SPACING
Wireless technologies can exhibit communication disruption if devices are
spaced too close together. To avoid this form of disruption, SWIFT® devices
should not be placed closer than 2 feet (60 cm) apart without an intervening
structure. For specific information regarding pull station placement refer to
NFPA 72, ADAAG, and ADA (in Canada, CAN/ULC S524, S528, and Canadian
accessibility laws).
MOUNTING
To mount the wireless pull station, attach the wireless pull station mounting
plate to a permanent structure. The mounting plate can be surface mounted.
To avoid interference with the wireless network metal electrical boxes are NOT
recommended. Do not detach the door of the pull station during installation.
The door of the pull station cannot be reattached to the main housing after the
pull station has been installed. Place the pull station onto the mounting plate
and secure by tightening all three (3) mounting screws inside the door of the
product housing using a #1 Phillips head screwdriver. (See Figure 3.)
NOTE: Do not attach the pull station to temporary structures such that the
placement could be altered.
FIGURE 3. DEVICE MOUNTING
Use of these products in combination with non-Honeywell products in a wireless mesh network, or to access, monitor or control devices in a wireless mesh nework via the internet
or another external wide area network, may require a separate license from Sipco, LLC. For more information, contact Sipco, LLC or Ipco, LLC at 8215 Roswell Rd., Building 900,
Suite 950, Atlanta, GA 30350, or at www.sipocollc.com or www.intusiq.com.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
WARNING: Do not make changes to the equipment. Changes or modifications not expressly approved by the manufacturer could void the user's authority to operate the equipment.
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2)
this device must accept any interference, including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes: (1)
l'appareil ne doit pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre
le fonctionnement.
This device utilizes the Honeywell915 rev A radio module and complies with IFETEL standard(s). IFT: RCPHOSW14-1983
Notifier
®
and SWIFT ® are registered trademarks of Honeywell International, Inc.
Mounting
Screws
Mounting
Plate
C2020-00
LICENSING STATEMENT
FCC STATEMENT
IC STATEMENT
RAPPORT D'IC
INSTITUTO FEDERAL DE TELECOMUNICACIONES
2
OPERATION
To activate the dual-action pull station:
Push in and pull down on the handle. The word 'ACTIVATED' appears after
the handle is pulled down. This will remain until the pull sta tion is reset.
To reset the pull station:
1. Insert the key into the lock and rotate ¼ turn counterclockwise.
2. Open the door until the handle returns to normal.
3. Close and lock the door.
NOTE: Closing the door automatically resets the switch to the 'Normal' posi-