Page 1
X3 PACKAGE DCI R32 DUCTED TYPE INDOOR UNITS Installation Manual OUTDOOR UNITS INDOOR UNITS AEG ECO PLUS 35PIH ADG ECO PLUS 35PH AEG ECO PLUS 50PIH ADG ECO PLUS 50PH AEG ECO PLUS 70PIH ADG ECO PLUS 71PH AEG ECO PLUS 85PIH...
Page 2
To Users Thank you for selecting Argoclima product. Please read this instruction manual carefully before installing and using the product, so as to master and correctly use the product. In order to guide you to correctly install and use our product and achieve expected operating effect, we hereby instruct as below: (1) This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or...
Page 3
Exception Clauses Manufacturer will bear no responsibilities when personal injury or property loss is caused by the following reasons: (1) Damage the product due to improper use or misuse of the product. (2) Alter, change, maintain or use the product with other equipment without abiding by the instruction manual of manufacturer.
Duct Type Unit 1 Safety Notice (Please be sure to abide them) SPECIAL WARNING: (1) Be sure to comply with national gas regulations. (2) Do not pierce or burn. (3) Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
Page 6
Duct Type Unit Please read this operating manual carefully before operating the unit. The air conditioner is charged with inflammable refrigerant R32 (GWP: 675). Before using the air conditioner, please read the instruction manual. Before installing the air conditioner, please read the instruction manual. Before repairing the air conditioner, please read the instruction manual.
Page 7
Duct Type Unit WARNING! (6) Air conditioner should be stored with protective measures against mechanical damage caused by accident. (7) If the installation space for air conditioner pipe is too small, adopt a protective measure to prevent the pipe from physical damage. (8) During installation, use the specialized accessories and components, otherwise water leakage, electric shock or fire hazard may occur.
Page 8
Duct Type Unit WARNING! (24) Do not make the air conditioner wet or electric shock may be lead, ensure that the air conditioner will not be cleaned by water rinsing under any circumstance. (25) When you do not connect the duct, you need to provide an extra protective net to avoid touching the basic insulation.
Duct Type Unit 2 Installation 2.1 Installation Preparation 2.1.1 Notice on Installation (1) Notice on Refrigerant Concentration before Installation. This air conditioner uses R32 refrigerant. The construction area for installation, operation and storage of the air conditioner must be larger than the minimum construction area.
Page 10
Duct Type Unit Ceiling type Wall mounted type Floor standing type Weight Weight Weight Area (m²) Area (m²) Area (m²) (kg) (kg) (kg) 6.54 9.76 87.9 7.38 11.0 99.2 8.27 12.4 9.22 13.8 10.2 15.3 11.3 16.8 12.4 18.5 13.5 20.2 14.7 22.0...
Page 11
Duct Type Unit (3) Please use the charging machine specialized for R32 refrigerant before charging, keep the refrigerant tank in an upright position. After charging, stick a label on the air conditioner saying no excessive charging. (4) The following tools will be used: 1) Liquid-level gauge; 2) Screwdriver; 3) Electric driven rotary hammer;...
Page 12
Duct Type Unit (8) Indoor unit, power cord, connecting wires and communication cords should be at least 1m from television and radio. This is to prevent image interference or noise (Even at a distance of 1m, a very strong electric wave may still generate noise).
Page 13
Duct Type Unit 2.1.3 Unit Dimension WARNING! (1) Install the indoor unit in a location which can withstand a load of at least five times the weight of the main unit and which will not amplify sound or vibration. (2) If the installation location is not strong enough, the indoor unit may fall and cause injuries.
Page 14
Duct Type Unit Unit: mm Dimensions Model ADG ECO PLUS 35PH ADG ECO PLUS 50 PH 1060 1000 ADG ECO PLUS 71 PH ADG ECO PLUS 85PH ADG ECO PLUS 100PH 1381 1340 ADG ECO PLUS 140 PH 1400 1440 1400 ADG ECO PLUS 160 PH 1440...
