1. Make sure that the correct fuse rating has been selected. Choosing the right fuse will also prevent
overheating of the alternator and/or DC cabling.
2. Check for loose/high resistance connections and ensure that appropriate gauge wiring is used in the
installation.
3. Do not install the Smart BMS unit in a location exposed to high temperature or radiant heat. Relocate the
Smart BMS to a cooler position or provide additional active cooling.
W-B12: Undervoltage warning
Urgent intervention required to prevent system shutdown.
1. Switch off/disconnect loads and recharge the battery.
2. Check charging system and battery for proper operation.
Page 14
Smart BMS 12-200