Page 1
Multi Variable Air Conditioners Wall Mounted Type Indoor Unit Owner's Manual Air Conditioners Models: AWMI-22VRDC1A AWMI-28VRDC1A AWMI-36VRDC1A AWMI-45VRDC1A AWMI-56VRDC1A AWMI-71VRDC1A AWMI-22VRDC1B AWMI-28VRDC1B AWMI-36VRDC1B AWMI-45VRDC1B AWMI-56VRDC1B AWMI-71VRDC1B Thank you for choosing Air Conditioners, please read this owner’s manual carefully before...
Page 2
Preface For correct installation and operation, please read all instructions carefully. Before reading the instructions, please be aware of the following items: (1) For the safe operation of this unit, please read and follow the instructions carefully. (2) During operation, total capacity of indoor units should not exceed the total capacity of outdoor units.
Contents Safety Precautions ................................ 1 2 Product Introduction ................................3 ..................3 2.1 Outline of the Unit and Main Parts ....................3 2.2 Rated Operating Condition 3 Installation Instruction ..............................3 ................3 3.1 Schematic diagram of installation spaces ................. 4 3.2 Requirements for Communication Line ......................
Multi Variable Air Conditioners Wall Mounted Type Indoor Unit 1 Safety Precautions means items that must be forbidden! Otherwise, it may lead to personal injury or death or serious damage. means items that must be followed! Otherwise, it may lead to personal injury or property loss.
Page 5
Any personal injury or property loss caused by improper installation, improper debug, unnecessary repair or not following the instructions of this manual should not be the responsibility of ALPICAIR Electric Appliances, Inc. of Zhuhai.
Multi Variable Air Conditioners Wall Mounted Type Indoor Unit 2 Product Introduction 2.1 Outline of the Unit and Main Parts Note: The appearances will be different by the different models of air conditioners. Part Name Part Name Surface panel Guide louver ①...
② Please contact the local ALPICAIR appointed service center before installation. Any malfunctioncaused by the unit that is not installed by the ALPICAIR appointed service center would probably not be dealt with on time because of the inconvenience of the business contact.
Multi Variable Air Conditioners Wall Mounted Type Indoor Unit Total Length L (m) of Communication Cable Wire size Material Material Type Remarks between Indoor Unit and ((mm Standard Indoor (Outdoor) Unit 1) If the wire diameter is enlarged to 2 ×...
Page 9
Multi Variable Air Conditioners Wall Mounted Type Indoor Unit Air Switch Minimum Minimum Model Power Cord Size apacity Sectional Area Sectional Area of of Ground Wire Power Cord(mm AWMI-22VRDC1(A/B) 208~230V ~ 60Hz 208~230V ~ 60Hz AWMI-28VRDC1(A/B) AWMI-36VRDC1(A/B) 208~230V ~ 60Hz AWMI-45VRDC1(A/B) 208~230V ~ 60Hz AWMI-50VRDC1(A/B)
Multi Variable Air Conditioners Wall Mounted Type Indoor Unit 4 Installation Instructions 4.1 Installation of Indoor Unit Below are dimensions of W, H, D for different models: Unit: mm Item Model AWMI-22VRDC1(A/B) AWMI-28VRDC1(A/B) AWMI-36VRDC1(A/B) AWMI-45VRDC1(A/B) AWMI-50VRDC1(A/B) AWMI-56VRDC1(A/B) 1008 AWMI-63VRDC1(A/B) AWMI-71VRDC1(A/B)
Multi Variable Air Conditioners Wall Mounted Type Indoor Unit 4.2 The installation of the rear panel Fig 4.2 (1) Find the horizontal position by the seton method; since the drainage pipe is on the left side, it is necessary to adjust the rear panel to make its left side a little bit lower. (2) Fix the rear panel on the wall by bolts.
Multi Variable Air Conditioners Wall Mounted Type Indoor Unit 4.4 Preparation of the piping hole (1) Make the piping hole (Φ 65mm) in the wall at a slight downward slant to the outdoor side. The center of the hole should be determined referring to Fig.4.2. (2) Insert the piping-hole sleeve into the hole to prevent the connected piping and wiring from being damaged when passing through the hole.
Multi Variable Air Conditioners Wall Mounted Type Indoor Unit 5.1 Connect Cables and Terminals of Wiring Board Connection of Wire and Patch Board Terminal (1) The connection of wire (as shown in fig 5.1.1) ① Strip about 25mm insulation of the wire end by stripping and cutting tool. ②...
Multi Variable Air Conditioners Wall Mounted Type Indoor Unit (4) Fix the power card with wiring clamp. 5.3 Connection of Communication Line of IDU and ODU (1) Open the cover of electric box of indoor unit. (2) Lead the communication line across the rubber ring. (3) Connect the communication line to terminal D1 and D2 on the 4-digit wiring board of indoor unit, as shown in Fig.5.3.1.
Multi Variable Air Conditioners Wall Mounted Type Indoor Unit 5.6 Installation of the indoor unit (1) When routing the piping and wiring from the left or right side of the indoor unit, it is necessary to cut off the tailings of the pipe left on the holder of the unit.
Multi Variable Air Conditioners Wall Mounted Type Indoor Unit temperature too low, for it is bad for health. (5) Do not pour water to unit or clean it by water, otherwise a malfunction or electric shock may happen. (6) Do not mangle the power cord and the communication cord. The damaged power cord and communication cord can only be replaced by the specified ones.
Multi Variable Air Conditioners Wall Mounted Type Indoor Unit ( lower than 45°C) with neutral detergent can be used, then dry it in the shade. Note: ① Do not clean the filter by hot water higher than 45°C for preventing fade or deformation. ②...
Multi Variable Air Conditioners Wall Mounted Type Indoor Unit 9 Malfunction Analyzing Warning: Do not repair the air conditioner by yourself for the incorrect repair would lead to electric shockor fire. Please contact the service center and have the unit repaired by the specialized personnel.
Multi Variable Air Conditioners Wall Mounted Type Indoor Unit 9.2 After-sales service When quality or other problems arise upon the purchased air conditioner, please contact the local service center. 10 Adjusting Method Of The Air Direction 10.1 Adjusting air direction up and down (1) Controlling the guide louver motor by the wireless remote controller can make the guide louver swing up and down, or makes the guide louver stop at a certain angle to have air supplied.