Page 15
Duct Type Unit (2) Outdoor Unit AEG ECO PLUS 35PIH, AEG ECO PLUS 50PIH, AEG ECO PLUS 71PIH, AEG ECO PLUS 85PIH, AEG ECO PLUS 100PIH, AEG ECO PLUS 100PIH3, AEG ECO PLUS 140PIH, AEG ECO PLUS 140PIH3, AEG ECO PLUS 160PIH3...
Page 16
Duct Type Unit 2.1.4 Diagram of Unit Installation Space and Location (1) Diagram of installation space and location for outdoor unit (Notice: for best performance of the outdoor unit, make sure its installation space conforms to the following installation dimensions). 1) When one outdoor unit is to be installed.
Page 17
Duct Type Unit 2) When two or more outdoor units are to be installed side by side. Unit: mm (mm) A,B,C — ≥300 ≥300 ≥1000 — — A,B,C,E — ≥300 ≥300 ≥1000 — ≥1000 — — — — ≥2000 — —...
Page 18
Duct Type Unit 3) When outdoor units are installed in rows. Unit: mm (mm) ≤1/2H b≥250 1/2H<H ≤H b≥300 >H Prohibited...
Duct Type Unit 4) When outdoor units are installed one above another. Unit: mm (2) Diagram of installation location and space for indoor unit (Notice: for the best performance of indoor unit, make sure its installation space conforms to the following installation dimensions). Unit: mm 2.2 Unit Installation 2.2.1 Indoor Unit Installation...
Page 20
Duct Type Unit (1) Install the bolts to the ceiling at a place strong enough to hang the unit. Mark the bolt positions from the installation template. With a concrete drill for 12.7mm diameter holes. See the following figure. Unit:mm (2) Insert the anchor bolts into the drilled holes, and drive the pins completely into the anchor bolts with a hammer.
Page 21
Duct Type Unit (4) Pass the unit hangers over the bolts installed to the ceiling and install the unit with the special nut. See the following figure. Unit:mm 2.2.1.2 Leveling After installing the indoor unit, level detection of the unit shall be conducted. Place the unit horizontally and leave the left and right side with a downward slope of 1/100~1/50 in drainage direction, as shown below.
Page 22
Duct Type Unit outdoor unit should be at least 10cm from the installation ground). See the following figures. (5) Plugs and drainage connector are not recommended if there is an electrical heater on the chassis. 2.2.3 Connection Pipe Installation 2.2.3.1 Installation Notice and Requirement on Connection Pipe Installation of Ordinary Nut and Tamperproof box Unfold the connecting pipe and bend the connecting pipe according to the required length.
Page 23
Duct Type Unit NOTES! The air conditioner must be installed in a room that is larger than the minimum room area. And it is not allowed to use in a room that has running fire. Before break the connection pipes between indoor and outdoor units, eliminate the refrigerant first and make sure there is no fire source or potential fire source in the maintenance area.
Page 24
Duct Type Unit When the drop between indoor and outdoor units is larger than 10m, an oil return bend should be added every 6m. The requirement on the adding of oil return bend is as below: (1) Outdoor unit is beneath the indoor unit. There’s no need to add non-return bend at the lowest or highest position of the vertical pipe, as shown below: (2) Outdoor unit is above the indoor unit.
Page 25
Duct Type Unit Dimensions for the making of oil return bend are as follows: A(inch) B(mm) C(mm) Ф3/8 ≥20 ≤150 Ф1/2 ≥26 ≤150 Ф5/8 ≥33 ≤150 2.2.3.2 Pipe Flaring (1) Cut the connection pipe with a pipe cutter. (2) The mouth of connection pipe should face downward. Remove burrs with the cut surface so that the chips do not enter the pipe.
Page 26
Duct Type Unit (2) Do not bend the pipes in an angle more than 90°. (3) If the pipe is repeatedly bent or extended, it will become hard and difficult to be bent or extended. So do not bend or extend the pipe for more than 3 times.
Page 27
Duct Type Unit Pipe diameter (inch) Tightening torque (N·m) Ф1/4 15-30 Ф3/8 35-40 Ф1/2 45-50 Ф5/8 60-65 Ф3/4 70-75 Ф7/8 80-85 Screw on the flare nut of the flaring connecting pipe on the outdoor unit valve. The method of screwing the flare nut is the same with that for indoor unit.
