva EM-PULSE Installation Instructions Manual

Pulse energy meter and current/voltage transducers

Advertisement

INSTALLATION INSTRUCTIONS
Pulse Energy Meter
EM-PULSE and Current/Voltage Transducers
The EM-PULSE is a three channel meter, capable of monitoring
single-phase, two-phase and three-phase systems, as well
as 3 independent single-phase systems with one meter. The
EM-PULSE meter offers 2 pulse outputs and 2 pulse inputs
to maintain flexibility during installation and operation. The
EM-PULSE is compatible with all sizes of current/voltage
transducers (CVTs). With the meter's Quickset feature the pulse
scale is set according to the CVT amperage, removing the need
for manual configuration.
Each CVT is independently calibrated to measure and digitally
communicate power values with the meter. The CVT's flexible
rogowski coil makes installations less burdensome. To maintain
high accuracy and flexibility for multiple channel installs, high
voltage connections are made directly into each CVT. Each
CVT is rated for installations ranging from 90 to 600V.
Additional features include customizable pulse scales, pulse
timing and alarm options, various energy output types,
balanced load multipliers, and the PowerPrint power quality
alarm.
LET'S GET STARTED!
Product Descriptions (page 2)
EM-PULSE product diagram
Current/Voltage Transducer (CVT) diagram
Mounting (page 2)
Versatile mounting options for EM-PULSE
Recommended mounting for maximum CVT accuracy
Wiring (page 3)
Typical single-phase and three-phase systems
Output wiring options
Input wiring options
Normal Operation (page 4)
LED indicators for Normal, Warning, and Error conditions
Diagnostics (page 4)
Diagnostic Mode and Diagnostic Codes
Default Settings (page 5)
Function Group Options (pages 5-6)
Pulse Scale
Pulse/Alarm Options
Energy Output Types
Balanced Load Multiplier
PowerPrint Power Quality Alarm
View and Edit Settings (pages 7-8)
View Settings Mode
Edit Settings Mode
Specifications (page 9)
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Failure to follow these instrutions may cause serious injury or death
The high voltage CVTs of this product must be mounted inside a suitable
fire and electrical enclosure. Follow safe electrical work practices. See
NFPA 70E in the USA, or applicable local codes.
This equipment must only be installed and serviced by qualified electrical
personnel having the skills and knowledge related to the construction
and operation of this electrical equipment and installation, and has
received safety training to recognize and avoid the hazards involved. NEC
Article 100.
Do not use this product for life or safety applications.
Do not install this product in hazardous or classified locations.
Read, understand and follow the instructions before installing this
product.
Turn off all power supplying equipment before working on or inside the
equipment.
Product may use multiple voltage/power sources. Disconnect ALL sources
before servicing.
Use a properly rated voltage sensing device to confirm that power is off.
DO NOT depend on this product for voltage indication.
Products rated only for basic insulation must be installed on insulated
conductors.
Replace all doors, covers and protective devices before powering the
equipment.
The installer is responsible for conformance to all applicable codes.
!
Failure to follow these instructions may cause injury, death or
equipment damage.
The EM-PULSE and CVT sensors are designed to be used as a system. DO
NOT connect anything other than a Senva CVT
on the meter base.
If product is used in a manner not specified by the manufacturer, the
protection provided by the product may be impaired. No responsibility is
assumed by the manufacturer for any consequences arising out of the use
of this material.
Higher Reliability, Faster Installation, Superior Accuracy | Sense the difference |
NEED HELP? Call 1-866-660-8864
DANGER
DANGER
WARNING
sensor to the RJ-11 jacks
TM
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EM-PULSE and is the answer not in the manual?

Questions and answers

Summary of Contents for senva EM-PULSE

  • Page 1 ▪ Pulse Scale ▪ Pulse/Alarm Options • The EM-PULSE and CVT sensors are designed to be used as a system. DO ▪ Energy Output Types NOT connect anything other than a Senva CVT sensor to the RJ-11 jacks on the meter base.
  • Page 2 The EM-PULSE supports the use magnets, mounting tabs, horizontal DIN rail and vertical DIN of all Senva CVT sensors. The EM-PULSE meter base is a class rail; for installation flexibility. II low voltage device for mounting flexibility. See Section 9 - Specifications for recommended conductor gage and terminal tightening torque.
  • Page 3 Pulse Comm Digital GND Pulse Out Neg. energy Unsigned PULSE INPUT WIRING The EM-PULSE is capable of accepting pulse inputs from other devices and meters. It will aggregate the pulses and report them. LOAD Power Ground Additional Meter Pulse Inputs...
  • Page 4: Normal Operation

    Diagnostic Mode Navigation If any LEDs display yellow or red in Normal Operation, enter When power is applied to the EM-PULSE meter, the device Diagnostic Mode to view underlying conditions. will begin Normal Operation. The meter will always return to...
  • Page 5: Default Settings

    Function Group 1. Pulse Scale 5. Powerprint Options Off/Disabled There are 8 Pulse Scale options on the EM-PULSE meter: Quickset operation based on CVT rated amperage, user Function Group 1. Pulse Scale selectable pulse scales, or Automeasure based on current energy.
  • Page 6 PowerPrint enabled for all channels with a PowerPrint on Channel S properly installed CVT. There are 3 Energy Output Type settings in the EM-PULSE PowerPrint on Channels RT meter: Real ‘True’ Power, Reactive Power, and Apparent Power. PowerPrint should not be saved if any channels...
  • Page 7 From Normal Operation, press and hold Setup Button  until Line LED  rapidly blinks green (approximately 5 second Each EM-PULSE meter features a View Settings Mode that will hold). Release and meter is in View Settings Mode. display the current settings and an Edit Settings Mode that will...
  • Page 8 Settings section to assist in working through Steps 1-6 to The current setting will be displayed on the CVT LEDs  in navigate the Edit Settings Mode in the EM-PULSE meter. yellow (representing Edit Mode). Momentarily press Ensure you can navigate the View Settings Mode before Setup Button ...
  • Page 9: Specifications