Page 28
Duct Type Unit 2.2.3.5 Thermal Insulation of Pipe Joint (Only for indoor unit) Stick coupler heat insulation (large and small) to the place where connecting pipes. 2.2.4 Connection Pipe Vacuum Pumping and Leak Detection 2.2.4.1 Vacuum Pumping NOTE! Make sure the outlet of vacuum pump is away from fire source and is well-ventilated.
Page 29
Duct Type Unit Model Time(min) ADG ECO PLUS 35PH ADG ECO PLUS 50PH ADG ECO PLUS 71PH ADG ECO PLUS 85PH ADG ECO PLUS 100PH ADG ECO PLUS 140PH ADG ECO PLUS 160PH And verify if the pressure gauge at the low pressure side of the manifold valve assembly reads -0.1MPa (-750mmHg), if not, it indicates there is leak somewhere.
Page 30
Duct Type Unit NOTE: For large-size units, there are maintenance ports for liquid valve and gas valve. During evacuation, you may connect the two hoses of the branch valve assembly to the maintenance ports to speed up the evacuation. 2.2.4.2 Leak Detection Methods The following leak detection methods are deemed acceptable for systems containing flammable refrigerants.
Page 31
Additional Item Standard Charge Pipe Refrigerant Amount Model Pipe Length Length for Extra Pipe AEG ECO PLUS 35PIH 16 g/m AEG ECO PLUS 50PIH AEG ECO PLUS 71PIH AEG ECO PLUS 85PIH 5.0m ≤7.0m AEG ECO PLUS 100PIH 20 g/m...
Page 32
Duct Type Unit (3) When the hose is long, install supporters. See the following figure. Unit: mm (4) Always use the drain hose which has been insulated properly. (5) Use a suitable drain hose. (6) There is a drain port on both the left and right sides. Select the drain port to match the local conditions.
Page 33
Duct Type Unit (10) The unused drain port also should be insulated properly. See the following figure. (11) There is adhesive on one side of the insulation so that after removing the protective paper over it the insulation can be directly attached to the drain hose.
Page 34
Duct Type Unit (2) If the outdoor unit is above the indoor unit, arrange the pipeline according to the following diagram. 1) Wind the insulating tape from bottom to top. 2) The whole pipeline should be wound together to avoid water returning to the room.
Page 35
Duct Type Unit (2) For the unit with the condensate pump, two drain ports at the bottom are defaulted to be factory plugged with drain caps. After the installation of the drain hose, these two drain ports also need to be insulated properly with the same way aforementioned.
Page 36
Duct Type Unit NOTE: The specification of the selected merged drainage pipe shall be appropriate for the operation capacity of the unit. (4) Drain branch should be connected to the vertical or horizontal part of the main drain pipe. (5) Horizontal pipe should not be connected to the vertical pipe that is on the same level.
Page 37
Duct Type Unit 2.2.7 Installation of the Duct 2.2.7.1 Dimensions of the Supply Air Outlet/Return Air Inlet Supply Air Outlet Return Air Inlet Unit: mm Supply Air Outlet Return Air Inlet Item Model ADG ECO PLUS 35PH ADG ECO PLUS 50PH 1000 ADG ECO PLUS 71PH ADG ECO PLUS 85PH...
Page 38
Duct Type Unit (2) If the downward return air method is adopted, then install the return air cover at the back of the unit after dismantling it. (3) Connect the return duct to the return air inlet of indoor unit with rivet, and the other side shall be connected to the return air inlet.
Page 39
Duct Type Unit (2) Install the round flange so that it can be connected to the fresh air duct, as is shown in the following figure. (3) The air duct and round flange duct shall be concealed and kept warm well.
Duct Type Unit 2.3 Electrical Installation 2.3.1 Requirement and Notice on Electrical Installation WARNING The electrical installation for the air conditioner should observe the following requirements: The electrical installation must be conducted by professionals in compliance ①. with local laws and regulations and the instructions in this manual. Never extend the power cord.
Page 41
Power supply breaker area of power Model capacity cord V/Ph/Hz AEG ECO PLUS 35PIH AEG ECO PLUS 50PIH AEG ECO PLUS 71PIH 220-240V ~50/60Hz AEG ECO PLUS 85PIH AEG ECO PLUS 100PIH AEG ECO PLUS 140PIH AEG ECO PLUS 100PIH3...
Page 42
Duct Type Unit Install a circuit breaker near the outdoor units with at least 3mm contact gap. ②. The units must be able to be plugged or unplugged. Circuit breaker and power cord specifications listed in the above table are ③.
Page 43
Duct Type Unit (2) For strand wires (as shown below): 1) Use wire cutters to cut off the wire end and then peel away about 10mm of the insulation layer. 2) Use a screwdriver to unscrew the terminal screw on the terminal board.
Page 44
Duct Type Unit ring. The engineering electric wires (live wire, neutral wire, earthing wire and communication cable) should pass through the buckle magnetic ring before entering into the unit. The magnetic ring should be fixed reliably by cable tie. The engineering wires and buckle magnetic ring are not allowed to touch sharp edges.
Page 45
(Insulators must be clamped securely; otherwise, electric leakage may occur.) (6) Ground wire should be connected. (4) Wire between indoor and outdoor units. Single-phase unit: AEG ECO PLUS 35PIH, AEG ECO PLUS 50PIH. ADG ECO PLUS 35PH+AEG ECO PLUS 35PIH ADG ECO PLUS 50PH+AEG ECO PLUS 50PIH Power cords 3×1.5mm...
Page 46
Duct Type Unit Single-phase unit: GUD71W1/NhA-S, GUD85W1/NhA-S ADG ECO PLUS 71PH+AEG ECO PLUS 71PIH ADG ECO PLUS 85PH+AEG ECO PLUS 85PIH Power cords 3×2.5mm ①. Power cords 4×1.0mm ②. Communication cords 2×0.75mm ③. Single-phase unit: AEG ECO PLUS 100PIH, AEG ECO PLUS 140PIH...
Page 47
Duct Type Unit ADG ECO PLUS 100PH+AEG ECO PLUS 100PIH ADG ECO PLUS 100PH+AEG ECO PLUS 100PIH ADG ECO PLUS 140PH+AEG ECO PLUS 140PIH Power cords 3×4.0mm ①. Power cords 4×1.0mm ②. Communication cords 2×0.75mm ③. Three-phase unit: AEG ECO PLUS 100PIH3, AEG ECO PLUS 140PIH3, AEG ECO PLUS 160PIH3 ADG ECO PLUS 100PH+AEG ECO PLUS 100PIH3 ADG ECO PLUS 140PH+AEG ECO PLUS 140PIH3...
Page 48
Duct Type Unit WARNING! (2) Do not bundle up the connection wire and communication wire of wired control or lay them side by side, otherwise errors will occur. (3) High and low voltage wires should be secured separately. Secure the former ones with big clamps and the latter ones with small clamps.
Page 49
Duct Type Unit Model: ADG ECO PLUS 71PH, ADG ECO PLUS 85PH Model: ADG ECO PLUS 100PH, ADG ECO PLUS 140PH, ADG ECO PLUS 160PH...
Page 50
Wire routing of outdoor unit: AEG ECO PLUS 35PIH, AEG ECO PLUS 50PIH, AEG ECO PLUS 71PIH, AEG ECO PLUS 85PIH. Single-phase: AEG ECO PLUS 100PIH, AEG ECO PLUS 140PIH...
Duct Type Unit 2.4 Check after Installation Check Items after Installation. Possible events due to improper installation Check items Is the main body installed The unit may fall down, vibrate or produce noise. securely? Did you do water leakage test? Cooling capacity may become unsatisfactory.
Page 52
Duct Type Unit Operation after connecting the power: (1) If all the above works are finished, power on the unit. (2) If the outside temperature is more than 30°C, heating mode can’t be enabled. (3) Make sure the indoor and outdoor units can run normally. (4) If there’s sound of liquid shock when the compressor is running, then stop the air conditioner immediately.
Duct Type Unit 3 Product Introduction 3.1 Overall Layout NOTES: The connection pipe, drain pipe, power cord, and duct for this unit should be ①. prepared by the user. The unit is standard equipped with rectangular duct. ②.
Duct Type Unit 3.2 Standard Accessories Indoor Unit Accessories Name Appearance Q'ty Usage Wired Controller To control the indoor unit. To fix the hook on the Nut with Washer cabinet of the unit. To be used together with the hanger bolt for installing the unit.
Duct Type Unit Outdoor Unit Accessories Name Appearance Q'ty Usage 0 or 3 or To plug the unused drain Drain Plug 4 or 5 hole. Drainage To connect with the hard Connector PVC drain pipe. For engineering Buckle magnetic installation. (only AEG ring+ Cable tie ECO PLUS 140PIH3, AEG ECO PLUS 160PIH3...
Duct Type Unit 5 Maintenance 5.1 Failures Not Caused by Faults of the AC (1) If your air conditioner fails to function normally, please first check the following items before maintenance: Problem Cause Corrective measure If you turn off the unit and then immediately turn it on, in order to protect the compressor and avoid Please wait for a while.
Page 57
Duct Type Unit (2) The following situations are not operation failures. Problem Time of occurrence Cause If the unit is running under Mist comes from high humidity, the wet air in During operation. the air conditioner. the room will be quickly cooled down.
Duct Type Unit NOTE: Check the above items and adopt the corresponding corrective measures. If the air conditioner continues to function poorly, please stop the air conditioner immediately and contact Gree’s authorized local service center. Ask our professional service staff to check and repair the unit. 5.2 Error Code WARNING! (1) If abnormal things (for example, awful smell) occur, please stop the unit...
Page 59
Duct Type Unit Error Error code Error Error code Discharge temperature Temperature drift protection sensor error Condenser Driveboard ambient meso-temperature sensor temperature sensor error error Compressor dial code or Bus high-voltage protection jumper cap abnormal Compressor driver memory Bus low-voltage protection chip failure Wired controller Input AC voltage error...
Page 60
Duct Type Unit Error Error code Error Error code Outdoor ambient DC indoor fan driver module temperature sensor error high temperature protection DC indoor fan driver module Recycling refrigerant mode temperature sensor error DC indoor fan driver memory Ordinary defrosting state chip error DC indoor fan driver charge Overload protection...
Duct Type Unit 5.3 Unit Maintenance NOTES! (1) Before cleaning, please make sure the unit is stopped. Cut the circuit breaker and remove the power socket, otherwise, electric shock may occur. (2) Do not wash the air conditioner with water, otherwise fire hazard or electric shock may occur.
Duct Type Unit 5.3.3 Drainage Pipe Periodically check if the drainage pipe is blocked to smooth the condensate water. 5.3.4 Notices at the Beginning of the Using Season (1) Check if the air inlet/outlet of indoor/outdoor unit is blocked. (2) Check if the ground connection is reliable. (3) Check if the battery of remote controller is replaced.
Page 63
Duct Type Unit 5.4.1.2 Work Procedure Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapour being present while the work is being performed. 5.4.1.3 General Work Area All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out.
Page 64
Duct Type Unit disperse any released refrigerant and preferably expel it externally into the atmosphere. 5.4.1.8 Checks to the Refrigeration Equipment Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed.
Page 65
Duct Type Unit (2) That no live electrical components and wiring are exposed while charging, recovering or purging the system. (3) That there is continuity of earth bonding. 5.4.2 Repairs to Sealed Components (1) During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc.
Page 66
Duct Type Unit 5.4.4 Cabling Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of ageing or continual vibration from sources such as compressors or fans.
Page 67
Duct Type Unit 5.4.7 Charging Procedures In addition to conventional charging procedures, the following requirements shall be followed. (1) Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.
Page 68
Duct Type Unit (4) Pump down refrigerant system, if possible. (5) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system. (6) Make sure that cylinder is situated on the scales before recovery takes place.
Duct Type Unit recovery of flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release.
Page 70
REGULATION (EU) N. 517/2014 - F-GAS The unit contains R32, a fluorinated greenhouse gas, with global warming potential (GWP) = 675. Do not release R32 into the environment. AEG ECO PLUS 35PIH Kg. 0,78 = 0,53 Tonn CO2 equiv. AEG ECO PLUS 50PIH Kg.